[CHAPTER 5 OPERATION]
5-13 |
DOOCHPUMP
D. Target Pressure Setup
•
If you don’t know about correct pressure setting, contact the specialist.
•
In case of linked drive operation, when setting up pressure on one drive, setup pressures are
automatically changed for all drives through CAN communication.
•
If you press
key for more than 3 seconds on a mode displaying S of ST group, it changes
to pressure setting screen. At the moment, if you use
key or
key to change the value
to desired setting and press
key, the pressure setting is changed with
screen.
(If you press
key without pressing
key after changing the setting, the setting will not
be changed and the screen will exit from pressure setting change mode.)
If the pressure setting is changed, the high pres
※
sure alarm ( ‘Pr-70’) setting will be automatically
set to the value 2 bar higher than the pressure setting.
E. Checkup on Rotation Direction of Pump
•
It would be correct if the rotation direction is counter clockwise from a viewpoint of fan cover of
the pump. (If the rotation direction is reversed, it cannot generate the normal pressure.)
•
In order change the rotation direction...(Select one of the methods below.)
- Change two from three wires of the motor input.
- Change the value of Parameter ‘dr-20’ to other one.
Содержание Q-Drive NQ-0075-S
Страница 1: ...User Guide Model AC Drive V F D 3 Phase input www doochpump com...
Страница 2: ......
Страница 8: ...SAFETY PRECAUTIONS 6 DOOCHPUMP...
Страница 16: ...CHAPTER 3 EXTERNAL DIMENSION 3 2 DOOCHPUMP 3 2 NQ 0400T H W D W1 D1 Weight NQ 0400T 162 151 229 133 217 3 3kg...
Страница 20: ...CHAPTER 3 EXTERNAL DIMENSION 3 6 DOOCHPUMP...
Страница 22: ...CHAPTER 4 INSTALLATION 4 2 DOOCHPUMP 4 2 Wiring Diagram of Terminals 3 380V 440 AC Input 50 60 Hz...
Страница 27: ...CHAPTER 4 INSTALLATION 4 7 DOOCHPUMP Power Range 5 5 22kW...
Страница 44: ...CHAPTER 5 OPERATION 5 14 DOOCHPUMP...