TROUBLESHOOTING
This section provides a list of the most common burner and boiler failures.
19.1
Burner failures
We have already mentioned that the burner is equipped with a cut-out system, indicated by a light.
It may cut out accidentally, in which case the button light will come on. It can be unblocked by
pressing the button.
FAILURE CAUSE
SOLUTION
- Fuel valve closed
Open it
- No electricity supply to boiler
Check it
- Nozzle defective or dirty
Replace or clean it
- Electrodes badly adjusted
Adjust them
- Timer on automatic
Turn it to manual
BURNER DOES
NOT IGNITE
- Room or boiler thermostat badly adjusted
Correctly adjust it
- Nozzle defective
Replace it
- Photoelectric cell dirty
Clean it
- Fume circuit obstructed
Clean it
FREQUENT
CUT-OUT
- Installation oil filter or burner pump oil filter dirty
Clean it
19.2
Boiler failures
FAILURE CAUSE
SOLUTION
- The pump is not turning
Unblock the pump
RADIATOR
DOES NOT
HEAT UP
- Air in hydraulic circuit
Drain the installation and
the boiler (the automatic
air drain valve cap must
always be loose)
- Burner badly adjusted
Adjust it correctly
- Flue not correctly sealed
Eliminate any leaks
- Flame unstable
Examine the burner
EXCESSIVE
NOISE
- Flue not insulated
Suitably insulate it