9
14
TECHNICAL CHARACTERISTICS
JAKA
HFD/HFS
30 40 50 60
Low temperature
Boiler type
-
heating only
Rated heat output
P
rated
kW 29 40 50 60
Useful heat output
P
4
kW 28,1 39,4 50,8 60,7
Useful heat output (30%)
P
1
kW 8,9 12,1 15,6 18,6
Seasonal space heating energy efficiency
Ƞ
S
% 86 87 86 86
%(PCI)
91,5 94,7 94,5 94,5
Useful efficiency
Ƞ
4
%(PCS)
86,3 89,3 89,1 89,1
%(PCI)
97,5 97 96,3 96,3
Useful efficiency (30%)
Ƞ
1
%(PCS)
92,0 91,4 90,8 90,8
Auxiliary electricity consumption at full load
el
max
kW 0,152 0,161 0,161 0,226
Auxiliary electricity consumption at part load
el
min
kW 0,055 0,056 0,056 0,078
Auxiliary electricity consumption in standby
mode
PSB kW 0,003 0,003 0,003 0,001
Standby heat loss
P
stby
kW 0,106 0,094 0,141 0,182
Emissions of nitrogen oxides
NOx mg/k
Wh
126 105 128 133
Heating temperature adjustment
ºC
60-85
Maximum safety temperature
ºC
110
Maximum pressure for heating mode
bar
3
Heating water volume
Lts
16,2 20,2 24,2 28,2
Water
pressure
drop
mbar 100 204 263 327
Fume
temperature
ºC
213 213 208 200
Volume on fume side
m
3
0,011 0,017 0,023 0,029
Maximum fume flow
Kg/s 0,0132 0,0186
0,0245 0,0299
Fume
pressure
drop
mbar
0,17 0,18 0,20 0,22
Combustion
chamber
length
mm
300 400 500 600
Combustion chamber type
-
wet, with three fume outlets
Burner adjustment type
-
ON/OFF
Electrical supply
-
~220-230 V - 50 Hz - 200 W
Gross
weight
Kg
110 135 160 185
Содержание Jaka HFD
Страница 1: ...INSTALLATION AND OPERATING INSTRUCTIONS JAKA HFD JAKA HFS ER 0170 1996 CGM 04 392 ...
Страница 21: ...19 17 SPARE PARTS LIST 1 2 3 4 5 6 7 ...
Страница 26: ...Jaka HFD HFS 24 NOTES ...
Страница 27: ...25 NOTES ...