10.- FAILURES 

This section provides an index of the most common failures in both the burner and boiler. 

10.1.- Burner failures 

It has already explained that the burner is equipped with a locking system indicated by a 
light, and it could unintentionally occur that it becomes locked making the push button 
be put on. In this case, unlock it by pressing the push button. 

FAILURE CAUSE 

REMEDY 

 

- Oil valve closed 

Open 

 

- Power supply is not reaching the boiler 

Check 

IT DOES NOT 

PUT ON 

- Nozzle faulty or dirty 

Replace or clean 

 

- Poorly-adjusted electrodes 

Adjust 

 

- Timer at automatic position 

Set it to manual 

 

- Poorly-set room or boiler thermostat  

Set properly 

 

- Nozzle faulty 

Replace 

FREQUENT  - Flame sensor dirty 

Clean 

LOCKING 

- Fume circuit clogged 

Clean 

 

- Oil filter or burner pump dirty 

Clean 

10.2.- Boiler failures 

FAILURE CAUSE 

REMEDY 

RADIATOR 

- The pump does not rotate 

Unlock the pump 

DOES NOT 

HEAT 

- Air in hydraulic circuit 

Purge the installation 
and boiler (The air vent 
plug is always to be 
loose) 

 

- Poorly-adjusted burner 

Adjust properly 

EXCESSIVE  - There is no sealing on the uptake 

Eliminate the leakage 

NOISE 

- Unstable flame 

Check the burner 

 

- Uptake with no thermal insulation 

Insulate properly 

 

 

 

UK ADDRESS 

   

 

HEADQUARTERS & FACTORY 

Unit D4 Stanlaw Abbey Business Centre, 

Bº San Esteban s/n

 

Ellesmere Port, CH65 9BF

    

 

20737 ERREZIL (Gipuzkoa) 

Tel: 0151 909 6222 

   

 

Tel: (+34) 943 813 899 

www.domusateknik.com 

 

DOMUSA TEKNIK

 reserves the right to make modifications of any kind to its product 

characteristics without prior notice.

*CDOC000079* 

CDOC000079 

07/16

Содержание granada

Страница 1: ...ALLATION AND OPERATING INSTRUCTIONS GRANADA This instruction manual includes all the details necessary for the proper installation and use of the boiler We thank you for having chosen a DOMUSA TEKNIK boiler ...

Страница 2: ...EGULATOR MOUNTING 3 2 INSTALLATION WATER FILLING 3 3 SAFETY LOCKING 3 3 1 TEMPERATURE SAFETY LOCKING 3 3 2 BURNER LOCKING 4 4 BOILER OPERATING 4 4 1 OPERATING WITH FIREWOOD 4 4 2 OPERATING WITH OIL BURNER 4 5 BOILER STOP 4 6 EQUIPMENT DELIVERY 4 7 BOILER MAINTENANCE 4 8 DIMENSIONS 5 9 ELECTRICAL DIAGRAM 6 10 FAILURES 7 10 1 BURNER FAILURES 7 10 2 BOILER FAILURES 7 ...

Страница 3: ...d it will never be less than the boiler outlet diameter Note If the design of the uptake is not capable of generate the necessary depression it can be possible to have a reduction in the quantity of combustion air reducing the heating output kW produced by the boiler 1 3 Hydraulic installation The hydraulic installation is to be carried out by skilled personnel complying with the installation stan...

Страница 4: ...isplacing the plastic tube and placing the lever over the horizontal plane Slide the lever in such a position that allows to open and close the boiler charge door Fix the lever with the screw Ignite the boiler and wait for the temperature reaches the desired one in the thermometer Then turn the draught regulator up to the temperature shown in the thermometer With the principal air inlet door close...

Страница 5: ...rder to switch on the boiler The burner will be put on The burner will stop when the boiler has reached the temperature selected in the control thermostat 5 BOILER STOP Set the main selector to ON position in order to switch on the boiler 6 EQUIPMENT DELIVERY The Technical Assistance Service once the first start up has been carried out will explain the boiler operation to the users by informing th...

Страница 6: ... 5 8 DIMENSIONS 290 VS IC RC 180 700 1330 1075 650 235 160 255 1000 IC Heating outlet RC Heating inlet VS Pressure relief valve ...

Страница 7: ... 6 9 ELECTRICAL DIAGRAM 1 2 3 4 5 6 B RT 1 C IG 2 C TC TS Black Red Green 7 8 1 2 5 Blue Brown Blue White P B Burner P Pump RT Room thermostat TC Control thermostat TS Security thermostat ...

Страница 8: ...Replace FREQUENT Flame sensor dirty Clean LOCKING Fume circuit clogged Clean Oil filter or burner pump dirty Clean 10 2 Boiler failures FAILURE CAUSE REMEDY RADIATOR The pump does not rotate Unlock the pump DOES NOT HEAT Air in hydraulic circuit Purge the installation and boiler The air vent plug is always to be loose Poorly adjusted burner Adjust properly EXCESSIVE There is no sealing on the upta...

Отзывы: