Evolution EV HFC
34
23.6
Technical specifications
MODEL EVOLUTION
EV
20 HFC
EVOLUTION EV
30 HFC
EVOLUTION EV
40 HFC
Consumption max. Kg/h.
1,6 2,5 3,4
Power kW.
19 30 40
Motor power
200 W
Functioning type
Todo o nada
Power supply
220 V - 50 Hz
23.7
Nozzles
Evolution
boilers are supplied with the burner fitted, together with its corresponding nozzle and a
standard pre-adjustment. The following table shows the nozzles and adjustments for each
particular model:
MODEL Nozzle
Burner pressure
(bar)
Air adjustment Line adjustment
EVOLUTION EV 20 HFC
0,40/ 80º H
15
6,5
1
EVOLUTION EV 30 HFC
0,60/ 60º H
11
4,5
1
EVOLUTION EV 40 HFC
0,60/ 45º H
18,5
4
1
23.8
Electrical connection diagram
1
2
5
6
8
10
11
12
3
FR
TR
MB
EV1
LB
RP
Black
Blue
TC
TS
Ph
N
4
EV2
Pre-heater
F
7
TP
Brown
Blu
e
Br
ow
n /
Bla
ck
TC:
Boiler Thermostat.
TS:
Safety Thermostat.
F:
Fuse.
LB:
Cut-off Light.
FR:
Photocell.
TR:
Transformer.
MB:
Oil Pump Motor.
EV:
Valve.
RP:
Pre-heater resistance.
Ph:
Phase.
N:
Neutral.
TP:
Pre-heater thermostat.