LAB1199R, Issue 4, Apr 2017

 

 

 

Page 26 

 

 

6.0

 

Maintenance 

 

6.1       Routine maintenance 

 

6.1.1  The two appliance G3 filters should be cleaned on a regular basis, the exact frequency will 

be determined by individual living conditions. 

 

6.1.2  The word ‘FILTER’ will appear on the home screen of the digital user-interface after the 

set time has elapsed – when this occurs, clean the filters – see 5.1.4 for resetting details. 

 

6.1.3    Before cleaning the filters, turn off the appliance at the isolator switch. 

 

6.1.4  To remove the two filters, pull out the two caps from the front of the appliance and gently 

slide out the filters in their carrier frames. 

 

6.1.5   Lightly vacuum the filters to remove surface debris and then gently wash through in warm 

soapy water. Ensure that the filters are completely dry before refitting. 

Important:

 do not 

dry on a radiator or use excessive heat as this may distort the carrier frames. 

 

7.0 Faults 

 

7.1 Fault finding 

Caution - the electrical supply to the unit and from any external triggers into the unit must 

be isolated before removing covers to electrical connections. 

Fault 

Checks and possible solutions 

Nothing displayed on the 

controller LCD screen 

  Check there is power connected to the unit.  

Presence of an orange light visible from 

outside the white wiring centre box will 

indicate this. 

  Check the electrical connections between 

VCC (on controller) and 5V (on PCB) 

  Check the electrical connections between 

GND (on controller) and GND (on PCB) 

‘Unconnect’ displayed on the 

controller LCD screen 

  Check the electrical connections between TD 

(on controller) and RXD (on PCB) 

  Check the electrical connections between RX 

(on controller) and TXD (on PCB) 

‘Fail’ displayed on the 

controller LCD screen 

  If relevant, check with the building 

management services team if the external 

inhibit function has been activated 

  If connected, check the smoke detector isn’t 

activating the external inhibit function 

  If no external inhibit control is connected, 

check there is a link wire present between the 

two terminals of the external inhibit connection 

on the main PCB 

  Check the electrical connections of the 

aforementioned link wire between the two 

terminals of the external inhibit on the main 

PCB 

 

 

LAB1199R, Issue 4, Apr 2017

 

 

 

Page 7 

 

297 dry-trap and condensate drainage kit 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

 

 
 

V E N T I L A T I O N

 

 
 

 

 
 

V E N T I L A T I O N

LAB1306R, Issue 1, March 2018 

Page 14

Содержание Bluebrain

Страница 1: ...1306R Issue 1 March 2018 Page 1 SPR418 Bluebrain Controller Installation and Operating Instructions It is important to follow the advice in this manual and correctly maintain the system to ensure a he...

Страница 2: ...appliance Cleaning and user maintenance shall not be made by children without supervision 3 All wiring must be in accordance with the current IEE Wiring Regulations BS7671 The electrical installation...

Страница 3: ...V E N T I L A T I O N LAB1306R Issue 1 March 2018 Page 3 Page 16 1 0 User control interface operation User control interface front view User control interface back view Day...

Страница 4: ...DAY The hour text will flash Use the and buttons to set the hour Press DAY The minute text will flash Use the and buttons to set the minute Press DAY The day will flash Use the and buttons to set the...

Страница 5: ...ic bypass operation Press COPY four times to move to Menu 7 IhuN Use the or button to set to off OF This action inhibits the automatic humidity controlled boost operation Press SET to return to the ho...

Страница 6: ...ow speed cannot be set higher than Boost speed and Boost speed cannot be set higher than Max speed Press SET to record or ESC to discard the settings and return to the home screen 1 4 Automatic heat e...

Страница 7: ...Press COPY as required to move to Menu 1 Filter Use the or buttons to change the time delay in steps of 50 hours as required or off Note The filter check reminder is factory set at the maximum of 3000...

Страница 8: ...Use the or button to set to on or off Note The Delay on function will always be overridden by automatic humidity sensing Press SET to record or ESC to discard the settings and return to the home scree...

Страница 9: ...and is adjustable between 15 C and 25 C Factory default 20 C Use the or buttons to set the operating temperature in steps of 1 C Press SET to record or ESC to discard the settings and return to the h...

Страница 10: ...squares indicate a time period where the unit is in automatic bypass mode i e the unit will monitor the temperatures and open or close the bypass accordingly White squares blank spaces indicate a time...

Страница 11: ...g PROG the day number will be displayed and then the day to copy to by pressing the and buttons the day number will flash When the two correct days have been selected press COPY and the timeline patte...

Страница 12: ...actory settings P1 t3 20 C t4 10 C Humidity 60 Filter 3000 hours Fan 1 Low 20 Fan 1 Boost 50 Fan 1 Max 80 Fan 2 Low 20 Fan 2 Boost 50 Fan 2 Max 80 Bypass temp off T5 Delay on off Delay off off Hum on...

Страница 13: ...LAB1199R Issue 4 Apr 2017 Page 25 V E N T I L A T I O N LAB1306R Issue 1 March 2018 Page 13...

Страница 14: ...isolated before removing covers to electrical connections Fault Checks and possible solutions Nothing displayed on the controller LCD screen Check there is power connected to the unit Presence of an o...

Страница 15: ...ct connection check there is nothing obstructing fan 2 Little or no air is extracting or supplying through the room valves Check that the filters have been removed from the pre commissioning protectiv...

Страница 16: ...715523 Web www domusventilation co uk E OE V E N T I L A T I O N V E N T I L A T I O N Domus Ventilation Cambria House Caerphilly Business Park Van Road Caerphilly CF83 3ED Tel 44 0 3443 715523 Fax 44...