Rectifying faults
11
Guarantee
The statutory warranty period applies. If the product is defective, please contact the
manufacturer's branch in your country (see the back of the instruction manual for the
addresses) or your retailer.
For repair and guarantee processing, please include the following documents when
you send in the device:
•
A copy of the receipt with purchasing date
•
A reason for the claim or description of the fault
Fault
Cause
Remedy
No output voltage
No contact to the battery
Check contact and cable.
Switch on the ignition if
necessary.
No output voltage
Overheating
Switch off power consuming
devices.
Let the inverter cool down
and ensure better ventila-
tion.
No output voltage
Defective fuse (in the inverter or
the vehicle)
Replace the the fuse with
one of the same specifica-
tions.
No output voltage
Device defective
Replace the device.
The device switches on
and off repeatedly
Excessive constant load
Reduce the load.
The inverter switches off
when the consumer is
switched on
Starting current too high
Compare the device power
with the maximum power of
the inverter.
The output voltage is too
low.
Batter voltage below 21,5 V
Charge the battery (start the
engine).
PP604--IO-EN-ZH.book Seite 13 Donnerstag, 2. November 2017 11:41 11
Содержание PERFECTPOWER PP604
Страница 2: ...PP604 IO EN ZH book Seite 2 Donnerstag 2 November 2017 11 41 11...
Страница 16: ...ZH PerfectPower 16 1 A I 2 2 1 2 2 PP604 IO EN ZH book Seite 16 Donnerstag 2 November 2017 11 41 11...
Страница 22: ...ZH PerfectPower 22 10 11 12 M 21 5 V PP604 IO EN ZH book Seite 22 Donnerstag 2 November 2017 11 41 11...