SETTINGS MENU
DEFINITIONS
:
CAP
- Effective capacity of battery: the initial capacity from the factory. Please set according to the
actual effective capacity of the battery bank to view the accurate capacity percentage
FULL V
- Full capacity voltage: the capacity value is automatically set to 100% after the voltage
is exceeded (Filled up).
Zero V
- Zero capacity voltage: The capacity value is automatically set to 0% if below this voltage.
The voltage value will flash and the buzzer will alarm once per 10s if the discharge continues
(Zero clearing)
PowOFF
- Shutdown voltage: Backlight and LCD off and no display if below this capacity
Alarm
- Low capacity alarm: The percentage and battery symbol will flash and the buzzer wil
sound per 10s if below this capacity.
Atten
- Battery attenuation ratio: After the battery capacity cumulatively once per cycle, the capacity
value is automatically changed according to this ratio.
Do not set Full V and Zero V without understanding the voltage characteristics of
the battery bank (full voltage and vent voltage). The factory default of Full V and
Zero V is 0V, which is invalid.
USING THE SETTINGS MENU:
1 Press the key for 3s to enter setting menu;
2. Click or
key to select the setting items.
INITIAL SET UP:
Calibration is required when the GP-BMK-25 is connected for the first time, or your battery bank
is being replaced.
If you are starting with a full battery, on the main screen hold the
key for 3s to set the
capacity to 100%.
If you are starting with an empty battery, h
old the
key for 3s while on the main screen
to set the capacity to 0%.