Service codes
DSP-EM
6
4
Service codes
Service code
Description
Range
Stand
ard
value
Device
S-00
Setting of the
connected devices
only battery sensor MCA-HS1
1
3
Display
only MCA battery charger
2
Battery sensor MCA-HS1 and MCA bat-
tery charger
3
only DSP-T inverter
4
Battery sensor MCA-HS1 and
DSP-T inverter
5
MCA battery charger and DSP-T inverter
6
Battery sensor MCA-HS1, MCA battery
charger and DSP-T inverter
7
DSP-C inverter
8
Battery sensor MCA-HS1 and
DSP-C inverter
9
S-01
Output voltage
Sets the output voltage of the inverter.
230 V or 240 V
230 V
DSP-T, DSP-C
S-02
Output frequency
Sets the frequency of the output voltage. 50 Hz or 60 Hz
50 Hz
DSP-T, DSP-C
S-03
Standby mode
Switches standby mode ON/OFF.
ON, OFF
ON
DSP-T, DSP-C
S-04
Standby timer
Sets the time in standby mode after
which the inverter switches off.
OFF, 5 min to 30 min
in 5 min intervals,
1 h to 24 h
in 1 h intervals
20 min
DSP-T, DSP-C
S-05
Standby delay
Sets the time after which the inverter
switches to standby mode if no load is
present.
10 s, 1 min to 10 min
10 s
DSP-T, DSP-C
S-06
Standby threshold
Sets the power at which the inverter is
activated from standby mode.
OFF, 1 W, 5 W to 45 W
1 W
DSP-T, DSP-C
S-07
DC high-voltage
shutdown
Sets the upper voltage value at which
the inverter switches off.
15 V to 16.5 V
in 0.1 V intervals
16.5 V
DSP-T, DSP-C
S-08
Upper DC restart
voltage
Sets the voltage at which the inverter
switches on again after a high-voltage
shutdown.
no recovery,
13 V to 16.4 V
in 0.1 V intervals
15.5 V
DSP-T, DSP-C
S-09
DC low-voltage
shutdown
Sets the lower voltage value at which the
inverter switches off.
10 V to 11.5 V
in 0.1 V intervals
10.5 V
DSP-T, DSP-C
S-10
lower DC restart
voltage
Sets the voltage at which the inverter
switches on again after a low-voltage
shutdown.
no recovery,
10.1 V to 14.5 V
in 0.1 V intervals
12.5 V
DSP-T, DSP-C
S-11
Advance warning
setting
Sets the value from which an imminent
switch off is displayed.
OFF,
0.1 V to 2.0 V
in 0.1 V intervals
0.5 V
DSP-T, DSP-C
S-12
Battery type
Sets the battery type.
0: Lead acid
1: Gel
2: AGM
3: eStore
4: Custom
0
IBS and IBS
multiplexer
S-13
Battery capacity
Sets the capacity of each battery sensor.
10 Ah to 249 Ah
100 Ah
IBS and IBS
multiplexer
S-14
Battery charging
current
Sets the maximum battery charging
current, as a percentage of the rated
charging current.
25 %, 50 %, 75 %,
100 %
50 %
DSP-C