Dometic AH-Passport I/O Compact Скачать руководство пользователя страница 29

29

EN

Passport I/O Digital Controls Disposal

Problem

Possible Causes

Recommended Solution

The display does 

not show the 

correct room 

temperature. 

(continued)

The temperature displayed is too high.

•  If the temperature displayed is within 50 °F above the actual 

temperature, use calibration parameter 4 to adjust.

•  If the temperature displayed is hotter than 50 °F above the 

actual temperature, adjust the JP5 jumper on the unit’s circuit 

board.

•  See the alternate air temperature sensor note. 

The temperature displayed is too low.

•  If the temperature displayed is within 50 °F below the actual 

temperature, use calibration parameter 4 to adjust.

•  If the temperature displayed is colder than 50 °F below the 

actual temperature, adjust the JP5 jumper on the unit’s circuit 

board.

•  See the alternate air temperature sensor note.

The temperature adjusts too quickly or still 

does not read correctly. 

Relocate the display or the alternate air temperature sensor. The 

supply air should not blow on or near a sensor. Locate alternate 

air temperature sensors in the return air stream, not physically 

touching any part of the unit. 

 

I

Alternate air temperature sensor note: if the unit uses an 

alternate air temperature sensor, it will be either an RJ11 4-pin 

3,000 K sensor or an RJ12 6-pin 10,000 K sensor.  

 

If the 6-pin sensor is installed, the JP5 jumper must be 

removed from the board. If neither sensor is installed on the 

circuit board, the display reads from its own built-in sensor, if 

applicable. 

A low pump-flow 

fault is present, if 

applicable.

The condenser coil is too hot. 

Verify the unit receives water flow and the condenser is not fouled.

The thermistor is damaged.

•  Unplug the water sensor if installed.
•  Install another thermistor if one is available.

There is a damaged jack/socket on the 

circuit board.

Visually check to verify the pins inside the socket are not bent or 

corroded. Repair or replace the circuit board if needed.

A filter reminder 

is presented.

The timer setting to clean or replace the 

filter has been reached.

Clean or replace the filter and reset the filter hours.

10 Disposal

 

M

Place the packaging material in the appropriate 
recycling waste bins, whenever possible. Consult 
a local recycling center or specialist dealer for 
details about how to dispose of the product in 
accordance with all applicable national and local 
regulations.

11  Warranty Information

LIMITED WARRANTY AVAILABLE AT DOMETIC.COM/
EN-US/TERMS-AND-CONDITIONS-CONSUMER/
WARRANTY
.

IF YOU HAVE QUESTIONS, OR TO OBTAIN A COPY 
OF THE LIMITED WARRANTY FREE OF CHARGE, 
CONTACT:

DOMETIC CORPORATION 
MARINE CUSTOMER SUPPORT CENTER 
2000 NORTH ANDREWS AVENUE 
POMPANO BEACH, FLORIDA, USA 33069 
1-800-542-2477

Содержание AH-Passport I/O Compact

Страница 1: ...0420 2021 Dometic Corporation WARNING Cancer and Reproductive Harm www P65Warnings ca gov Passport I O Legacy Passport I O Compact AH Passport I O Legacy AH Passport I O Compact EN Passport I O Digita...

Страница 2: ...enter Dealer Locations Visit www dometic com Please read these instructions carefully and follow all instructions guidelines and warnings included in this product manual in order to ensure that you in...

Страница 3: ...nings could result in death or serious injury Use only Dometic replacement parts and components that are specifically approved for use with the appliance Avoid improper installation adjustment alterat...

Страница 4: ...tional Parts Air Filter Cleaning or Replacement Timer2 x x Alternate Air Temperature Sensor x x Low Voltage Monitor2 x Outside Air Temperature OAT Sensor x x Plastic Bulkhead Adapter x x Condenser Coi...

Страница 5: ...ent mode 4 Specifications The following table lists the dimensions cable lengths system inputs and operational specifications for the Passport controls 4 1 Product Dimensions Display Panel Dimensions...

Страница 6: ...VAC Low Voltage Processor Reset 50 VAC Universal Line Voltage 100 240 VAC Frequency 50 Hz or 60 Hz Fan Output 6 A 100 120 VAC 6 A 208 240 VAC Valve Output 5 A 100 120 208 240 VAC For DX Only Passport...

Страница 7: ...ssport controls Run Capacitor Low Pressure Switch High Pressure Switch Comp L1 Pump L1 Pump L2 Blue Orange Black Fan L1 Comp L2 Compressor Display Jacks Inside Temperature Sensor Jack Not Active GND 0...

Страница 8: ...ocate the display panel in direct sunlight near any heat producing appliances or in a bulkhead where temperatures radiating from behind the panel may affect performance Do not mount the display in the...

Страница 9: ...onal Sensor 1 Mount the optional sensor according to the installation instructions included with the sensor 2 Plug the sensor cable into the appropriate sensor jack on the upper side of the control bo...

Страница 10: ...ture set point by 2 F 1 C and starts a heating cycle once the cabin temperature falls below the temperature set point by 2 F 1 C The system continues the cycle until the cabin temperature equals the s...

Страница 11: ...th firmware B30 or newer When interrupting a cycle by pressing the Power button on the display or changing the set point using the display panel To reduce reversing valve noise the default limits unne...

Страница 12: ...hour without the same recurring fault clears the fault counter but the event remains in the service history log until overwritten If a different fault occurs during the hour it shows on the service h...

Страница 13: ...utton On All Passport control outputs are on and the display indicates the current state of operation The display shows the cabin temperature All parameters operate as set To turn on the Passport cont...

Страница 14: ...enever the system is in ON mode or it can be set to cycle between ON and OFF mode in conjunction with the cooling or heating cycles Program menu setting P 14 determines the fan operational setting CYC...

Страница 15: ...lease the Power button 2 While the display shows tSt the following commands cycle continuously a Hr displays for one second b The display blanks out for one second then displays for three seconds a tw...

Страница 16: ...ll indicators for one second and flashes 888 on the display then resumes operating according to the last program settings The Passport control has factory default values stored in permanent memory mem...

Страница 17: ...of the unit 7 3 5 Selecting a Parameter The following table lists the factory default parameter settings for the Passport controls Parameter Name DX CW Factory Default Parameter Range P 1 Operating Mo...

Страница 18: ...ure The setting of 2 should only be used if a setting of 1 does not prevent evaporator ice from forming P 9 Optional Pump Sentry x OFF OFF ON Select 100 F to 150 F 38 C and 66 C Set this parameter set...

Страница 19: ...nal electric heater that exceeds this load it is necessary to install an additional contactor that is rated to handle the full load of the electric heater P 16 Fan Motor Selection x x SC SC Split Capa...

Страница 20: ...r Down buttons Calibrating this parameter provides a more accurate voltage level when calculating low voltage for parameter P 7 Use a reliable voltmeter during adjustment IAvailable only in software v...

Страница 21: ...ay x PLF Low Pump Flow Fault indicates a high water temperature in the condensing coil or low pump flow x Fail Safe Levels Lvl Description DX Only 0 Fail Safe Level 0 Provides minimal failsafe protect...

Страница 22: ...ing Heating P 14 Cycle Fan With Compressor P 15 Reverse Cycle or Electric P 16 Fan Motor Selection P 17 Reset Memorized Defaults P 18 Reserved P 19 Reserved P 20 Air Filter Cleaning Replacement Timer...

Страница 23: ...ump is on a separate circuit breaker be sure to turn it ON 4 Turn the Passport control ON 5 Press the Fan button 6 Verify that the fan is running and that a steady airflow is coming out of the supply...

Страница 24: ...cleaning of the system 9 Provide additional cleaning as necessary for extreme contaminations 8 6 Winterizing the System DX Systems Only Any winterization method that causes the antifreeze solution to...

Страница 25: ...heat if reverse cycle option is installed in water as low as 40 F 4 C The alternate air temperature sensor is not located properly Verify the display location with the criteria found in the installati...

Страница 26: ...all a service technician if that does not correct the problem The seawater temperature is too low Seawater temperature directly affects the unit s efficiency For the unit to heat if the reverse cycle...

Страница 27: ...a low pressure switch ensure the JP2 jumper on the board is in place over both pins Disable the parameter if applicable The low pressure switch is open due to low seawater and or low return air temper...

Страница 28: ...tromagnetic interference from other equipment or similar power related issue Perform a factory reset of the display 1 Turn the power off 2 Disconnect the cable from the display 3 Turn the power on wai...

Страница 29: ...3 000 K sensor or an RJ12 6 pin 10 000 K sensor If the 6 pin sensor is installed the JP5 jumper must be removed from the board If neither sensor is installed on the circuit board the display reads fr...

Страница 30: ...30 EN Passport I O Digital Controls...

Страница 31: ...31 EN Passport I O Digital Controls...

Страница 32: ...list of Dometic companies which comprise the Dometic Group can be found in the public filings of DOMETIC GROUP AB Hemv rnsgatan 15 SE 17154 Solna Sweden CONTACT US dometic com en us terms and conditio...

Отзывы: