7.  Start each mounting bolt through the ceiling tem-

plate and up into the unit base pan by hand. Install 

wood screw in each end of the ceiling template. 

This insures a tight fit of the return air cover to 

ceiling. See FIG. 11.

 

Evenly tighten the  four mounting bolts to a 

torque of 40 to 50 inch pounds. This will com-

press the roof gasket approximately 1/2". The 

bolts are self locking so further tightening is 

not necessary. See FIG. 11.

 

8.  Installation of Divider Plate 

 

 

a.  Measure the ceiling to roof thickness:

 

 

 

•  If distance is 2.0" - 3-3/4", remove perfo-

rated tab from divider plate. 

 

 

 

•  If distance is 3-3/4" - 5-1/2", remove no 

tabs.

 

 

b.  Remove the backing paper from double sided 

tape located on ceiling template. See FIG. 12.

FIG. 11

Finger 

Tight

Front of Vehicle

Tighten To Com-

press Gasket To 

1/2"

Roof 

Gasket

Screws

If bolts are left loose there may not be an ad-

equate roof seal or if over tightened, damage 

may occur to the unit base or ceiling template. 

Tighten to torque specifications listed in this 

manual.

FIG. 12

Backing Paper

2.00" -3.75"

 

 

c.  Place divider plate up to bottom of the unit base 

pan firmly. The foam tape on the divider plate 

must seal to bottom of base pan. See FIG. 13.

Note: 

The adhesive on the insulation is extremely sticky. 

Be sure the part is located where desired before pressing 

into place.

 

 

d.  With  slight  pressure  push  the  divider  plate 

against the double sided tape on the ceiling 

template.

 

 

e.  Locate the 1/8" x 7" x 18" self -adhesive insula-

tion supplied with the return air kit. Remove the 

backing paper from the insulation and carefully 

stick onto the ceiling template divider panel. 

See FIG. 14.

 

 

 

•  Excess width is intended to seal the divider 

plate to the sides of the 14-1/4" x 14-1/4" 

(±1/8")  opening. This  is  to  help  prevent 

cold air discharge from circulating into the 

unit return air opening.

 

 

 

•  If the insulation is too high, stick excess 

height of insulation to the unit base pan. 

Do not cover up unit rating plate.

FIG. 13

Improper installation and sealing of divider 

plate will cause the compressor to quick cycle 

on the cold control. This may result in fuse or 

circuit breaker opening and/or lack of cooling. 

Push Divider Plate Firmly 

Onto Base Pan

 

FIG. 14

Place Insulation In Position

(Do Not Cover Unit Rating Plate) Foam Tape

Divider Plate

Содержание 641915

Страница 1: ...e Zone LCD Thermostat Air Conditioner 641915 641916 3105007 XXX OR 3105935 XXX 3313192 XXX Cool Furn 3313193 XXX Cool Furn HP 3313194 XXX Cool Furn HS Air Conditioner W Electric Heat 641935 Heat Pump...

Страница 2: ...ution to high heat gain acces sories like Dometic outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add aniceareatoenjoycompanyduringthecooloftheevening D Con...

Страница 3: ...5 30X 13 500 12 5 61 0 3 5 10 0 17 5 20 Amp 3 5 KW 5 0 KW 651915 30X 13 500 12 5 61 0 3 5 10 0 25 0 20 Amp 3 5 KW 5 0 KW 651916 30X Hi Cap 12 3 61 0 3 3 8 5 24 0 20 Amp 3 5 KW 5 0 KW SPECIFICATIONS Fo...

Страница 4: ...to side 2 For two unit installations Install one unit 1 3 and one unit 2 3 s from front of RV and centered from side to side It is preferred that the unit be installed on a relatively flat and level r...

Страница 5: ...uct System Sizing De sign See Chart On Page 6 The Installer of this system must design the air distri bution system for their particular application Several requirements for this system MUST be met fo...

Страница 6: ...uct Size Depth Width Total Duct Length Duct Length short run 1 1 2 In Min 2 1 2 In Max 7 0 In Min 10 0 In Max 15 0 Ft Min 40 0 Ft Max 1 3 Total Duct Length Register Requirements Number Required Per Ru...

Страница 7: ...d in the front portion of the 14 1 4 x 14 1 4 1 8 open ing b Make sure that at least 15 of supply wire ex tends into the roof opening 3 Route a 3 conductor cable 18 to 22 AWG from the Single Zone LCD...

Страница 8: ...t Slide I Installing The Unit 1 Check gasket alignment of the unit over the roof openingandadjustifnecessary Unitmaybemoved from below by slightly lifting See FIG 8 2 Remove return air cover and ceili...

Страница 9: ...er 2 00 3 75 c Place divider plate up to bottom of the unit base pan firmly The foam tape on the divider plate must seal to bottom of base pan See FIG 13 Note The adhesive on the insulation is extreme...

Страница 10: ...r regulations Disconnect 120 VAC Failure to obey these instructions could create a shock hazard causing death or severe personal injury Thisproductisequippedwitha3wire ground ed system for protection...

Страница 11: ...7 1 7 1 87 51 57 21 21 8 7256 2 86 233 5 9 5 6 1625 5 5 8 20 12 02725 62 5 25 57 7 5 1 725 86 6 5 2 5 8 7 5 67 57 3 5 7 7 5 37 5 237 5 9 56 1 9 9 37 5 237 5 7 7 5 67 57 3 5 7 8 5 2 5 6 287 225 7 03 6...

Отзывы: