background image

5

C.  Roof Preparation

 

1.  Opening Requirements - Before preparing the ceil-

ing opening, the type of system options must be 

decided upon. Read all of the following instructions 

before beginning the installation.

 

2.  Mark a 14-1/4" x 14-1/4" (±1/8") square on the roof 

and carefully cut the opening. The 14-1/4" x 14-1/4" 

(±1/8") opening is part of the return air system of 

the unit and must be finished in accordance with 

ANSI A119.2.

 

3.  Using the roof opening as a guide, cut the matching 

hole in the ceiling.

 

4.  The opening created must be framed to provide 

adequate support and prevent air from being drawn 

from the roof cavity. Framing stock 3/4" or more 

in thickness must be used. Remember to provide 

an entrance hole for power supplies, 3 conductor 

communication cable, and furnace wiring (if ap-

plicable).

Do Not Cut Roof 

Structure Or 

Rafters

Good-Rafters 

Supported By 

Cross Beams

Good Location-

Between Roof 

Rafters

Frame Opening So It 

Won't Collapse When 

Bolting Down Unit

Leave Access For Power 

Supply Wiring

15" Min. At 

Front Of 

Opening

3/4" Min.

FIG. 3

It is the responsibility of the installer of this  

system to ensure structural integrity of the 

RV roof. Never create a low spot on the roof 

where  water  will  collect.  Water  standing 

around  the  unit  may  leak  into  the  interior 

causing damage to the product and the RV.

There may be electrical wiring between the 

roof  and  the  ceiling.  Disconnect  120  VAC 

power cord and the positive (+) 12 VDC  ter-

minal at the supply battery. Failure to follow 

this instruction may create a shock hazard 

causing death or severe personal injury.

 

D.  Air Distribution Duct System Sizing & De-

sign  (See Chart On Page 6)

 

The Installer of this system must design the air distri-

bution system for their particular application. Several 

requirements for this system 

MUST

 be met for the unit 

to operate properly. These requirements are as follows:

 

1.  The duct material must meet or exceed any agency 

or RVIA Standard that may be in existence at the 

time the RV is produced.

 

2.  All discharge air ducts must be properly insulated 

to  prevent  condensation  from  forming  on  their 

surfaces or adjacent surfaces during operation of 

the unit. This insulation must be R-7 minimum.

 

3.  Ducts and their joints must be sealed to prevent 

condensation from forming on adjacent surfaces 

during operation of the unit.

 

4.  Return air openings must have 40 square inches 

minimum free area including the filter.

 

5.  Return air to the unit must be filtered to prevent 

dirt accumulation on unit cooling surface.

 

6.  Air Distribution System Installation

 

 

a.  Dometic,  LLC  recommends  the  basic  con-

figuration shown on page 6, for installing this  

system. We have found by testing, that this 

configuration works best in most applications 

of  this  system. It is  the  responsibility  of  the 

installer of this system to review each RV floor 

plan and determine the following:

It is the responsibility of the installer to insure 

the duct work will not collapse or bend dur-

ing and after the installation. Dometic, LLC 

will not be liable for roof structural or ceiling 

damage due to improperly insulated, sealed 

or collapsed duct work.

Frame

14-1/4" (±1/8")

 Opening

AC Power

Supply Wire

Duct

Frame

Duct

Roof

Insulation

Duct

Ceiling

Duct

14-1/4" (±1/8")

 Opening

Insulation

SIDE VIEW

(TOWARD BACK OF RV)

TOP VIEW

(BACK OF RV)

Low Voltage Wires:

12 VDC

Furnace

  

  

Frame

3 Conductor

Communication

Cable

FIG. 4

Содержание 641915

Страница 1: ...e Zone LCD Thermostat Air Conditioner 641915 641916 3105007 XXX OR 3105935 XXX 3313192 XXX Cool Furn 3313193 XXX Cool Furn HP 3313194 XXX Cool Furn HS Air Conditioner W Electric Heat 641935 Heat Pump...

Страница 2: ...ution to high heat gain acces sories like Dometic outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add aniceareatoenjoycompanyduringthecooloftheevening D Con...

Страница 3: ...5 30X 13 500 12 5 61 0 3 5 10 0 17 5 20 Amp 3 5 KW 5 0 KW 651915 30X 13 500 12 5 61 0 3 5 10 0 25 0 20 Amp 3 5 KW 5 0 KW 651916 30X Hi Cap 12 3 61 0 3 3 8 5 24 0 20 Amp 3 5 KW 5 0 KW SPECIFICATIONS Fo...

Страница 4: ...to side 2 For two unit installations Install one unit 1 3 and one unit 2 3 s from front of RV and centered from side to side It is preferred that the unit be installed on a relatively flat and level r...

Страница 5: ...uct System Sizing De sign See Chart On Page 6 The Installer of this system must design the air distri bution system for their particular application Several requirements for this system MUST be met fo...

Страница 6: ...uct Size Depth Width Total Duct Length Duct Length short run 1 1 2 In Min 2 1 2 In Max 7 0 In Min 10 0 In Max 15 0 Ft Min 40 0 Ft Max 1 3 Total Duct Length Register Requirements Number Required Per Ru...

Страница 7: ...d in the front portion of the 14 1 4 x 14 1 4 1 8 open ing b Make sure that at least 15 of supply wire ex tends into the roof opening 3 Route a 3 conductor cable 18 to 22 AWG from the Single Zone LCD...

Страница 8: ...t Slide I Installing The Unit 1 Check gasket alignment of the unit over the roof openingandadjustifnecessary Unitmaybemoved from below by slightly lifting See FIG 8 2 Remove return air cover and ceili...

Страница 9: ...er 2 00 3 75 c Place divider plate up to bottom of the unit base pan firmly The foam tape on the divider plate must seal to bottom of base pan See FIG 13 Note The adhesive on the insulation is extreme...

Страница 10: ...r regulations Disconnect 120 VAC Failure to obey these instructions could create a shock hazard causing death or severe personal injury Thisproductisequippedwitha3wire ground ed system for protection...

Страница 11: ...7 1 7 1 87 51 57 21 21 8 7256 2 86 233 5 9 5 6 1625 5 5 8 20 12 02725 62 5 25 57 7 5 1 725 86 6 5 2 5 8 7 5 67 57 3 5 7 7 5 37 5 237 5 9 56 1 9 9 37 5 237 5 7 7 5 67 57 3 5 7 8 5 2 5 6 287 225 7 03 6...

Отзывы: