Auto Generator Start (AGS)

On RVs equipped with an optional AGS Kit, the vehicle generator will automatically 

start when any zone calls for cooling and will shut OFF when zones reach set point.
The Auto Generator Start (AGS) function will be implemented by an individual pow

-

er module board configured for this function by setting the 

GEN

 

Start

 DIP switch 

ON. On the AGS power module board a relay shall be used to provide a start signal 

to the generator. The normally open relay contacts are utilized and the closure of 

these contacts provides the signal to start the generator. The AGS relay shall be ac

-

tivated when any zone or stage requires cooling, heat pump or  heat strip operation. 

When a zone calls for heating or cooling, the AGS relay shall be closed, followed 

by a time delay to allow the generator to warm up after which time the output relay 

will be activated on the zone that initiated the heating or cooling request. When the 

heat/cool requests in all zones have been satisfied, the AGS relay will open and the 

generator will shut-down.

J. 

Load Shed 

The Dometic CCC 2 thermostat has provisions for Load Shedding. The AC pow

-

er module board shall provide the 12 Vdc source for the Load Shed signal. This 

 

12 Vdc source shall be turned ON 1 second before the compressor relay when the 

system calls for the compressor to be ON. The Load Shed source shall remain ON 

when compressor is caused to turn OFF due to being disable by either a Freeze 

Sensor or a Load Shed condition. The load shed source signal will be switched to 

the Load Shed input by the normally open contacts or an off-board relay from the RV 

power management system. When the Load Shed signal is detected, the compres

-

sor shall turn OFF.

K. 

Defrost Cycle (Heat Pump Models Only)

To avoid frost formation on the outside coil and to obtain maximum performance 

when  the  outside  temperature  is  less  than  42  °F  (6  °C)  and  greater  than  30  °F 

 

(-1 °C), a defrost cycle will be initiated. While operating in this temperature range the 

compressor continuous run time is limited to 25 minutes. When this time is accumu

-

lated, the fan will shut OFF, the refrigerant flow will be reversed, and the compres

-

sor will continue to run for 4.5 minutes. During this 4.5 minute period, the LCD will 

toggle between HP and Defrost. The refrigerant flow will then be reversed and after 

a 30 second delay the fan will resume operation. This cycle will remove any frost 

formation on the outside coil. This cycle will repeat itself until the outside tempera

-

ture is greater than 42 °F (6 °C). If the outside temperature becomes less than 30 °F 

(-1 °C) the heat pump will shut OFF and the auxiliary heat (if provided) will turn ON.

L. 

Compressor Time Delay

A time delay of approximately 2 minutes occurs any time the compressor is required 

to begin the cooling or heat pump cycle.

SPECIAL FEATURES

Содержание 3314080.000 BLACK

Страница 1: ...t 3 Brantford ON N3T 5L8 CANADA For Service Center Dealer Locations Please Visit www eDometic com COMFORT CONTROL CENTER 2 THERMOSTAT OPERATING INSTRUCTIONS REVISION B Form No 3314149 018 08 16 French 3314169 016_B 2016 Dometic Corporation LaGrange IN 46761 PROGRAMMABLE THERMOSTAT MODEL 3314080 000 BLACK 3314080 015 WHITE ...

Страница 2: ... 2 13 D Examples Of Times Programmed 15 E CANbus Interface 15 F Auxiliary Heat Heat Pump Models Only 16 G Stage Select Two Air Conditioner Heat Pump Units Select Models On One Zone 16 H Stage Select Dual Compressor Air Conditioner Heat Pump Select Models 16 I Auto Generator Start AGS 17 J Load Shed 17 K Defrost Cycle Heat Pump Models Only 17 L Compressor Time Delay 17 M Power Interruption 18 N LCD...

Страница 3: ...t review the following diagrams and accompanying text that explain the functional characteris tics of this system Your CCC 2 thermostat is equipped with a liquid crystal display LCD that identifies the mode of operation OFF Cool Heat Pump Fan Heat Strip Auto Furnace or Aqua temperature set point zone identification 1 2 3 4 fan speed Auto Low Med High program 1 and 2 inside temperature clock F C co...

Страница 4: ...4 In the unlikely event of CCC 2 system memory loss or dip switch setting change the CCC 2 thermostat will require a system reset For system reset procedure see main heading System Reset Procedure on page 19 Your Dometic CCC 2 thermostat has been pre programmed Review settings below and adjust the settings to your personal comfort level Any time the CCC 2 is in an idle stage not illuminated you wi...

Страница 5: ... increase temperature set point Press to select zone Press to select On and OFF Press to select fan speed Press to set clock Press to select mode Press to select program 1 or 2 D Quick Reference To LCD Icons Temperature Set Point or Error Code Operation Mode Time of Day Fan Speed Zone Program Clean or Replace Filter Compressor Delay ABOUT YOUR NEW THERMOSTAT ...

Страница 6: ...tat is in the OFF condition B Clock Setting Press the CLOCK button to initiate the clock setting sub menu on the CCC 2 ther mostat When in this menu the hour digits will flash first The hour can be adjusted using the or buttons Press the CLOCK button again and the minute digits will flash allowing the minute setting to be adjusted using the or buttons Press it a third time and the AM or PM icon wi...

Страница 7: ...EMP button and the LCD will display the current inside temperature recorded at the CCC 2 thermostat or at the optional remote indoor temperature sensor instead of the temperature set point The LCD will also display IN to indicate that the inside temperature is being displayed When the INSIDE TEMP button is released the LCD will return to the programmed temperature set point PROGRAMMING OPERATIONS ...

Страница 8: ...ction B Zone Control on page 13 F Mode Selection Press the MODE button and the LCD will display the first available mode Each successive press will advance to the next available mode Continue to press the MODE button until the desired mode appears Depending on the systems installed your choices will be OFF COOL AUTO HP FURN or AQUA HS and FAN For more information on modes see main heading Mode Des...

Страница 9: ...ing For more information on auto fan see section A Auto Fan on page 12 H Temperature Set Point Press the or button to change the temperature set point The temperature set point is indicated by 2 digits on the LCD Press the button to increase and the button to decrease the temperature set point The maximum set point for the system is 90 F 32 C The minimum set point is determined by the active opera...

Страница 10: ...r shuts OFF first followed by the fan in approximately 15 seconds For more informa tion on auto fan see section A Auto Fan on page 12 C HP Heat Pump Mode In the HP mode the system will cycle the compressor ON and OFF based on the room air temperature and the temperature set point on the CCC 2 thermostat When the system calls for heating there will be a delay of approximately 2 minutes During this ...

Страница 11: ...g is FURN To change the setting from FURN to AQUA or vice versa simultaneously press the and buttons The LED will display the selected option In the FURN AQUA mode the system will cycle the RV s furnace aqua ON and OFF based on the room air temperature and the temperature set point on the CCC 2 thermostat The system can be configured to operate using an ON OFF differential of either 1 F C or 2 F C...

Страница 12: ...ner will cycle OFF Auto Change Over Heating If the room temperature goes below the temperature set point by 2 F C the available heat source will be cycled ON until the room temperature reaches the temperature set point at which time it will cycle OFF If more than one heat source is available on this zone the priority for selecting the heat source will be heat pump first furnace second and heat str...

Страница 13: ...played When the zones have been programmed the zones in operation will be displayed To program each zone simply repeat the programming steps shown under main heading Pro gramming Operations on page 6 C Program 1 2 The Dometic CCC 2 thermostat can store two operating programs Each program can be set on individual zones with different mode and time settings for each zone For each event the user can ...

Страница 14: ...be dis played in the LCD The zone will continue to operate in the programmed setting until the program is manually cancelled To cancel the program operation press and hold the PROGRAM button for 3 sec onds The zone will be restored to normal operation SPECIAL FEATURES ...

Страница 15: ...s Interface The CANbus interface is designed to communicate between the Dometic CCC 2 thermostat and a CAN Controller Area Network protocol generator Refer to the CANbus installation instructions for more information on installation and operation of the CANbus ...

Страница 16: ...will be used for both the primary and the secondary stage air conditioner heat pump Only one indoor temperature sensor is required for this configuration and it must be installed in the power module board configured as the primary control The turn ON time for the compressors and fans will be controlled to ensure that compressors on the system start one at a time A minimum delay of 20 to 30 sec ond...

Страница 17: ...s for the compressor to be ON The Load Shed source shall remain ON when compressor is caused to turn OFF due to being disable by either a Freeze Sensor or a Load Shed condition The load shed source signal will be switched to the Load Shed input by the normally open contacts or an off board relay from the RV power management system When the Load Shed signal is detected the compres sor shall turn OF...

Страница 18: ...eat and cool op eration will be locked out Manual fan operation will continue E3 Shorted Indoor Temperature Sensor All heat and cool operation will be locked out Manual fan operation will continue E4 Open circuit or out of range Outdoor Temperature Sensor select models Heat pump operation will be locked out Air conditioner furnace heat strip and fan operation can continue to operate E5 Open circui...

Страница 19: ... and or curtains Keeping windows and doors shut or minimizing usage Avoiding the use of heat producing appliances Operation on High Fan Cooling mode will give optimum or maximum efficiency in high humidity or high outside temperatures Starting the air conditioner early in the morning and giving it a head start on the expected high outdoor ambient will greatly improve its ability to maintain the de...

Страница 20: ...owing before calling your service center If RV is connected to a motor generator make sure the motor generator is run ning and producing power If RV is connected to a power supply by a land line make sure the line is sized properly to run air conditioner load and it is plugged into the power supply Check the 120 Vac fuse or circuit breaker to see if it is open Make sure fuse is not burnt or circui...

Отзывы: