Leak Sensor Advanced User Manual
Configuration Parameters
Configuration Parameters
Configuration parameters are sent using a standard syntax to ensure interopera-
bility between all manufacturers’ products. All values are represented using the
hexadecimal number system.
Typical syntax is as shown below. Note that the value sent must be the exact size,
in bytes, as accepted by the setting. The “extra” spaces should be filled with zeros
(see the “value” column below.)
Example Configuration Parameter:
02 02 00 0A
Param #
Size
Value
02
(Param #2)
02
(2 Bytes)
00 0A
(10)
Param
#
Size
Name
Available Values
Default
Value
05
This parameter enables or disables the audible alarm (“beeping”) functionality of the Leak Sensor.
01
Enable/Disable Audible Alarm
00
(Audible Alarm Disabled)
01
(Audible Alarm Enabled)
01
(Audible
Alarm
Enabled)
06
This parameter enables or disables the Leak Sensor - if disabled, the device will not respond in any way to detected
leaks.
01
Enable/Disable Water Detection
00
(Water Detection Disabled)
01
(Water Detection Enabled)
01
(Water
Detection
Enabled)
07
This parameter defines the value sent by the BASIC_SET command to Association Group 2 (for more information,
see “Assocation Groups”.)
01
Basic Set Level
00
(0/Turn Off Device)
01 ~ 63
(0-99)
FF
(255/Turn On Device)
FF
(255/Turn
On Device)
Table 6 -
Configuration Parameters