domat US100 

The controller contains real time clock with a weekly scheduler (6 events per day). It 
changes  between three  operation modes: Day, Night, and Off. A short push in the 
Night mode switches to Party mode 

 Comfort extension by 2 hours. 

 
The Change-over function (communicated over the bus) switches to the cooling mode 
while cooling setpoints come into effect. This mode is used when heat pumps with 
change-over mode are installed. The change-over signal is read from the heat pump 
interface  or  a  thermostat  at  the  supply  water  piping,  and  is  transmitted  to  the 
controllers  over  MiniPLC,  UCWEB,  or  any  Modbus  master.  See 

Room  units  and 

controllers, Communication protocol description

 handbook for register addressing and 

communication examples. 
 
The  communication  bus  is  Modbus  RTU  over  RS485,  therefore  the  controllers  are 
easily to integrate into any SCADA or BMS system.  
 

Technical data 
 

Power 

24 V AC +/- 10% 

Consumption 

1,5 W + peripherials (ca. 5VA) 

Measuring range 

-

20 ÷ 50 °C

 

Protection 

IP20 

Sensor accuracy 

according to DIN IEC 751, Class B 

Output - heating 

1x solid state relay, zero switching, for AC load, 24 V AC 
against G0, max. switching current 0,4A; recommended 
thermic actuators are Siemens STA71, Danfoss TWA (24V 
types) etc.  

Outputs - sunblinds 

2x solid state relay, zero switching, for AC load, 24 V AC 

against G0, max. switching current 0,4A 

Input 

24 V AC, 7.5 mA 

Setpoint correction 

according to configuration, +/- 10 to +/- 1 K 

Communication 

2  wire  RS485  -  Modbus  RTU,  slave,  optically  separated, 

1200...115200 bps, bus end switches 

Display 

LCD 60 x 60 mm 

Terminals 

screw terminals for 0,14 

 1,5 mm

2

 wires 

Cover 

ABS, similar to RAL9010

other colours

 

Weight 

0,13 kg 

Dimensions 

see below 

 

 

 

Содержание US100

Страница 1: ...l button The room temperature is measured in the range of 20 to 50 C Measured and set values are processed in a PI algorithm at the output of which there is a PWM controlled triac All values are displayed on a large LCD display The output works either as PWM controlled by a PI controller or on off thermostat The functionality and control parameters i e P and I constants and hysteresis can be set w...

Страница 2: ...essing and communication examples The communication bus is Modbus RTU over RS485 therefore the controllers are easily to integrate into any SCADA or BMS system Technical data Power 24 V AC 10 Consumption 1 5 W peripherials ca 5VA Measuring range 20 50 C Protection IP20 Sensor accuracy according to DIN IEC 751 Class B Output heating 1x solid state relay zero switching for AC load 24 V AC against G0...

Страница 3: ...ller into default state and sets bus address to 1 baud rate to 9600 To init proceed as follows connect the device over RS485 to a PC with ModComTool config tool set INIT to ON apply power use only the connector without bottom find the controller in the tool Scan set INIT to OFF in the ModComTool tool open the controller window click the Init button in the tool remove and apply power Installation U...

Страница 4: ...ot at the top nor bottom Settings Temperature correction Push the right button to increase setpoint push the left button to decrease setpoint The maximum correction range can be modified over the bus e g with the ModComTool configuration tool Sunblind controls Push the up down button shortly to change the slat angle Hold the up down button 1 5 s to travel the sunblind up down Push the down up butt...

Страница 5: ...s to select another weekday After all desired events have been edited long push the central button to leave the time schedule settings The controller goes to the basic display mode also after 30 secs of user inactivity Change of setpoints and controller time Switch to the settings mode with a superlong central button push 2 5 s The controller switches to settings mode flashing thermometer icon Pus...

Страница 6: ...tarting power of the controller and valve of ca 7 VA and acceptable voltage drop of max 15 the maximum cable length for 10 controllers is about 50 m If the controllers and valves are at higher distance than 50 m from the transformer or more valves are connected to the transformer max 2 valves per controller it is more suitable to supply the controllers locally The RS485 bus is galvanically separat...

Страница 7: ...s All dimensions in mm RoHS notice The device contains a non rechargeable battery which backups the real time clock and part of the memory After the device is not operable please return it to the manufacturer or dispose of it in compliance with local regulations ...

Страница 8: ...es domat US100 Changes in version 09 2016 Changed the format and reference to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours 05 2018 Change technical data ...

Отзывы: