Installation and Commissioning 

Rev.  2020 - V34

ATTENTION!   

There is no universally uniform standard, which could be applied to a 

VOC sensor

 (Volatile Organic Compounds). The monitored air contains a large 

number of substances to which the sensor responds, and gas mixtures are adjusted. Therefore this sensor does not act selectively, but rather 
 reflects the overall air quality. In principle, one also cannot state precisely what is "bad air" or what is "good air" because this is a purely subjective 
sensation. 
The gas inter-exchange in the sensor element happens by diffusion. Depending on the changes to the concentration and the flow velocity of the air 
surrounding the sensor, the reaction of the device to the change of concentration may take place with a delay. It is essential to choose an installation 
location for the device in which the air stream flows around the sensor. Otherwise the gas exchange may be considerably delayed or prevented.  

Automatic calibration of air quality  (default)

The automatic background logic is a self-calibrating mechanism that is suitable  
for use in applications in which the air quality regularly drops to fresh air level.  
This should typically occur during times in which the rooms are unoccupied. 

The sensor reaches its normal accuracy after 24 hours of continuous operation  
in an environment that has been subjected to a fresh air supply.  
The deviation errors remain minimal if the sensor is exposed to fresh air at least  
4 times within 28 days. The device needs continuous operating cycles of more than 
24 hours to operate correctly.

Manual calibration of air quality 

After connecting the device, ensure continuous operation for at least 2 hours  
using air defined as "normal" air quality.  
Manual calibration can be started by pressing the button position,  
irrespective of the DIP 3 -switch.  

The calibration procedure is started by pressing the "ZERO" button  
(for approx. five seconds). This is signalled via the flashing LED. 

Then calibration takes place. During this phase, the LED is continuously active  
and a 600 second countdown runs. 

Putting in operation 

After switching on the device, a self-test and tempering period follows.  
This process takes around 30 - 50 minutes, depending on the ambient conditions. 
It is imperative to perform manual calibration once this process is completed. 

Switching point setting 

A switching point between 10 % and 95 % of the measuring range can be selected 
using the SET potentiometer.  
A potential-free changeover contact is available as a switch output.

Offset 

The VOC measured value can be adjusted subsequently using the offset 
 potentio meter. The adjusting range is ± 10 % of the measuring range.

DIP switches 

KLQ - W

VOC sensitivity

DIP 1

DIP 2

LOW

OFF

OFF

MEDIUM  (default)

O N

OFF

HIGH

OFF

O N

VOC automatic zero point

DIP 3

deactivated

OFF

activated  (default)

O N

Output

DIP 4

Voltage 0 -10 V  (default)

OFF

Current  4...20 mA

O N

DIP switches 

KLQ - SD

VOC sensitivity

DIP 1

DIP 2

LOW

OFF

OFF

MEDIUM  (default)

O N

OFF

HIGH

OFF

O N

Содержание AERASGARD KLQ- SD

Страница 1: ... and measuring transducers including installation flange self calibrating with multi range switching and active switching output KLQ W IP 65 KLQ SD IP 54 6000 3440 0000 1XXD1 34400 2020 D1 V106 08 2020 Domat Control System s r o U Panasonicu 376 530 06 Pardubice Stare Civice CZ Česká republika Tel 420 461 100 823 Fax 420 226 013 092 info domat cz www domat int com Gratulujeme Zakoupili jste produk...

Страница 2: ...astic Montážní schéma Mounting diagram ø 250 mm 115 mm ø 250 mm 115 mm Rozměry Dimensional drawing KLQ W KLQ SD KLQ W KLQ SD 14 8 37 8 M16x1 5 ø32 3 12 13 4 202 5 37 8 ø20 60 87 30 32 62 ø5 2 ø20 M4 ø 4 3 39 49 107 72 64 13 4 202 5 37 8 ø20 60 87 30 32 62 ø5 2 ø20 M4 ø 4 3 39 49 107 72 64 ...

Страница 3: ...ro OFFSET 13 11 12 1 2 3 Breaker Normally open contact Output air quality UB GND UB 24V AC DC Zero 1 2 3 1 2 ON DIP VOC Výst kvalita vzduchu 0 10V UB GND UB 24V st ss Schéma zapojení KLQ SD U Zero 1 2 3 1 2 ON DIP VOC Output air quality 0 10V UB GND UB 24V AC DC Connecting diagram KLQ SD U 1 2 3 12 11 13 UB 24V st ss Výst kvalita vzduchu 0 10V 4 20mA UB GND Rozp kont Spín kont C O 24V 1A Instalačn...

Страница 4: ...uch 10 V znečištěný vzduch KLQ SD 0 10 V pevný KLQ W 0 10 V nebo 4 20 mA pracovní odpor 800 Ω volitelný pomocí DIP přepínačů s offsetovým potenciometrem 10 z měřícího rozsahu Výstup relé KLQ SD bez přepínacího kontaktu KLQ W s bezpotenciálovým přepínacím kontaktem 24 V 1 A spínací bod nastavitelný Přesnost měření typicky 20 z konečné hodnoty dle kalibračního plynu Životnost 60 měsíců za podmínky n...

Страница 5: ...voz vyžaduje nepřetržitý pracovní cyklus trvající déle než 24 hodin Manuální kalibrace kvality vzduchu Po připojení zařízení dbejte na zajištění nepřetržitého provozu po dobu nejméně dvou hodin s kvalitou vzduchu nastavenou na normální Manuální kalibraci lze spustit stisknutím tlačítka ZERO po dobu cca 5 sekund bez ohledu na polohu přepínače DIP 3 Započetí procesu kalibrace je indikováno blikáním ...

Страница 6: ...ní v blízkosti jiných zařízení která neodpovídají směrnicím EMC může ovlivnit jeho funkčnost Toto zařízení nesmí být používáno jako bezpečnostní prvek pro monitorovací aplikace které slouží k ochraně osob před nebezpečím zraněním nebo jako NOUZOVÝ VYPÍNAČ pro systémy stroje anebo pro jiné podobné účely kde selhání může vést ke škodám na majetku zdraví či životním prostředí Rozměry krytu nebo přísl...

Страница 7: ......

Страница 8: ...ium high Output 0 V clean air 10 V polluted air KLQ SD 0 10 V fixed KLQ W 0 10 V or 4 20 mA working resistance 800 Ω selectable via DIP switches with offset potentiometer 10 of the measuring range Relay output KLQ SD without changeover contact KLQ W with potential free changeover contact 24 V 1 A switchpoint adjustable Measuring accuracy typical 20 of final value referred to calibrating gas Servic...

Страница 9: ...viation errors remain minimal if the sensor is exposed to fresh air at least 4 times within 28 days The device needs continuous operating cycles of more than 24 hours to operate correctly Manual calibration of air quality After connecting the device ensure continuous operation for at least 2 hours using air defined as normal air quality Manual calibration can be started by pressing the button posi...

Страница 10: ...Direct sun irradiation or heat irradiation by similar sources powerful lamps halogen spotlights must absolutely be avoided Operating this device close to other devices that do not comply with EMC directives may influence functionality This device must not be used for monitoring applications which serve the purpose of protecting persons against hazards or injury or as an EMERGENCY STOP switch for s...

Страница 11: ...zchybnou kvalitu zaručujeme v rámci našich Všeobecných obchodních podmínek Subject to errors and technical changes All statements and data herein represent our best knowledge at date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are used under a wide range of diff...

Страница 12: ...AERASGARD KLQ W AERASGARD KLQ SD G ...

Отзывы: