24
UH 6932 / 21.08.18 en / 010A
General Data
Nominal operating mode:
continuous operation
Temperature range
operation:
- 20 ... + 60
°
C
storage:
- 20 ... + 70
°
C
Altitude:
< 2.000 m
Clearance and creepage distance
rated impuls voltage /
pollution degree:
4 kV / 2
IEC 60 664-1
EMC
IEC/EN 61 326-3-1, IEC/EN 62 061
Interference suppression:
Limit value class B
EN 55 011
Degree of protection:
Housing:
IP 40
IEC/EN 60 529
Terminals:
IP 20
IEC/EN 60 529
Housing:
Thermoplastic with V0 behaviour
according to UL subject 94
Vibration resistance:
Amplitude 0,35 mm
frequency 10 ... 55 Hz IEC/EN 60 068-2-6
Climate resistance:
20 / 060 / 04
IEC/EN 60 068-1
Terminal designation:
EN 50 005
Wire connection:
DIN 46 228-1/-2/-3/-4
Wire fixing:
captive slotted screw
Mounting:
DIN-rail
IEC/EN 60 715
Weight:
approx. 320 g
Dimensions
Width x height x depth:
45 x 107 x 121 mm
Frequency Measuring Input E1 and E2
Supply voltage:
DC 24 V (provided by the device)
Input current:
max. 30 mA
Output:
as option PNP or NPN
HIGH-level:
DC 10 V ... DC 26.4 V
LOW-level:
< DC 2 V
Min. pulse duration e. g.
on and off time:
75 µs
Input frequency:
< 3 kHz
Response value
:
adjustable from 1 Hz ... 2 kHz
Measuring accuracy:
<
±
2 %
Stability of the setting
threshold at variation of
auxiliary voltage and
temperature:
<
±
1 %
Hysteresis:
adjustable from 2 ... 10 %
of the set response value
Reaction time of
Frequency monitoring:
Duration of 1 cycle (inverse value of
adjusted frequency) + 10 ms
+ adjusted response delay
Response delay t
v
:
adjustable from 0.1 ... 100 s
Start up time delay t
A
:
adjustable from 0 ... 100 s
Reset delay t
F
:
adjustable from 0 ... 100 s
Switchover time period t
U
:
adjustable from 0 ... 100 s
Accuracy of the
adjustable times:
<
±
5 %
Time between connection
of auxiliary supply and
ready to mesure:
approx. 1.5 s (with start up delay is 0)
Auxiliary circuit (A1-A2)
Auxiliary voltage U
H
:
DC 24 V
The power supply shall meet the
requirements of SELV / PELV
Voltage range:
0.8 ... 1.1 U
H
Nominal consumption:
typ. 3.2 W
Short-circuit protection:
Internal PTC
Overvoltage protection:
Internal VDR
Duty-cycle Reset button:
> 1.2 s
Output
Contacts
:
2 NO contacts
Contact type:
Relay forcibly guide
Thermischer Strom I
th
:
8 A
(see current limit curve)
Switching capacity
to AC 15:
3 A / AC 230 V
IEC/EN 60 947-5-1
to DC 13:
2 A / DC 24 V
IEC/EN 60 947-5-1
to DC 13:
4 A / DC 24 V at 0.1 Hz
Electrical life
at 5 A, AC 230 V cos
ϕ
= 1: > 2.2 x 10
5
switch. cycl. IEC/EN 60 947-5-1
Short circuit strength
max. fuse rating:
10 A gL
IEC/EN 60 947-5-1
Mechanical life:
20 x 10
6
switching cycles
Semiconductor
monitoring output:
DC 24 V, 50 mA, plus switching
Analogue output:
2 ... 10 V, max. 10 mA
Technical Data
Technical Data
The safety functions were not evaluated by UL. Listing is accomplished
according to requirements of Standard UL60947, “general use
applications”
Standards:
- ANSI/UL 60947-1, 5
th
Edition (Low-Voltage Switchgear and Controlgear
Part1: General rules)
- ANSI/UL 60947-5-1, 3
th
Edition (Low-Voltage Switchgear and Controlgear
Part5-1: Control circuit Devices an Switching Elements - Electro-
mechanical Control Circuits Devices)
- CAN/CSA-C22.2 No. 60947-1-13, 2
nd
Edition (Low-Voltage Switch-
gear and Controlgear - Part1: General rules)
- CAN/CSA-C22.2 No. 60947-1-14, 1
st
Edition (Low-Voltage Switch-
gear and Controlgear - Part5-1: Control circuit Devices an Switching
Elements - Electromechanical Control Circuits Devices)
Nominal voltage U
N
:
DC 24 V:
Device must be supplied with a Class 2 or
a voltage / current limited power supply.
Switching capacity:
Semiconductor monitoring
outputs:
24Vdc, 50mA, pilot duty
Switching capacity
Relay output
device free-standing:
Ambient temperature 60°C:
Pilot duty B300, Q300
8A 250Vac G.P.
8A 24 Vdc
Device mounted without
distances heated by devices
with same load:
Ambient temperature 55°C:
Pilot duty B300, Q300
5A 250Vac G.P.
5A 24 Vdc
Ambient temperature 60°C:
Pilot duty C300, Q300
4A 250Vac G.P.
4A 24 Vdc
Wire connection
Ambient temperature
60°C, 4A bzw. 55°C, 5A:
min. 75°C aluminum or copper conductors
Ambient temperature
60°C, 8A:
min. 90°C aluminum or copper conductors
nfo
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
UL-Data