LG 5925 / 26.02.18 en / 972

Switching capacity

to AC 15: 

NO contacts: 

3 A / AC 230 V 

IEC/EN 60 947-5-1

NC contacts: 

2 A / AC 230 V 

IEC/EN 60 947-5-1

to DC 13: 

NO contacts: 

2 A / DC 24 V 

IEC/EN 60 947-5-1

NC contacts: 

2 A / DC 24 V 

IEC/EN 60 947-5-1

to DC 13:

NO contact:      

 4 A / DC 24 V at 0.1 Hz     

NC contact:          

 4 A / DC 24 V at 0.1 Hz

Electrical contact life

 

to 5 A, AC 230 V cos 

ϕ

 = 1: 

> 2.2 x 10

5

  switching cycles 

Permissible operating

frequency:

 

max. 1 200 operating cycles / h

Short circuit strength

max. fuse rating: 

10 A gG / gL 

IEC/EN 60 947-5-1

line circuit breaker: 

B 6 A

Mechanical life:

 

> 20 x 10

6

 switching cycles

Semiconductor output:

 

DC 24 V 100 mA, plus switching

General Data

Operating mode:

 

Continuous operation

Temperature range

Operation: 

- 25 ... + 55 

°

C

Storage : 

- 40 ... + 85 

°

C

altitude:

 

< 2.000 m

Clearance and creepage

distances

Rated impuls voltage / 

pollution degree: 

4 kV / 2 (basis insulation)  IEC 60 664-1

EMC 

IEC/EN 62 061

Interference suppression: 

Limit value class B 

EN 55 011

Degree of protection

Housing: 

IP 40 

 

IEC/EN 60 529

Terminals: 

IP 20 

 

IEC/EN 60 529

Housing:

 

Thermoplastic with V0 behaviour

   

according to UL subject 94

Vibration resistance:

 

Amplitude 0.35 mm  IEC/EN 60 068-2-6

   

frequency 10 ... 55 Hz

Climate resistance:

 

25 / 055 / 04 

IEC/EN 60 068-1

Terminal designation:

 

EN 50 005

Wire fixing:

 

Plus-minus terminal screws M 3.5

   

box terminals with wire protection or

   

cage clamp terminals

Mounting:

 

DIN rail 

IEC/EN 60 715

Weight:

 

LG 5925, AC/DC 24 V: 

210 g

LG 5925.54, AC/DC 24 V: 

220 g

LG 5925, AC 230 V: 

275 g

LH 5925, AC/DC 24 V: 

375 g

Dimensions

Width x height x depth

 

LG 5925: 

22.5 x   90 x 121 mm

LG 5925 PC: 

22.5 x 111 x 121 mm

LG 5925 PS: 

22.5 x 104 x 121 mm

The safety functions were not evaluated by UL. Listing is accom-

plished according to requirements of Standard UL 508, “general use 

applications”

Nominal voltage U

N

:

LG 5925: 

AC/DC 24 V, AC 110 ... 115 V

   

AC 230 V

Ambient temperature

LG 5925

 

- 25 … + 55 °C

Switching capacity:

LG 5925.04

Ambient temperature 35°C:

 

Pilot duty B300

  

8A 250Vac Resistive

  

8A 24Vdc Resistive or G.P.

LG 5925.04

Ambient temperature 55°C:

 

Pilot duty B300

  

4A 250Vac Resistive

  

4A 24Vdc Resistive or G.P.

Switching capacity:

LG 5925.02, .48, .54

Ambient temperature 45°C:

 

Pilot duty B300

  

8A 250Vac Resistive

  

8A 24Vdc Resistive or G.P.

LG 5925.02, .48, .54

Ambient temperature 55°C:

 

Pilot duty B300

  

6A 250Vac Resistive

  

6A 24Vdc Resistive or G.P.

Wire connection: 

60°C / 75°C copper conductors only

Screw terminals fixed: 

AWG 20 - 12 Sol/Str Torque 0.8 Nm

Plug in screw: 

AWG 20 - 14 Sol Torque 0.8 Nm

   

AWG 20 - 16 Str Torque 0.8 Nm 

Plug in cage clamp: 

AWG 20 - 12 Sol/Str 

nfo

Technical data that is not stated in the UL-Data, can be found 

in the technical data section.

LG 5925.48/61   AC/DC 24 V
Article number: 

0061919

LG 5925.54/61   AC/DC 24 V
Article number: 

0064882

•  Output: 

3 NO contacts, 1 NC contact

•  Nominal voltage U

N

AC/DC 24 V

•  Width: 

22.5 mm

LG 5925  ._ _  _ _  /61    DC 24 V
   

 

 

 

Nominal voltage

  

 

 

 

UL-approval

   

 

 

 

Type of terminals

   

 

 

   

 

without indication: 

  

 

 

   

 

 terminal 

blocks fixed

   

 

 

   

 

  with screw terminals

  

 

 

   

 

PC (plug in cage clamp): 

  

 

 

   

 

 pluggable terminal blocks 

   

 

 

   

 

  with cage clamp terminals

   

 

 

   

 

PS (plug in screw): 

   

 

 

   

 

  pluggable terminal blocks 

   

 

 

   

 

  with screw terminals

  

 

 

 

Contacts

  

 

 

 

Type

Technical Data

UL-Data

Standard Type

Ordering Example

Содержание Safemaster LG 5925

Страница 1: ...AFEMASTER Not Aus Modul LG 5925 0262658 Datenblatt Betriebsanleitung DEUTSCH E DOLD S HNE KG Postfach 1251 78114 Furtwangen Deutschland Telefon 49 7723 6540 Fax 49 7723 654356 dold relays dold com www...

Страница 2: ...5 Schaltbilder 6 Anschlussklemmen 6 Hinweise 6 Technische Daten 6 Technische Daten 7 UL Daten 7 Standardtype 7 Bestellbeispiel 7 Vorgehen bei St rungen 8 Wartung und Instandsetzung 8 Kennlinie 8 Kennl...

Страница 3: ...olgen Deshalb muss in den Betriebs arten mit automatischem Start eine bergeordnete Steuerung einen automatischen Start nach einem Not Aus verhindern Durch ffnen des Geh uses oder eigenm chtige Umbaute...

Страница 4: ...4 LG 5925 26 02 18 de 972...

Страница 5: ...emmen oder mit Federkraftklemmen 22 5 mm Baubreite Ein Taster Not Aus K1 K2 M8574 Schutz von Personen und Maschinen Not Aus Schaltungen von Maschinen berwachung von Schiebeschutzgittern Einsatz in Feu...

Страница 6: ...A pro Kontakt siehe Summenstromgrenzkurve LG 5925 03 S33 A1 S11 A2 S34 13 S12 14 41 23 S21 24 42 33 S22 34 M10536 S12 S22 S33 S34 A1 S11 A2 S21 K1 K2 13 23 33 41 14 24 34 42 Leitungsschlusserkennung...

Страница 7: ...ite x H he x Tiefe LG 5925 22 5 x 90 x 121 mm LG 5925 PC 22 5 x 111 x 121 mm LG 5925 PS 22 5 x 104 x 121 mm Die Sicherheitsfunktionen des Ger tes wurden nicht durch die UL untersucht Die Zulassung bez...

Страница 8: ...50 200 Schaltspannung VDC M2028_e Sicheres Abschalten kein stehender Lichtbogen max 1 Schaltspiel s Fehler m gliche Ursache LED Netz leuchtet nicht Versorgungsspannung nicht angeschlossen Querschluss...

Страница 9: ...verst rkt werden Die Funktion der externen Sch tze wird durch Einschleifen der ffnerkontakte in den Einschaltkreis Klemmen S33 S34 berwacht Bitte Hinweis Ger teprogrammierung beachten Schalterstellun...

Страница 10: ...14 Ein Zweikanalige Not Aus Schaltung mit Querschlusserkennung Bitte Hinweis Ger teprogrammierung beachten Schalterstellung S2 Handstart Geeignet bis SIL3 Performance Level e Kat 4 L1 M9759 N Not Aus...

Страница 11: ...gency Stop Module LG 5925 0262658 Datasheet Operating Instructions ENGLISH E DOLD S HNE KG P O Box 1251 D 78114 Furtwangen Germany Tel 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold com...

Страница 12: ...nection Terminals 16 Notes 16 Technical Data 16 Technical Data 17 UL Data 17 Standard Type 17 Ordering Example 17 Troubleshooting 18 Maintenance and repairs 18 Characteristics 18 Characteristics 18 Ap...

Страница 13: ...evice is under supply voltage AUTOMATIC START According to IEC EN 60 204 1 part 9 2 5 4 2 and 10 8 3 it is not allowed to restart automatically after emergency stop Therefore the machine control has t...

Страница 14: ...14 LG 5925 26 02 18 en 972...

Страница 15: ...p terminals Width 22 5 mm 0243372 Protection of people and machines Emergency stop circuits on machines Monitoring of safety gates Usage in furnace application in continuous operation acc to EN 50156...

Страница 16: ...and S2 are used These are loca ted behind the front cover see unit programming The setting with or without cross fault monitoring on E stop buttons is made with S1 not for LG 5925 54 The LG 5925 54 ha...

Страница 17: ...LH 5925 AC DC 24 V 375 g Dimensions Width x height x depth LG 5925 22 5 x 90 x 121 mm LG 5925 PC 22 5 x 111 x 121 mm LG 5925 PS 22 5 x 104 x 121 mm The safety functions were not evaluated by UL Listin...

Страница 18: ...64 I 2 A 2 150 200 256 100 0 10 20 30 40 60 50 T C 0 0 1 0 3 0 5 1 3 5 10 switching current A 50 100 150 250 200 switching voltage VDC M5834_c safe breaking no continuous arcing max 1 switching cycle...

Страница 19: ...S11 S33 S34 S12 S22 S21 LG5925 13 23 14 24 K4 K4 K5 K5 on Single channel emergency stop circuit This circuit does not have any red undancy in the emergency stop control circuit Note Refer to Unit pro...

Страница 20: ...S22 S21 LG5925 13 14 on 2 channel emergency stop circuit with cross fault detection Note Refer to Unit programming Switches in pos S2 manual start Suited up to SIL3 Performance Level e Cat 4 L1 M10096...

Страница 21: ...dule d arr t d urgence LG 5925 0262658 Fiche Technique Manuel d utilisation FRAN AIS E DOLD S HNE KG B P 1251 78114 Furtwangen Allemagne T l 49 7723 6540 Fax 49 7723 654356 dold relays dold com www do...

Страница 22: ...ristiques techniques 26 Caract ristiques techniques 27 Donn es UL 27 Versions standard 27 Exemple de commande 27 Diagnostics des d fauts 28 Entretien et remise en tat 28 Courbe caract ristiques 28 Co...

Страница 23: ...apr s un Arr t d urgence Losqu un d marrage automatique est toutefois demand il est nec ssaire de assurer qu une commande prioritaire effectue le blocage apr s une action d arr t d urgence L ouverture...

Страница 24: ...24 LG 5925 26 02 18 fr 972...

Страница 25: ...bornes ressorts ou avec bornes vis Largeur utile 22 5 mm 0247145 Protection des personnes et des machines Couplages Arr t d urgence des machines Contr le des grilles de protection coulissantes Pour un...

Страница 26: ...d arr t d urgence s effectue au moyen de l interrupteur S1 sauf pour le LG 5925 54 qui u a pas le switch S1 et qui est toujours avec reconnaissance de C C transversaux L interrupteur S2 permet de choi...

Страница 27: ...LG 5925 24 V AC DC 210 g LG 5925 54 24 V AC DC 220 g LG 5925 230 V AC 275 g Dimensions largeur x hauteur x profondeur LG 5925 22 5 x 90 x 121 mm LG 5925 PC 22 5 x 111 x 121 mm LG 5925 PS 22 5 x 104 x...

Страница 28: ...stiques Courbes caract ristiques Diagnostics des d fauts Entretien et remise en tat 0 0 1 0 3 0 5 1 3 5 10 Courant de commutation A 50 100 150 250 200 Tension de commutation VDC M2034_d D clenchement...

Страница 29: ...La fonction des contacteurs externes est contr l e en bouclant les contacts ouverture dans le circuit d enclenchement bornes S33 S34 Bien tenir compte du paragraphe Programmation du module Pos interr...

Страница 30: ...6_b N A2 A1 S11 S33 S34 S12 S22 S21 LG5925 13 14 arr t d urgence marche Couplage Arr t d urgence 2 canaux sans d tection des courts circuits transversaux Bien tenir compte du paragraphe Programmation...

Страница 31: ...2 2 x AWG 20 to 16 A 10 12 mm 1 x 0 5 2 5 mm2 1 x AWG 20 to 14 A 12 mm 1 x 0 5 4 mm2 1 x AWG 20 to 12 M10249 A A 8 mm 1 x 0 5 2 5 mm2 1 x AWG 20 to 14 2 x 0 5 1 5 mm2 2 x AWG 20 to 16 A 8 mm 1 x 0 5 2...

Страница 32: ...niers amovibles 1 Mise hors tension de l appareil 2 Enfoncer un tourne vis dans la fente entre la face avant et le bornier 3 Tourner le tourne vis pour lib rer le bornier 4 Tenir compte du fait que le...

Страница 33: ...an das Ger t im High Demand Mode Intervall f r zyklische berpr fung der Sicherheitsfunktion Demand to our device based on the evaluated neccessary safety level of the application at High Demand Mode I...

Страница 34: ...34 LG 5925 26 02 18 de en fr 972 DE EG Konformit tserkl rung EN CE Declaration of Conformity FR D claration de conformit europ enne...

Страница 35: ...35 LG 5925 26 02 18 de en fr 972 DE Notizen EN Notice FR Note...

Страница 36: ...36 LG 5925 26 02 18 de en fr 972 E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Отзывы: