27.10.15 en / 605

Wiring

Devices with DC 24V auxiliary supply have to be operated on a galvanic 
separated power supply.

Configuration Cycle

1.) 

Wire the system

2.) 

Adjust module address on extension modules with switch “ADR” 

 

(different addresses for all modules)

2.1)  When display units are integrated into the annunciator system the 

address setting of each display unit has to be done as follows

 

- if the display unit should display the state of the base module  
  (RP 5994) set “MODE” switch on back of the unit to position 

 

  “Basismodul” and adjust an address that is not used by any 

 

  other display unit.

 

- if the display unit should display the state of an extension module  
  (RP 5995) set “MODE” switch on back of the unit to position 

 

  “Erw.modul” and adjust the same address as on the extension  
  module (RP 5995) of which the status should be displayed.

3.) 

Set “MODE” switch on base module to position “Config” 

4.) 

Choose input mode on extension modules:

 

Terminals X1/X2 open = open circuit operation

 

Terminals X1/X2 linked = closed circuit operation

5.) 

Set  delay on switch, „td“ 0 ... 10 s

6.) 

Power up the system

7.) 

Fault signal LEDs of the base module are flashing for some time

8.) 

On the detected extension modules the fault signal LEDs are now  
flashing

9.) 

Fault signal LEDs change to continuous state and indicate number 
of detected extension modules in binary code

10.)  The detected modules are stored no voltage safe in the base 

 

module memory. The fault annunciator only works with the 

 

detected modules. If a new module is added, the configuration 

 

cycle has to be run again.

11.)  Select the required alarm function with switch “MODE” on the base 

module 

12.)  Press push buttons QH and QHC to leave the configuration mode.

Function Switch „MODE“

    
   switch
  „MODE“  description

      0 

First fault signal

      1 

New fault signal

      2 

Common alarm manual reset

      3 

Common alarm auto reset

  Config. 

Configuration

Function Switch „Set“

 

Setting and Adjustment

 

Setting and Adjustment

Possible Alarm Modes:

Alarm annunciator

Alar

m reset QA

A

udib

le alar

m

reset QH

Common alar

reset QCA

New signal alarm annunciator

-

First signal annunciator

-

Common alarm annunciator manual reset

Common alarm annunciator auto reset

-

-

 

: this setting ist not supported by the module

Lamp Test

Pressing the pushbuttons QH and QCA simultaneously during normal 
operation will force a lamp test function (LT). During lamp test all fault signal 
LEDs are switched on.
The lamp test function can also be operated by bridging the terminal QX1/
QX2 (connection remote reset) if this function is selected on switch “Set” 
for QX1/QX2

Fault Diagnostics

To indicate failures of the system the unit generates a flash code on the Bus 
LED. When a failure code 1 to 3 is displayed, the contacts of the common 
alarm relay switch off.

LED continuously on: 

System has no failure

Failure 1 

 : 

Configuration failure. One ore more 

 

 

extension modules, that have been 

 

 

detected during configuration do not exist  

 

anymore. The address of the first missing  

 

extension module is displayed as binary  

 

code on the fault signal LEDs.

Failure 2 

 : 

The base module cannot communicate 

 

 

with the extension modules. The address  

 

of the first extension module that cannot  

 

communicate with the base module is 

 

 

displayed as binary code on the fault 

 

 

signal LEDs.

Failure 3 

  : 

The bus wire is interrupted or the bus is not  

 

terminated correctly. The base module 

 

 

does not find any  extension modules to  

 

communicate with.

Failure 4 

  : 

In normal operation: the configuration data  

 

has been found faulty. A new configuration  

 

cycles has to be run.

 

During configuration: the detected 

 

 

configuration data  could not be stored.

Failure 5 

: New modules unknown to the device 

 

 

software of the base module have to be  

 

implemented by a firmware update of the  

 

base module.  

Remark:

  Different types of devices (device classes) can be connected  

 

to the annunciator bus e.g. extension modules RP 5995, display  

 

units EH 5994, EH 5995 etc. The base module detects the  

 

different module types and adds a device specific number to the  

 

adjusted bus module address (address offset). In the case of  

 

failure this added number is indicated as binary code on the  

 

LEDs of the base module.

 

Max. 4 text display units EH 5996 can be connected to the 

 

Base module RP 5994.

 

These 4 units has to be designation by adresse 0 up to 3

 Device class 

adress offset 

modules

 Extension modules 

+ 0 

RP 5995

 Display unit 

+ 10 

EH 5994, EH 5995

 Textdisplay unit 

+ 20 

EH 5996

Function of QX1 / QX2

Function principle 

of

fault signal inputs

Switch 

„Set“

Alar

m reset 

QA

A

udib

le 

alar

m

reset QH

Common 

alar

m reset

QCA

Lamp test 

LT

open circuit 

oper

ation

closed 

circuit 

oper

ation

0

-

-

-

-

1

-

-

-

-

2

-

-

-

-

3

-

-

-

-

4

-

-

-

-

5

-

-

-

-

6

-

-

-

-

7

-

-

-

-

Содержание RP 5994

Страница 1: ...for audible alarm and common alarm on request Reset buttons for audible alarm common alarm and single alarm Connection of remote reset button Function according to setting Display unit EH 5994 EH 5995 Exchangable front label for individual legending As option galvanic separated RS458 bus Protection degree for front side IP 64 Enclosure for flush mounting 96 x 96 mm Display unit EH 5994 8 fault sig...

Страница 2: ... operation alarm 2 open circuit operation alarm 1 closed circuit operation alarm 2 closed circuit operation LED 1 LED 2 LED CA relay audible alarm off on reset audible alarm relay common alarm M9902 alarm 1 open circuit operation alarm 1 open circuit operation alarm 1 closed circuit operation alarm 1 closed circuit operation LED 1 LED 2 LED CA relay audible alarm reset common alarm off on reset au...

Страница 3: ...y the module Lamp Test Pressing the pushbuttons QH and QCA simultaneously during normal operation will force a lamp test function LT During lamp test all fault signal LEDs are switched on The lamp test function can also be operated by bridging the terminal QX1 QX2 connection remote reset if this function is selected on switch Set for QX1 QX2 Fault Diagnostics To indicate failures of the system the...

Страница 4: ...ibration resistance 0 35 mm amplitude frequency 10 55 Hz IEC EN 60 068 2 6 Climate resistance 20 055 04 IEC EN 60 068 1 Terminal designation EN 50 005 Wire connection DIN 46 228 1 2 3 4 fixed screw terminal S 0 2 4 mm2 solid or 0 2 1 5 mm2 stranded wire with sleeve plug in screw terminal PS 0 1 2 5 mm2 solid or 0 1 1 5 mm2 stranded wire with sleeve plug in cage clamp terminals PC 0 2 2 5 mm2 solid...

Страница 5: ...7 S7 S6 S8 S8 S5 GND 1 GND 1 GND 1 RP5994 RP5995 RP5995 Indication EH5994 Ra Ra Ra Ra B B B B A A A A Rb Rb Rb Rb Sh Sh Sh Sh CA CA T1 External rest button function according to configuration with bridge X1 X2 closed circuit operation T3 External rest button function according configuration both ends of the bus have to be terminated on the first and on the last module by inserting the links A Ra a...

Страница 6: ...6 27 10 15 en 605 E DOLD SÖHNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com POBox1251 Telephone 49 7723 654 0 Telefax 49 77 23 654 356 ...

Отзывы: