Notes

WARNING

  Risk of electrocution! 

      Danger to life or risk of serious injuries. 

•  Disconnect the system and device from the power supply and ensure  
  they remain disconnected during electrical installation.
•  The display of the voltage is not in real time. The Value on the display is  
  updated at the end of a measuring cycle. Determine voltage free status  
  by using appropriate instruments.
•  The terminals of the control input X1-X2 have no galvanic separation to 

the measuring circuit L(+) and L(-) and are electrically connected together, 
therefore they have to be controlled by volt free contacts or bridge. These 
contacts ore bridges must provide a sufficient separation depending on 
the mains voltage on L(+)-L(-).

•  Please do not connect external voltage to terminals X1/X2. The control 

must only be made by bridging X1 and X2.

!

 Attention! 

    

•  Before checking insulation and voltage, disconnect the monitoring device  

  RN 5897 from the power source!

•  In one voltage system only one insulation monitor can be used. This has  

  to be observed when interconnecting two separate systems..
•  Device terminals PE1 and PE2 must always be connected via separate  
  lines to different terminal points of the protective-conductor system.
•  The device must not be operated without PE1/PE2 connection!

nfo

 Attention! 

    

•  The main measuring circuit can be connected with its terminals L(+) and 

L(-) both to the DC and also AC side of a mixed network; it is done most 
practically where the primary incoming power supply takes place e.g. 
with battery networks with connected inverters on the DC side, with 
Generators/Transformers with connected Rectifiers or inverters on the 
AC-side. To monitor a 3NAC system the device can be connected sin-
gle pole, (L(+) and L(-) are bridged, to the neutral of the 3p4w system. 
The 3 phases have a low-ohmic (approx. 3 – 5 Ohm) connection via 
the transformer windings so also insulation failures of the not directly 
connected phases are detected. Via the display menu in programming 
mode  the correct type of network needs to be selected (see „Connec-
tion Examples“).

•  If a monitored AC system includes galvanically connected DC circuits 

(e.g. via a rectifier), an insulation failure on the DC side can only be 
detected correctly, when a current of min 10 mA can flow via the semi-
conductor connections.

•  If a monitored DC system includes galvanically connected AC circuits 

(e.g. via an inverter), an insulation failure on the AC side can only be 
detected correctly, when a current of min 10 mA can flow via the semi-
conductor connections.

•  The measuring circuits of the device RN 5897 is designed for leakage 

capacities up to 300µF. The measurement of the insulation resistance 
will not be influenced but for the measuring phases longer time periods 
are necessary as with smaller capacities. If the max. possible leakage 
capacity is known, the device can be adjusted to the required lower 
level, which will reduce the response time and measurement time.

Содержание RN 5897

Страница 1: ...ide voltage input for auxiliary voltage Width 52 5 mm Product Description The insulation monitor RN 5897 of the VARIMETER IMD family provides best and up to date insulation monitoring of modern IT sys...

Страница 2: ...itored for wire breaks not only at Power On or a manual or occasional automatic test The response time of monitoring is only a few seconds Broken wire detection between L and L is performed via couple...

Страница 3: ...1 X2 for 3 s a stored alarm will be reset This has the same function as pressing the internal reset button Programming setting of parameters set up of the insulation monitor The response values for al...

Страница 4: ...k an asymmetric insulation resistance to or is indi cated by displaying RE k or RE k By pressing the scroll buttons Scroll Up und Scroll Down more measured values can be shown Another value is the mai...

Страница 5: ...ing measuring voltage internal tests Advanced Test additional control of indicator relay Error Indication Display Indication Failure cause Failure recovery Broken wire detection on L L Check measuring...

Страница 6: ...to the DC and also AC side of a mixed network it is done most practically where the primary incoming power supply takes place e g with battery networks with connected inverters on the DC side with Gen...

Страница 7: ...e Net Default Ac Parameter 5 Max line capacitance CE F Default 30 Parameter 1 Broken wire detect in measuring circuit BrWiD Broken Wire Detect oFF Parameter 1 Broken wire detect in measuring circuit B...

Страница 8: ...rox 205 g Dimensions Width x height x depth 52 2 x 90 x 71 mm Measuring ciruit L L to PE1 PE2 Nominal voltage UN AC DC 0 230 V Max voltage range UN AC DC 0 300 V Frequency range DC or 40 1000 Hz Max l...

Страница 9: ...duty C300 R300 5A 250Vac 2A 30Vdc Wire connection 60 C 75 C copper conductors only Torque 0 5 Nm Test specification ANSI UL 60947 1 5th Edition ANSI UL 60947 5 1 3rd Edition CAN CSA C22 2 No 60947 1 1...

Страница 10: ...ted from earth AC 0 300V 40 1000Hz L2 L PE RN5897 X1 External combined test reset button L X2 11 PE1 12 PE2 14 21 22 24 M11601_a 2 A1 A2 UH 1 Setting of type of network AC UN L1 Ungrounded mains 3N AC...