Your Advantages

•  Preventive fire and system protection
•  Detection of symmetric and asymmetric insulation faults
•  Quick fault localisation through selective earth fault detection to L+  
  and L-
•  Universal application in non-earthed AC, DC, AC/DC networks  
  up to 300 V
•  Easy adjustment of response values and setting parameter via  
  rotational switch and menu display
•  Suitable for large leakage capacitances up to 300 µF
•  Optimised reaction time for large leakage capacitances
•  Monitoring also with voltage-free mains
•  Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
•  Protective conductor PE1/PE2 with broken wire detection  
  (can't be switched off)
•  No additional coupling device required

Features

•  Insulation monitoring according to IEC/EN 61557-8
•  2 separate adjustable response thresholds  
  (using e.g. for pre-Alarm and Alarm)
•  Setting range of 1st response value (Pre-Alarm): 10 k

Ω

 … 1 M

Ω

•  Setting range of 2nd response value (Alarm): 1 k

Ω

 … 250 k

Ω

•  2 changeover contacts für insulation failures-Pre-Alarm and -Alarm
•  Energized or de-energized on trip can be selected for indicator relay
•  Display for indication of measured value, device parameters and  
  device status
•  Setting the maximum leakage capacitance to shorten the response time
•  Automatic and manual device self-test
•  Alarm storage selectable
•  Protection against manipulation by sealable transparent cover
•  External control input for combined Test-/Reset-button 
•  3 wide voltage input for auxiliary voltage
•  Width 52.5 mm

Product Description

The insulation monitor RN 5897 of the VARIMETER IMD family provides 
best and up to date insulation monitoring of modern IT systems in an op-
timum and state of the art way fulfilling the relevant standards. The device 
can be used in the most flexible way for AC, DC and AC/DC systems even 
with large leakage capacity to earth (PE). The adjustment of the setting 
values is simple and user friendly done on 2 rotary switches on the front of 
the device. Via display and LEDs the measured value, device parameters 
and device status are indicated easy to read. With a sealable transparent 
cover the device is protectet against manipulation.

Approvals and Markings

Applications

Insulation monitoring of:
•  Non-earthed AC, DC, AC/DC networks
•  UPS systems
•  Networks with frequency inverters
•  Battery networks
•  Networks with direct current drives

•  Hybrid and battery-powered vehicles
•  Mobile generator sets

Monitoring Technique

VARIMETER IMD

Insulation monitor
RN 5897

Function Diagram

Manual reset

Alarm

Alarm

Pr

e-Alarm

Pr

e-Alarm

Hysteresis function

Reset

21-24

21-24

21-24

21-24

11-14

11-14

11-14

11-14

11-12

11-12

11-12

11-12

Earth fault

E

R

A

R

pA

R

21-22

21-22

21-22

21-22

t

t

Open circuit operation

Open circuit operation

Open circuit operation

Open circuit operation

De-energized on trip

De-energized on trip

De-energized on trip

De-energized on trip

UH

M11593

AC/DC

Canada / USA

Translation

of the original instructions

All Technical Data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.

Содержание RN 5897

Страница 1: ...ide voltage input for auxiliary voltage Width 52 5 mm Product Description The insulation monitor RN 5897 of the VARIMETER IMD family provides best and up to date insulation monitoring of modern IT sys...

Страница 2: ...itored for wire breaks not only at Power On or a manual or occasional automatic test The response time of monitoring is only a few seconds Broken wire detection between L and L is performed via couple...

Страница 3: ...1 X2 for 3 s a stored alarm will be reset This has the same function as pressing the internal reset button Programming setting of parameters set up of the insulation monitor The response values for al...

Страница 4: ...k an asymmetric insulation resistance to or is indi cated by displaying RE k or RE k By pressing the scroll buttons Scroll Up und Scroll Down more measured values can be shown Another value is the mai...

Страница 5: ...ing measuring voltage internal tests Advanced Test additional control of indicator relay Error Indication Display Indication Failure cause Failure recovery Broken wire detection on L L Check measuring...

Страница 6: ...to the DC and also AC side of a mixed network it is done most practically where the primary incoming power supply takes place e g with battery networks with connected inverters on the DC side with Gen...

Страница 7: ...e Net Default Ac Parameter 5 Max line capacitance CE F Default 30 Parameter 1 Broken wire detect in measuring circuit BrWiD Broken Wire Detect oFF Parameter 1 Broken wire detect in measuring circuit B...

Страница 8: ...rox 205 g Dimensions Width x height x depth 52 2 x 90 x 71 mm Measuring ciruit L L to PE1 PE2 Nominal voltage UN AC DC 0 230 V Max voltage range UN AC DC 0 300 V Frequency range DC or 40 1000 Hz Max l...

Страница 9: ...duty C300 R300 5A 250Vac 2A 30Vdc Wire connection 60 C 75 C copper conductors only Torque 0 5 Nm Test specification ANSI UL 60947 1 5th Edition ANSI UL 60947 5 1 3rd Edition CAN CSA C22 2 No 60947 1 1...

Страница 10: ...ted from earth AC 0 300V 40 1000Hz L2 L PE RN5897 X1 External combined test reset button L X2 11 PE1 12 PE2 14 21 22 24 M11601_a 2 A1 A2 UH 1 Setting of type of network AC UN L1 Ungrounded mains 3N AC...

Страница 11: ...11 06 05 21 en 393A Characteristic M11603_a...

Страница 12: ...12 06 05 21 en 393A E Dold S hne GmbH Co KG D 78120 Furtwangen dold relays dold com www dold com Bregstra e 18 Phone 49 7723 654 0 Fax 49 7723 654356...

Отзывы: