background image

5

11.01.21 en / 335A

During normal operation failure messages may occur. The messages are 
indicated by a flashing sequence of the „Error“ LED.

Fault Indication by Flashing Code

Flashes

Fault

Reason

Failure  

recovery

1 x

Overtemperature 

on 

power unit

Permitted 

duty cycle ex-

ceeded

Reduce 

duty-cycle 

Wait till heat sink 

cools down

2 x

Overtemperature 

on motor or 

broken wire in 

thermistor circuit

High duty-cycle 

on motor or 
broken wire

Decrease 

duty-cycle. 

Repair wiring 

of temperature 

sensor

3 x

Short circuit in 

thermistor circuit

Squeeze conduit, 

defective

 soldering point

Check

 connection wire, 

repair 

4 x

Phase failure

Defective fuse

Change fuse

Check 

voltage range

5 x

Decrease 

phase sequence

Connection 

L1, L2, L3 

incorrect

Correct connetion 

sequence see 

application

6 x 

Mains frequency 

is out of

 tolerance

Wrong mains 

frequency

Device 

not suitable for 

the frequency.

Contact 

manufacturer.

7 x

Broken ciruit

Cable break

Check wiring

Defective 

braking relay

The unit has to 

repaired

9 x

Incorrect

internal 

temperature 

sensor

Defective

 component or  

temperature 
out of range

Check 

temp. range

The unit has to 

repaired

10 x

RAM defective

Defective

 component

The unit has to 

repaired

13 x

Overcurrent 

on power 

semiconductors

Gravitational 

start

Prolonging ramp 

up time. Set 

starting torque 

lower. Use 

unit with higher 

ranges

Motor blocked Remove blockage

14 x

Brake current 

to high

Braking current 

adjusted over 

permitted value

Back off 

potentiometer I

Br

15 x

Overcurrent on 

ramp

Gravitational 

start, ramp time 

to short or 

starting torque 

to high

Prolonging ramp 

up time. Set 

starting torque 

lower. Use 

unit with higher 

ranges

16 x

Communication 

error

internal

Defective

 component

The unit has to 

repaired

17 x

Overcurrent on 

bridging relay

Motor blockage

Remove 
blocking

Отзывы: