Technical User Guide
6
DOl 10 kit for water temperature
3 Installation
Installation, servicing and troubleshooting of all electrical equipment must be carried out by quali-
fied personnel in compliance with the applicable national and international standard EN 60204-1
and any other EU standards that are applicable in Europe.
The installation of a power supply isolator is required for each motor and power supply to facili-
tate voltage-free work on the electrical equipment. The power supply isolator is not included.
3.1 Circuit Diagram
Figure 1: DOL 10.
o
C
kΩ*
V
o
C
kΩ*
V
o
C
kΩ*
V
-40
82.50
8.08
13
22.03
5.44
33
12.24
4.03
-35
76.84
7.96
14
21.36
5.37
34
11.91
3.97
-30
70.60
7.83
15
20.71
5.29
35
11.60
3.91
-25
63.97
7.68
16
20.09
5.22
36
11.30
3.85
-20
57.18
7.49
17
19.48
5.15
37
11.01
3.79
-15
50.50
7.26
18
18.90
5.07
38
10.72
3.73
-10
44.12
7.00
19
18.33
5.00
39
10.45
3.67
-5
38.22
6.70
20
17.79
4.93
40
10.1
3.61
0
32.1
6.37
21
17.26
4.85
41
9.94
3.55
1
31.92
6.30
22
16.76
4.78
42
9.70
3.50
2
30.96
6.23
23
16.27
4.71
43
9.47
3.44
3
30.02
6.16
24
15.79
4.64
44
9.24
3.39
4
29.11
6.09
25
15.34
4.57
45
9.03
3.34
5
28.23
6.02
26
14.90
4.50
46
8.82
3.29
7
26.53
5.88
27
14.48
4.43
47
8.62
3.24
8
25.72
5.81
28
14.07
4.36
48
8.43
3.19
9
24.94
5.73
29
13.68
4.30
49
8.24
3.14
10
24.17
5.66
30
13.30
4.23
50
8.06
3.09
11
23.44
5.59
31
12.93
4.16
55
7.26
2.87
12
22.72
5.51
32
12.58
4.10
60
6.59
2.68
Table 1:
Sensor characteristics. *Zero power measurement