background image

3931187/03/05/E

7

Doepke

11. Technical Data

Min.

Typ.

Max.

Dupline

Current input

800 µA

Input channels 1 Temperature value

Output channels None

Temperature sensor

Type PT1000

Measuring range

-30°C

+60°C

Time constant typ. 450 s (air flow = 0 m/s)

typ. 350 s (air flow = 1m/s)

Resolution 8 Bit (approx. 0.35°C/Bit)

Measuring error

+2%

Operating Voltage

Rated operating voltage Not required (supplied by Dupline signal line)

Terminals

Type M12-socket connection

Housing

Type Flat-pack design

Dimensions 35 x 68 x 15 (W x H x D in mm)

Material Polycarbonate, light gray

General technical data

Ambient temperature

-30°C

+60°C

Encl. protection type /

standards

IP67

Order number, description 09 501 112, DTS 1

09 501 140, DKM 1 (M12-cable, 2 m, straight)
09 501 141, DKP 3 (Coding cable for DHK 1)

Содержание Dupline DTS 1

Страница 1: ...nleitung Operating Instructions Inhaltsverzeichnis 1 Allgemeines 2 2 Kodierung 2 3 Inbetriebnahme 2 5 Technische Daten 3 4 Garantie 3 6 Anschlussschema 4 Table of Contents 7 General Information 5 8 Co...

Страница 2: ...orgungsspannung sowie ohne Dupline Signal vorgenommen werden Sie bleibt dauerhaft erhalten kann aber jederzeit berschrieben werden 3 Inbetriebnahme Die Installation darf nur von einer autorisierten Fa...

Страница 3: ...stenlosen Ersatz Bei ffnen des Ger tes erlischt der Ga rantieanspruch 5 Technische Daten Draht Beschreibung Draht Beschreibung Braun Dupline Signalleiter Dupline Blau Dupline Signalleiter Dupline Drah...

Страница 4: ...B x H x T in mm Material Polycarbonat hellgrau Allg technische Daten Betriebstemperatur 30 C 60 C Schutzart Normen IP67 Bestellnummer bezeichnung 09 501 112 DTS 1 09 501 140 DKM 1 M12 Kabel 2 m gerade...

Страница 5: ...s be overwritten 9 Putting into Service Installation may only be carried out by an authorized technician The DTS 1 is suitable for direct installation at walls or other objects The DTS 1 has to be exp...

Страница 6: ...The guarantee is not ap plicable to damage incurred during transport or caused by short circuit or overloading In the event of defects in workmanship or material which are discovered within the guar...

Страница 7: ...approx 0 35 C Bit Measuring error 2 Operating Voltage Rated operating voltage Not required supplied by Dupline signal line Terminals Type M12 socket connection Housing Type Flat pack design Dimension...

Страница 8: ...n den Sie sich bitte an In case of queries concerning this product or the Dupline system plea se contact Doepke Schaltger te GmbH Co KG Stellmacherstra e 11 D 26506 Norden Germany Tel 49 0 4931 1806 0...

Отзывы: