Upon installation, my units is alarming but I know my dock is wired correctly, 
why is this? 

Most likely it is an improper bonding issue.  Have your safety ground bonding system checked by a 
qualified electrician. 

My unit is alarming, and I have checked my safety ground bonding system . 
where is the stray electricity coming from? 

The Dock Lifeguard Unit is designed to detect any stray electricity whether it is at a lethal or non-lethal 
level.  Below are listed a few scenarios which may add in determining where your stray electricity is 
coming from: 

-

 

Dock De-Icers

:     Water aerators placed in the water are susceptible to leaking stray 

electricity in the water.   If your unit is detecting stray electricity around your dock, try 
isolating the De-Icer unit that is causing the problem by unplugging your or your neighbors 
De-Icer and seeing if the stray electricity goes away. 

-

 

Underwater Water Pumps

:  Underwater water pumps are subject to leaking electricity in 

the water.  A lot of these underwater pumps are 220Volt and are ran on non-GFCI’d 
breakers.   If you are using an submersible water pump,  it may be a good time to change 
it out to an above water pump. Current trend of governing bodies of lakes is to disallow 
underwater pumps and only allow above water pumps.   

-

 

Ambient Voltage of Water

:  Each body of water will inherently have some small level of 

electricity in it.  In most lakes this is between 0.05 and 1 volt.  Depending on your 

sensitivity settings of your unit, then number of LEDs shown on the front of the display 

will reflect this ambient voltage.   i.e.  You sensitivity jumper setting is set to 0.25 volts and 

you have 0.8 volts of ambient voltage in the water, then 3 LEDs will be lit on the Dock 

Lifeguard.   Note: Ambient voltage of your lake can be checked by using a standard volt 

meter and placing one lead in the water and the other touch the GROUND plug of an 

outlet. 

 

-

 

Back Feed from your Home

: If you have a well-grounded dock with a grounding rod < 25 

ohms, but your homes grounding rod is above the 25 ohm threshold, your electrical 

system may run into the situation where non-lethal stray electricity from your home (i.e. 

From a A/C Unit or Heat Pump) may bypass the home’s grounding rod and feed down to 

the grounding rod with lower resistance (The Dock) which is tied to your dock. To correct 

this situation you will need to correct the ground resistance of your home’s grounding rod, 

or you can run an isolated grounding rod to feed the Dock Lifeguard unit. In certain areas 

of the country where hard water is prevalent, the heating element of yours (or your 

neighbors) may short out and put electricity back on the ground wire which can be back 

fed down to your dock. 

 

-

 

It may not be your house or dock: 

Any nearby house or dock that shares the same safety 

ground from a shared transformer has the potential of putting hazardous electricity back 

on the ground wire  and then having it back fed to your dock..   Not only check your house, 

but check surrounding houses and docks for stray electricity. 

Содержание DOCK LIFEGUARD

Страница 1: ...Users Guide Basic Version 1 1...

Страница 2: ...probe This unit can ONLY give detection if it is installed maintained and located where stray electricity can reach it and where all residents can hear it as described in this manual This unit cannot...

Страница 3: ...horn at close range may harm your hearing Recommended Locations for Dock Lifeguard Install your Dock Lifeguard with an unobstructed view to allow viewing of the warning strobe when electricity is dete...

Страница 4: ...unded dock and to the ground of the electrical system of the dock Note You must have a proper bond of the dock lifeguard green wire to the dock safety ground for correct operation Pier Docks with Wood...

Страница 5: ...t to a metal underwater structure such as underwater bracing sea anchor cables or steel underwater dampening structures Non Detection Zones Underwater structures such as sea anchors with metal extrudi...

Страница 6: ...continued usefulness For instance the probe may gather algae after a long time in the water Wiping it clean annually will ensure that the range of the probe stays as consistent as possible In additio...

Страница 7: ...ash WARNING If the unit alarms and you are not testing the unit it is a warning of potentially dangerous situation that requires immediate attention NEVER ignore any alarm Ignoring the alarm may resul...

Страница 8: ...l Information Lethal Voltage is 2 volts AC per foot The Dock Lifeguard units are setup to trigger at approximately 1500 millivolts To see exact settings of your system you need to reference the sensit...

Страница 9: ...rigger Level Factory setting is set to trigger alarm when 4 LEDs are lit Alarm trigger point can be raised by turning the potentiometer counter clockwise and lowered by turning the potentiometer clock...

Страница 10: ...allow for adjusting the sensitivity level of the Dock Lifeguard unit The more sensitive the setting the further out the Dock Lifeguard will detect stray voltage X0 Nothing Jumped each LED 0 5 Volts X...

Страница 11: ...s common on Smith Lake AL Sensitivity will need to be decreased and the Alarm level raised in order to filter out the ambient voltage With decreased sensitivity comes decreased range of detection It i...

Страница 12: ...tors are not foolproof Like any electronic device Dock Lifeguard is made of components that can wear out or fail at any time You must test the unit weekly to ensure your continued protection Dock Life...

Страница 13: ...ate insurance coverage is your responsibility Consult your insurance agent For Warranty Service In many cases the quickest way to exchange your alarm is to return it to the original place of purchase...

Страница 14: ...and 1 volt Depending on your sensitivity settings of your unit then number of LEDs shown on the front of the display will reflect this ambient voltage i e You sensitivity jumper setting is set to 0 25...

Отзывы: