3. Setting Up and Running a Test
72A-2570-01 Rev. K 07/2011
3-25
Diagnosing Open-Circuit Response
An open-circuit response may be caused by the black test lead dropping off the
bushing, a poor connection, or damage within the test lead. The discrete
change in the lower frequency range in
shows
typical open-circuit behavior: about –90 to –100 dB. Investigate a test like this
to see if the open circuit lies in the test setup or the transformer.
Figure 3.39 Typical Open-Circuit Trace
Sample Test Results
This section provides typical results from a number of transformer windings
and designs. These are examples of how designs and phase results vary
between transformers.
Three Responses for One Transformer
shows the two open-circuit responses and the
short-circuit response of one phase of an autotransformer. The three traces are
clearly different at low frequencies.
Typically, the HV response starts at a much lower level than the LV response.
The short-circuit response approaches 0 dB at low frequency but comes back
in line with the HV response at higher frequencies.
Содержание SFRA
Страница 12: ...Sweep Frequency Response Analyzer SFRA User Guide xii 72A 2570 01 Rev K 07 2011...
Страница 14: ...Sweep Frequency Response Analyzer SFRA User Guide xiv 72A 2570 01 Rev K 07 2011...
Страница 24: ...Sweep Frequency Response Analyzer SFRA User Guide 2 4 72A 2570 01 Rev K 07 2011...
Страница 56: ...Sweep Frequency Response Analyzer SFRA User Guide 3 32 72A 2570 01 Rev K 07 2011...
Страница 78: ...Sweep Frequency Response Analyzer SFRA User Guide 5 18 72A 2570 01 Rev K 07 2011...
Страница 98: ...Sweep Frequency Response Analyzer SFRA User Guide A 20 72A 2570 01 Rev K 07 2011...
Страница 110: ...Sweep Frequency Response Analyzer SFRA User Guide C 6 72A 2570 01 Rev K 07 2011...
Страница 116: ...Sweep Frequency Response Analyzer SFRA User Guide D 6 72A 2570 01 Rev K 07 2011...