Instructions for installation, setup and operation - FP9000L-2/4/6/8
Page
11
of
16
FIRE/
C
" and "REL FIRE/
NC
" and in case of Fire - between terminals "REL FIRE/
C
" and "REL
FIRE/
NO
".
If relay outputs are not used, then its terminals remain free (nothing is connected to them).
5.4. Power supply connection
To the terminal with mains fuse connect feeding cable observing the following positions.
-
P - power wire " Phase";
-
N - power wire " None ";
-
"Earth" - safety ground wire.
The cable should be double insulated and section not less than 0,5 mm
2
for power cables and 1,5
mm
2
for the safety ground wire.
The other end of the feeding cable is connected to the mains using a junction box.
The mains power supply of the panel should be on a separate circuit.
6. PUTTING THE PANEL IN WORKING CONDITION
Check the connection to mains power supply.
Check the correct connection of peripheral devices.
Place the fuse in the terminal.
Join the feeding cables to the batteries, where as the batteries are connected in series. To the
positive terminal of the battery join the red wire and the negative – to the blue wire. The overall
voltage of both batteries must be greater than 17,6 V, otherwise the panel does not recognize
them. Thermal sensor in the panel place in the battery. With it you monitor the temperature and
control the mode battery charge.
If everything is done correctly and the lines parameters are within the factory settings, the panel
enters Duty Mode.
Set the accession of exits and the respective delays, if they are necessary.
7. LEVELS OF ACCESS
In panel FP9000L There are
4 LEVELS
of access to the various indications and control functions.
Access Level 1
This level of access is for all persons, whom can be expected to identify and react to Fire alarm or
fault. Visible are all light indicators.
Available are the following features:
suppression of built sounder;
displaying suppressed messages for Fire, Fault and Disabled components;
displaying the status of the lines;
Access Level 2
This is a level of access to persons, who are responsible for the safety and are trained and authorized to
operate the panel in the conditions:
Security;
Fire;
Fault;
Disabled component;
Test.