Instructions for installation, setup and operation - FP9000L-2/4/6/8
Page
10
of
16
Fig. 3
If controllable outputs are not used, directly to terminals "+Outx", "-Outx" a resistor 4,7k/0,5W is
connected, otherwise the outputs will be in Fault condition.
5.3.2.
Installation of the executive devices to RELAY OUTPUTS.
Used:
-
Terminal "+28VDC" - positive lead of the stabilized direct voltage for external devices (light and
sound signaling devices, executive devices, etc. );
-
Terminal "GND" – (negative lead for supplying the external devices);
-
Terminal of the corresponding relay outputs.
Relay outputs with changeover contacts for
Fault (REL Fault)
and
Fire (REL Fire)
conditions.
-
When in Fault condition of the panel, output -
REL Fault
, is activated immediately, regardless of
the type of fault. The output may not be disabled or delayed.
-
Upon entering the panel’s condition
Fire
, no matter what line, output -
REL FIRE
be activated
immediately. The output may not be disabled or delayed.
Fig. 4
-
REL
Fault
- terminals "REL Fault/
C
", "REL Fault/
NO
" and "REL Fault/
NC
" - potential free
relay contacts of the relay. In the absence of failure, there is a link between terminals "REL
Fault/
C
" and "REL Fault/
NO
", and in case of failure - between terminals "REL Fault/
C
" and
"REL Fault/
NC
".
-
REL FIRE
- terminals "REL FIRE/
C
", "REL FIRE/
NO
" and "REL FIRE/
NC
" - potential free
relay contacts of the relay. In standby mode there is a connection between terminals "REL