DMS 38MHR Скачать руководство пользователя страница 12

12

SYSTEM VACUUM AND CHARGE

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment
damage or improper operation.

Never use the system compressor as a vacuum pump.

CAUTION

!

Refrigerant tubes and the indoor coil should be evacuated using the
recommended 500 microns deep vacuum method. The alternate
triple evacuation method may be used if the procedure outlined
below is followed.

NOTE:  Always break a vacuum with dry nitrogen.

Using Vacuum Pump

1. Completely tighten flare nuts A, B, C, D, connect the

manifold gage charge hose to a charge port of the low side
service valve (see Fig. 14).

2. Connect the charge hose to vacuum pump.

3. Fully open the low side of manifold gage (see Fig. 15).

4. Start the vacuum pump.

5. Evacuate using either the deep vacuum or triple evacuation

method.

6. After evacuation is complete, fully close the low side of

manifold gage and stop the vacuum pump operation.

7. The factory charge contained in the outdoor unit is good for

up to 25 ft. (8 m) of line length. For refrigerant lines longer
than 25 ft. (8 m), add refrigerant, up to the allowable length,
as specified in the System Requirements section.

8. Disconnect the charge hose from the charge connection of

the low side service valve.

9. Fully open service valves B and A.

10. Securely tighten the service valve caps.

Outdoor Unit

Indoor Unit

Refrigerant

Service Valve

Low Side

High Side

A

B

C

D

A07360

Fig. 14

 - 

Service Valve

Manifold Gage

500 microns

Low side valve

High side valve

Charge hose

Charge hose

Vacuum pump

Low side valve

A07361

Fig. 15

 - 

Manifold

Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling
a vacuum of 500 microns and a vacuum gage capable of accurately
measuring this vacuum depth. The deep vacuum method is the best
way to assure a system is free of air and liquid water (see Fig. 16).

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET

TIGHT

DRY SYSTEM

2000

MICRONS

2500

3000

3500

4000

4500

5000

A95424

Fig. 16

 - 

Deep Vacuum Graph

Triple Evacuation Method

The triple evacuation method should only be used when the
vacuum pump is only capable of pumping down to 28 in. of
mercury vacuum and the system does not contain any liquid water.

Refer to Fig. 17 and proceed as follows:

1. Pump the system down to 28 in. of mercury and allow the

pump to continue operating for an additional 15 minutes.

2. Close the service valves and shut off the vacuum pump.

3. Connect a nitrogen cylinder and regulator to the system and

open until the system pressure is 2 psig.

4. Close the service valve and allow the system to stand for 1

hr. During this time, dry nitrogen can diffuse throughout the
system absorbing moisture.

5. Repeat this procedure as indicated in Fig. 17. The system

will then be free of any contaminants and water vapor.

CHECK FOR TIGHT, DRY SYSTEM

(IF IT HOLDS DEEP VACUUM)

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

RELEASE CHARGE INTO SYSTEM

BREAK VACUUM WITH DRY NITROGEN

EVACUATE

WAIT

A95425

Fig. 17

 - 

Triple Evacuation Method

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both the
indoor and outdoor unit has not shifted during shipment. Ensure
tubes are not rubbing against each other or any sheet metal. Pay
close attention to the feeder tubes, making sure wire ties on feeder
tubes are secure and tight.

Содержание 38MHR

Страница 1: ...ages are for illustration purposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS OUTDOOR 5 CLEARANCES OUTDOOR 8 INSTALLATION TIPS 9 OUTDOOR UNIT INSTALLATION 9 ELECTRICAL DATA 11 CONNECTION DIAGRAMS 11 SYSTEM VACUUM AND CHARGE 12 START UP 13 OUTDOOR UNIT DIAGNOSTIC GUIDES 13 ...

Страница 2: ...s hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation WARNING ELECTRICAL SHOCK HAZARD Failure ...

Страница 3: ...drips from the connection pipe before it enters the wall Piping and the interconnecting wiring are field supplied The illustration above is only a sketch Different models may be slightly different The following units are covered in these installation instructions Table 2 Unit Sizes Cooling Only SYSTEM TONS BTUh VOLTAGE PHASE OUTDOOR MODEL 0 75 9 000 115 1 38MHRC09A 1 1 00 12 000 115 1 38MHRC12A 1 ...

Страница 4: ...and local codes Use Electrical Data table MCA minimum circuit amps and MOCP maximum over current protection to correctly size the wires and the disconnect fuse or breakers respectively Per the caution note only stranded copper conductors with a 600 volt insulation rating wire must be used Recommended Connection Method for Power and Communication Wiring The main power is supplied to the outdoor uni...

Страница 5: ... 88 6 40 2 Heat Pump System Size Height H in mm Width W in mm Depth D in mm Weight Net lbs kg 9K 115 21 85 555 30 31 770 11 81 300 61 5 27 9 12K 115V 21 85 555 30 31 770 11 81 300 65 0 29 5 9K 208 230V 21 85 555 30 31 770 11 81 300 57 1 25 9 12K 208 230V 21 85 555 30 31 770 11 81 300 60 6 27 5 18K 208 230V 21 81 554 31 50 800 13 11 333 94 6 42 9 24K 208 230V 27 64 702 33 27 845 14 29 363 105 2 47 ...

Страница 6: ... 800 20 24 514 21 81 554 2 36 6 0 3 37 8 5 5 13 39 340 0 47 1 2 12 24 311 12 80 325 13 11 333 2 76 7 0 H H1 H2 D1 D2 D3 2 43 6 1 8 4 17 1 06 0 87 2 2 R 0 79 R 20 R 0 24 R 6 2 43 6 1 6 D W W1 W2 B1 B2 A2 A1 Unit inch mm Fig 3 Size 18K ...

Страница 7: ...7 DIMENSIONS OUTDOOR CONT Unit inch mm Fig 4 Size 24K ...

Страница 8: ...t C E A07894 Fig 5 Outdoor Unit Clearance Table 5 Outdoor Unit Clearance Dimensions UNIT MINIMUM VALUE in mm A 24 610 B 24 610 C 24 610 D 4 101 E 4 101 NOTE The outdoor unit must be mounted at least 2in 50mm above the maximum anticipated snow depth ...

Страница 9: ...inants to avoid damaging the refrigerant system Avoid sags in the suction line to prevent the formation of oil traps Insulate each tube with a minimum 3 8 in 10 mm wall thermal pipe insulation Inserting the tubing into the insulation before making the connections will save time and improve installation quality 1 Remove the service valve cover if provided with the unit 2 Cut the pipe with a pipe cu...

Страница 10: ... malfunction A fire hazard may also exist Therefore ensure all wiring is tightly connected S No wire should be allowed to touch the refrigerant tubing compressor or any moving parts S Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner S Connecting cable with the conduit shall be routed through hole in the conduit panel Over 1 57 4...

Страница 11: ...ible limits of the voltage range at which the unit will operate satisfactorily LEGEND FLA Full Load Amps MCA Minimum Circuit Amps MOCP Maximum Over Current Protection RLA Rated Load Amps CONNECTION DIAGRAMS S L N 115 1 60 Main PowerSupply 115 1 60 L N S L N Power to Indoor Unit CONNECTING CABLE OUTDOORTOINDOOR GND Ground Indoor Signal High Voltage 115 1 60 115 1 60 FIELD POWER SUPPLY GND Indoor Si...

Страница 12: ...Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the best way to assure a system is free of air and liquid water see Fig 16 500 MINUTES 0 1 2 3 4 5 6 7 1000 1500 LEAK IN SYSTEM VACUUM TIGHT TOO WET TIGHT DRY SYSTEM 2000 MICRONS 2500 3000 3500 4000 4500...

Страница 13: ...or unit s problems If possible always check the diagnostic codes displayed on the indoor unit first The diagnostic codes displayed on the outdoor units are listed on Table 10 Table 10 Unit Diagnostic Guides DISPLAY LED STATUS E1 Communication malfunction between indoor and outdoor units F0 Protection of over current F1 Open circuit or short circuit of outdoor ambient temperature sensor T4 F2 Open ...

Страница 14: ...P S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM 38MHR 02 Replaces IM 38MHR 01 Edition Date 6 17 ...

Отзывы: