background image

Digital Monitoring Products 

693/

791/793 Installation Sheet

2

3. Maximum number of devices per 2,500 feet circuit is 40.  

Note:

  Each panel allows a speci

Þ

 c number of supervised keypads.  Add additional keypads in the 

unsupervised mode.  Refer to the panel installation guide for the speci

Þ

 c number of supervised keypads 

allowed.  

4. Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 VDC.  If the 

voltage at any device is less than the required level, add an auxiliary power supply at the end of the circuit.  
When voltage is too low, the devices cannot operate properly.  

Refer to the 710 Module Installation Sheet (LT-0310) for more information.  Also see the LX-Bus/Keypad Bus Wiring 
Application Note (LT-2031).  

Voltage Protection Diode

Each keypad includes a separate clamping diode.  This diode may be installed across an electromagnetic lock power 
inputs to shunt excessive voltages away from the keypad.  Install diode as shown in Figure 2.

Note: The diode banded end 
must be connected to the  
supply voltage positive side.

Supply
Voltage

Electromagnetic Lock

or Magnetic Solenoid

Type Lock

Figure 2: Voltage Diode Installation

2-Button Panic Keys

The Panic key function of the 693, 791, and 793 keypads allows users to send Panic, Emergency, or Fire reports to 
the central station.  The user must press and hold the two Select keys until a beep from the keypad is heard.  At the 
beep, the panel sends an alarm report to the central station with the following zone numbers: 

• 19 = 

Panic

 

•  29 = non-medical 

Emergency

 • 

39 

Fire

You must program the Panic key function in order to use the Panic keys.  See Programming Instructions later in this 
document.  Install the supplied icon label below the top row of Select keys. 

Top Row Select Keys

Police

Emergency

Fire

Label shows Icons only.

Figure 3: Panic key label placement

Internal Speaker Operation

The Easy Entry keypads emit standard tones for key presses, entry delay, and system alerts.  When used with the 
XR200, XR200-485, XR2400F, or XR500XR500N Command Processor Panels, the speaker also provides distinct burglary, 

Þ

 re, zone monitor, and prewarn tones.  The Easy Entry keypads provide an alternate entry delay audible prewarn 

cadence that occurs when a zone alarm displays in the status list.  

Keyboard Backlighting

The Easy Entry keyboards light any time a key is pressed or the speaker sounds.  During an alarm condition, the 
keyboard turns Red to visually alert on-site staff.  The Red backlighting turns off when all areas in the system are 
disarmed or when the Sensor Reset function is used.  The keypad backlighting dims to medium brightness whenever 
the speaker is on.

How the Easy Entry Keypads Work

The 693, 791, and 793 keypads allow users to present a proximity credential to an access control reader that in turn 
sends their user code to the keypad.  Users can also manually enter their user code into the keypad.  The keypad 
reads the user code, veri

Þ

 es its authority with the panel, and then powers its on-board Form C relay releasing a door 

strike or magnetic lock.

Содержание Easy Entry 693

Страница 1: ...s The harness connections and color codes are shown in Figure 1 Surface and Backbox Mounting Holes Combined 4 square adn 3 gang switch box Mounting Holes Keypad Base Back Surface and Backbox Mounting Holes 1K EOL 1K EOL 1K EOL 1K EOL Green White Connect Reader Data 0 White Connect Reader Data 1 Orange Door Strike Normally Open Gray Door Strike Common Violet Door Strike Normally Closed Yellow White...

Страница 2: ...l sends an alarm report to the central station with the following zone numbers 19 Panic 29 non medical Emergency 39 Fire You must program the Panic key function in order to use the Panic keys See Programming Instructions later in this document Install the supplied icon label below the top row of Select keys Top Row Select Keys Police Emergency Fire Label shows Icons only Figure 3 Panic key label p...

Страница 3: ...data wire from the reader Data 0 to the Green White wire on the 5 wire keypad harness 1K EOL 1K EOL 1K EOL 1K EOL Green White Connect Reader Data 0 White Connect Reader Data 1 Orange Door Strike Normally Open Gray Door Strike Common Violet Door Strike Normally Closed Yellow White White Yellow Orange White White Orange Red White White Red Brown White White Brown Black Data Bus 693 Ground 791 793 Gr...

Страница 4: ...he factory default address is set at 01 To change the current address press any Select key and then enter the new address using the appropriate number keys on the keyboard It is not necessary to enter a leading zero for addresses 01 to 09 Select Supervised or Unsupervised KEYPAD MODE You can conÞgure the keypad for either supervised or unsupervised operation Supervise keypads that have zones conne...

Страница 5: ... user codes ALL NO YES DELAY 2 Select the number of seconds the keypad should wait when an area system displays ALL NO YES during arming disarming or a HOME SLEEP AWAY system waits during arming only If No or YES or HOME SLEEP or AWAY is not pressed before the delay expires the keypad automatically selects the YES or the AWAY key Select zero 0 for no delay The delay can be one to nine 1 9 seconds ...

Страница 6: ...The Form C relay draws up to 30mA of current and its contacts are rated for 1 Amp at 24 VDC Access the User Menu You can also use a card reader to access the User Menu When the MENU NO YES displays present your proximity card to the reader Door Strike Relay Operation As soon as the user code sent from the reader has been veriÞed by the panel the keypad Door Strike relay activates for Þve seconds D...

Страница 7: ...TER CODE Present your card to the reader Once validated by the system both areas arm or disarm automatically and the Door Strike relay activates Home Away system Arming and Disarming Present your card to the reader If the system is armed once the card is validated all areas are disarmed If the system is disarmed when you present your card once the card is validated all areas are armed in the AWAY ...

Страница 8: ... conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Changes or modiÞcations made by the user and not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment NOTE This equipment has been tested and found to comply with...

Отзывы: