background image

 16 

734INT Installation and Programming Guide     |     Digital Monitoring Products, Inc.

734INT Address Table

To set the module’s address, move the DIP switches to the appropriate positions. See 

Figure 10 for Keypad Bus and AX‑Bus DIP switch positions.

Table 2: Device Addresses and 734INT Zone Numbers

Keypad Bus

AX‑Bus

DEVICE/

DOOR

ZONES

DEVICE/

DOOR

ZONES

DEVICE/

DOOR

ZONES

DEVICE/

DOOR

ZONES

DEVICE/

DOOR

ZONES

DEVICE/

DOOR

ZONES

1

11‑14

501

501‑504

601

601‑604

701

701‑704

801

801‑804

901

901‑904

2

21‑24

505

505‑508

605

605‑608

705

705‑708

805

805‑808

905

905‑908

3

31‑34

509

509‑512

609

609‑612

709

709‑712

809

809‑812

909

909‑912

4

41‑44

513

513‑516

613

613‑616

713

713‑716

813

813‑816

913

913‑916

5

51‑54

517

517‑520

617

617‑620

717

717‑720

817

817‑820

917

917‑920

6

61‑64

521

521‑524

621

621‑624

721

721‑724

821

821‑824

921

921‑924

7

71‑74

525

525‑528

625

625‑628

725

725‑728

825

825‑828

925

925‑928

8

81‑84

529

529‑532

629

629‑632

729

729‑732

829

829‑832

929

929‑932

9

91‑94

533

533‑536

633

633‑636

733

733‑736

833

833‑836

933

933‑936

10

101‑104

537

537‑540

637

637‑640

737

737‑740

837

837‑840

937

937‑940

11

111‑114

541

541‑544

641

641‑644

741

741‑744

841

841‑844

941

941‑944

12

121‑124

545

545‑548

645

645‑648

745

745‑748

845

845‑848

945

945‑948

13

131‑134

549

549‑552

649

649‑652

749

749‑752

849

849‑852

949

949‑952

14

141‑144

553

553‑556

653

653‑656

753

753‑756

853

853‑856

953

953‑956

15

151‑154

557

557‑560

657

657‑660

757

757‑760

857

857‑860

957

957‑960

16

161‑164

561

561‑564

661

661‑664

761

761‑764

861

861‑864

961

961‑964

Содержание 734INT

Страница 1: ...INSTALLATION AND PROGRAMMING GUIDE 734INT Access Control Module...

Страница 2: ......

Страница 3: ...s 9 Connect a Wiegand Card Reader 11 Set the 734INT Address 14 TABLE OF CONTENTS Program the Panel 17 Device Setup 17 Device Number 17 Device Name 17 Device Type 18 Communication Type 18 Program the 7...

Страница 4: ...Keypad Bus Wiring Specifications 32 Public Card Formats 33 International Certifications 34 Intertek ETL Listed 34 Product Specifications 36 Readers and Credentials 37...

Страница 5: ...s that the module is communicating with the panel The 734INT Access Control Module allows you to use the powerful built in access control capability of DMP Panels using smartcard proximity mag stripe...

Страница 6: ...rom XR150INT XR550INT Series panels Keypad In and Out Connections The keypad in KYPD IN connection receives and transmits data to the panel Keypad Bus or AX Bus The keypad out KYPD OUT connection rece...

Страница 7: ...ON NC C NO GRN YEL RED Piezo 1 2 3 4 5 6 7 8 10 11 12 13 14 9 LC AS REDWHTGRN BLK Z1 Z2 Z3 Z4 Z4 RA GND GND KYPD IN RED ON 1 2 3 4 Door Relay Terminal Reader Inputs Status Indicator Outputs Zones To...

Страница 8: ...ple mounting holes that allow you to mount the module on a single gang switch box DMP recommends mounting the 734INT near the protected door Refer to Figure 2 for mounting hole locations on the housin...

Страница 9: ...s resistive at 12 24 VDC When connecting multiple locks to the Form C relay the total current for all locks cannot exceed 10 Amps If the total current for all locks exceeds 10 Amps problems may arise...

Страница 10: ...dual connector harness to allow connection to other devices up to the maximum number of devices supported When the 734INT is powered from 24 VDC do not connect devices to KYPD OUT header Status LEDs...

Страница 11: ...NO C NC To Panel Keypad Bus Common RED PROG PIEZO RED KYPD IN RED KYPD OUT RED WIEGAND READ LED DATA XMT LED RELAY ON YEL GRN Normally Open 12 24VDC Power Supply 734 Series Module Model 333 Suppressor...

Страница 12: ...als If the device being controlled by the relay is connected to the NO and C terminals install the suppressor on the NO and C terminals Conversely if the device is connected to the NC and C terminals...

Страница 13: ...nals 13 and 14 connect to zone 4 Zone 4 provides a non powered Class B ungrounded zone suitable for connection to fire devices such as heat detectors or pull stations Note You must provide a mechanica...

Страница 14: ...1 2 3 4 5 6 7 8 10 11 12 13 14 9 LC AS REDWHTGRN BLK Z1 Z2 Z3 Z4 Z4 RA GND GND 1k EOL 1k EOL 1k EOL 1k EOL Zone 3 can also be wired normally closed with an in line 1k Ohm resistor Table 1 734INT Zone...

Страница 15: ...green wire carries Data Zero D0 and the white wire carries Data One D1 The red wire connects 12 24 VDC 200 mA maximum power and the black wire is ground The wire colors may be different depending on t...

Страница 16: ...ched ground for a remote annunciator that turns on when the Zone 2 Bypass timer expires Connect the wire from the RA Terminal to a remote annunciator The remote annunciator silences when the RA restor...

Страница 17: ...llation and Programming Guide 13 Figure 9 Card Reader Wiring Red 12 24VDC Black GND Orange or Brown Yellow Green Data 0 Wiegand Card Reader White Data 1 1 2 3 4 5 6 7 8 10 11 12 13 14 9 LC AS RED WHT...

Страница 18: ...Addresses Explained XR550INT panels are capable of access control expansion using any of the five AX LX Bus headers AX LX500 600 700 800 and 900 An AX Bus address can accommodate one door output and...

Страница 19: ...ming Guide 15 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1...

Страница 20: ...813 813 816 913 913 916 5 51 54 517 517 520 617 617 620 717 717 720 817 817 820 917 917 920 6 61 64 521 521 524 621 621 624 721 721 724 821 821 824 921 921 924 7 71 74 525 525 528 625 625 628 725 725...

Страница 21: ...ess CMD to advance to the next option Refer to the panel programming guide as needed DEVICE SETUP Advance to DEVICE SETUP then press any select area or top row key to enter the setup menu Device Numbe...

Страница 22: ...RD OPTIONS or 734 OPTIONS in Device Setup Device Type Press any select area or top row key then select DOOR as the device type Communication Type If the module is connected to the Keypad Bus select KP...

Страница 23: ...del 330 24 4 wire programming harness with in line resistor Caution Do not connect a keypad using a standard Model 330 harness if using a 24 V power supply Damage to the keypad could occur You can als...

Страница 24: ...y defaults Press any select key or area to enter the Initialization Menu Press CMD to advance to Access Options Initialize Confirm Option After selecting YES to clear the Access Options the 734INT dis...

Страница 25: ...le zone 2 When the onboard Form C relay activates and the user opens the door connected to zone 2 the zone is delayed for the number of seconds programmed in ZONE 2 BYPASS TIME allowing the user to en...

Страница 26: ...ting YES turns the relay off when zone 2 changes state Selecting NO leaves the relay on when zone 2 changes state Turning off the relay allows a long strike time to be automatically ended upon zone 2...

Страница 27: ...iring details refer to Figure 8 Activate Strike Relay and Bypass Wire zone 3 as normally open with a 1k Ohm EOL resistor When zone 3 shorts the onboard Form C relay activates for the programmed number...

Страница 28: ...t remote annunciator open collector RA operation The default is NO Card Formats Select DMP to allow credentials that use a 26 45 bit data string The menu advances to Require Site Code Select CUSTOM to...

Страница 29: ...t 1 is the default format In the event that a card with an unrecognized format is used that card will be read in the format that is programmed in slot 1 To restrict card reads to specific formats only...

Страница 30: ...select area to rename the card format Press CMD to save and advance Wiegand Code Length When using a custom credential enter the total number of bits to be received in Wiegand code including parity bi...

Страница 31: ...efault is 1 Press select area 4 to clear the site code length and enter a number between 1 24 Press CMD to save Default is 8 User Code Position and Length Define the user code start bit position and l...

Страница 32: ...verification door access is only granted when any one site code programmed at the SITE CODE ENTRY option matches the site code received in the Wiegand string Site Code Display You can program up to e...

Страница 33: ...lt is 5 All bits are read and converted into a decimal number string The number string is left padded with 0 zero if needed for long user code lengths Example decoded 1234567 10 digits 0001234567 4 di...

Страница 34: ...t turns off at the end of the door strike timer Press the second select key or area to choose SITE Accept Site Code Door access is granted when the Wiegand site code string received matches any site c...

Страница 35: ...EYPAD After programming is saved the REMOVE KEYPAD option continually displays with no timeout if the keypad remains connected to the module After five seconds the piezo begins sounding continually To...

Страница 36: ...ackup Maximum distance for any one bus circuit length of wire is 2 500 ft regardless of the wire gauge This distance can be in the form of one long wire run or multiple branches with all wiring totali...

Страница 37: ...nd Code Length Site Code Position Site Code Length User Code Position User Code Length User Code Digits H10301 26 bit 26 1 8 9 16 5 H10302 37 bit w o FAC 37 0 1 1 35 11 H10304 37 bit w FAC 37 1 16 17...

Страница 38: ...ty requirements for components of fire intruder hold up CCTV access control and social alarm systems EN 50130 5 2011 Alarm systems Environmental test methods EN 50131 1 2006 A1 2009 Alarm systems Intr...

Страница 39: ...ts for harmonic current emissions EN 61000 3 3 2013 Electromagnetic compatibility EMC Part 3 3 Limits Limitation of voltage changes voltage fluctuations and flicker in public low voltage supply system...

Страница 40: ...ICATIONS Primary Power 8 5 VDC to 28 5 VDC Current Draw Standby 240 mA Includes 200 mA for proximity reader Alarm 260 mA Includes 200 mA for proximity reader Form C Relay 35 mA at 12 24 VDC Zones 5 VD...

Страница 41: ...eypad MP 5365 MiniProx proximity reader MX 5375 MaxiProx proximity reader PP 6005B ProxPoint Plus proximity reader PR 5355 ProxPro proximity reader with keypad PR 5455 ProxPro II proximity reader TL 5...

Страница 42: ...iegand Smartcard Readers Delta3 Mullion mount smartcard reader Delta5 Single gang box mount smartcard reader Delta6 4 Smartcard reader with keypad CSR 35P Bluetooth smartcard reader 13 56 MHz Smartcar...

Страница 43: ......

Страница 44: ...LT 0737INT 20314 1 01 2020 Digital Monitoring Products Inc...

Отзывы: