Digital Monitoring Products
1119 Installation Guide
2
Programming the 1119 in the Panel
To allow the 1119 sounder to be turned on or silenced by the panel, the OUTPUT serial number must be programmed
as an output in Output Information, and assigned to the 1119 zone ALARM ACTION output section in panel Zone
Information programming.
If the 1119 is programmed as a zone, but the output is not programmed into the panel at Output Information, the
1119 annunciates up to five minutes dependant on the sounder cutoff jumper setting and cannot be silenced from
the panel.
If the 1119 is programmed into Output Information, but not assigned to the 1119 zone ALARM ACTION output section,
the sounder only operates for a few seconds when the 1119 zone is tripped even if the sounder cut off jumper is set
to five.
Output Programming
Enter the output number, output name, and eight digit OUTPUT serial number. For extended battery life, a 15
second slow response output is recommended. This gives the 1119 an estimated battery life of 2 1/2 years,
depending on usage. A list of the slow response outputs for each panel is listed below.
XR100/XR500: 450-474
XTL/XT30/XT50: 31-34
Use the following output numbers for fast response outputs that respond within 1 second. The typical battery life is
3 months. Fast response outputs are listed below.
XR100/XR500: 480-499
XTL/XT30/XT50: 41-44
Zone Programming
Program the 1119 in Zone Information as a Day type zone (DY) when local annunciation at the keypad is required in
addition to the sounder when the panel is disarmed. If the 1119 sounder is to be the only annunciation during the
disarmed state, program as a Night type zone (NT). At the Serial Number: prompt enter the eight-digit ZONE serial
number. To allow the panel to control the output, program the output number in the zone ALARM ACTION.
Supervision Time
When programming the 1119 in both Zone Information and Output Information, the supervision time should be the
same, typically 240 minutes for burglary applications.
Note: When a receiver is installed, powered down and powered up, the panel is reset, or programming is complete,
the supervision time is reset. If the receiver has been powered down for more than one hour, the 1119 may take
up to an additional hour to send a supervision message unless tripped, tampered, or powered up. This operation
extends battery life. A missing message may display on the keypad until the supervision message is sent. Refer to the
panel programming guide as needed.
Selecting the Proper Location (LED Survey Operation)
The 1119 provides a survey capability to allow one
person to confirm communication with the receiver
while the cover is removed. The 1119 PCB Red Survey
LED (See Figure 2) turns on whenever data is sent to
the receiver then immediately turns off when the
receiver acknowledgement is received. Pressing the
tamper switch is a convenient way to send data to the
receiver to confirm operation. When the 1119 does
not receive an acknowledgement from the receiver
the survey LED remains on for about 8 seconds to
let you know communication is not established.
Communication is also faulty when the LED flashes
multiple times in quick succession. Relocate the
1119 or receiver until the LED immediately turns off
indicating the 1119 and receiver are communicating
properly. Proper communication between the 1119 and
receiver is verified when for each press or release of
the tamper switch, the LED blinks immediately on and
immediately off.
Figure 2: 1119 Wireless Sounder PCB
Mounting Holes
Model
1119
RED LED
(SURVEY)
TAMPER
SWITCH
SOUNDER
Mounting Holes
Zone
terminals
Red
Survey
LED
Locking Screw
Locking Screw
1
SEC
5
MIN
SOUNDER
CUTOFF
ZONE
OUT