We recommend that the connecting wire which is used to connect the meter to 
the outside circuit should be sized according to local codes and regulations for 
the ampacity of the circuit breaker or over current device used in the circuit. 

An external switch or a circuit-breaker should be installed on the inlet wire, 
which will be used as a disconnection device for the meter. And there it is 
recommended that the switch or circuit-breaker is near the meter so that it is 
more convenience for the operator. The switch or circuit-breaker should comply 
with the specifications of the buildings electrical design and all local regulations. 

This meter can be installed indoor directly, or in a meter box which is waterproof 
outdoor, subject to local codes and regulations. 

To prevent tampering, secure the meter with a padlock or a similar device. 

The meter has to be installed against a wall which is fire resistant. 

The meter has to be installed in a good ventilated and dry place. 

The meter has to be installed in a protection box when placed in dangerous or 
dusty environment. 

The meter can be installed and used after being tested and sealed with a letter 
press printing. 

The meter can be installed on a 35mm DIN rail or direct on a meter board with 
screws. 

The meter should be installed in an available height so that it is easy to read. 

When the meter is installed in an area with frequent surges due to e.q. 
thunderstorms, welding machines, inverters etc, protect the meter with Surge 
Protection Devices 

After finishing installation, the meter must be sealed to prevent tampering. 

Connection of the wires should be done in accordance with the underneath 
connection diagram. 

 
 
 
 

A. Direct series 

CAUTION 

 

Turn off and lock out all power supplying the energy meter and the 
equipment to which it is installed before working on it. 

 

Always use a properly rated voltage sensing device to confirm that power is 
off. 

 

WARNING 

 

Installation should be performed by qualified personnel familiar with 
applicable codes and regulations. 

 

Use isolated tools to install the meter. 

 

Fuse or thermal cut-off or single-pole circuit breaker can’t be fitted on the   
supply line and not the neutral line. 

 

 

 

Содержание PRO-1250 Series

Страница 1: ...se four wire energy meter 1 1 Safety instruction 1 2 Foreword 1 3 Performance criteria 1 4 Specifications 1 5 Basic errors 1 6 Description 1 7 Dimensions 1 8 Installation 1 9 Operating 1 10 Troublesho...

Страница 2: ...ground and label devices systems and circuits according to safety and Regulatory standards Use for the intended purpose The equipment device module may only be used for the application cases specified...

Страница 3: ...member of the Inepro Group The other names appearing in this manual may be trade names the use of these names by third parties for their own purposes may infringe the rights of the owners 1 2 Forewor...

Страница 4: ...d 6KV 1 2 S waveform Basic current Ib CT version 1A Direct version 10A Maximum rated current Imax CT version 5A Direct version 100A Operational current range 0 4 Ib Imax Over current withstand 30Imax...

Страница 5: ...ription A Front panel B Cover C Base D Security hasp Material Front panel PC inflammable retarding Cover ABS inflammable retarding Base ABS inflammable retarding 1 7 Dimensions Height 130 mm Width 126...

Страница 6: ...meter has to be installed in a protection box when placed in dangerous or dusty environment The meter can be installed and used after being tested and sealed with a letter press printing The meter ca...

Страница 7: ...color and one decimal is marked with red The PRO 1250D series energy meter is equipped with 5 2 LCD display which is used as recording consumption and can t be reset to zero The reading accuracy is 1...

Страница 8: ...ank wire or other material as you will have the chance of an electricity shock and a possible chance for health damage Turn off and lock out all power supplying the energy meter and the equipment to w...

Страница 9: ...or L2 or L3 when power supply is input Reinstall terminal screws on the 1 2 3 4 5 6 and 7 Make sure all screws are fixed Than there should be a 230V 50Hz AC voltage between the terminal screws on the...

Страница 10: ...is is why it seems like the meter won t count Please contact your technical supporter to replace this meter No test pulse output Is DC power supply connected to the meter Is the connecting correct May...

Отзывы: