DMEGC Photovoltaic Modules Installation Manual

- 12 -

DMEGC modules are supplied with connectors used for system electrical connections. We strongly
recommends using the genuine connector type specified by DMEGC's product data sheet. Any choice
of a different connector type other than specified may void the warranty of the module.

To ensure reliable electric connection and to prevent possible intrusion of humidity, two connectors
must be mated and locked together until a click can be heard.

Long-term exposure to wet environments may cause connectors' poor connectivity, resulting in current
leakage and poor conductivity which voids the warranty. DMEGC recommends proper
connector/cable/wire management to prevent moisture intrusion. Depending on the amount of
humidity, DMEGC recommends periodic inspections of the installation system to maintain optimal
module performance.

The DC current generated by photovoltaic systems can be converted into AC and fed into a public
Grid. As local utilities’ policies on connecting renewable energy systems to the Grids vary from region
to region. Always seek the advice from a qualified system designer or integrator. Building permits,
inspections and approvals by the local utility are generally required.

Especially for larger installations DMEGC recommends lightning protection following the local
requirements and regulations.

6. Grounding

For grounding and bonding requirements, please refer to regional and national safety and electricity

standards. If grounding is required, use a recommended connector type for the grounding wire.

DMEGC PV Modules use an anodic oxidized aluminum frame to resist corrosion, so the frame of

Modules should be connected to the equipment grounding conductor to prevent thunder and electrical
shock.

The frame rails have pre-drilled holes marked with a grounding sign, these holes should be used for

grounding purposes and should not be used for mounting the Modules.

We recommends always refer to local state and national code requirements for PV module grounding.

DMEGC highly recommends negative grounding if it's allowed by local authorities.

When attaching the frame grounding hardware and wire to the frame it must be placed corresponding

to the ground symbol stamped location to ensure proper electrical connection.

DMEGC recommends one of the following parts for grounding:
1) Use M8 bolt and washer to bond the ground wire and aluminum frame through the grounding hole

(as shown below left). The tightening torque is 3-7Nm. All nuts and washers should be made of stainless
steel. 4-14 mm

2

(AWG 6-12) exposed copper wire is recommended as ground wire.

Содержание DM M2-60BW Series

Страница 1: ...agnetics Co Ltd DMEGC Solar Energy Hengdian Industrial Area Dongyang City Zhejiang Province China Tel 86 579 86554950 Fax 86 579 86554845 Email solar dmegc com cn DMEGC Photovoltaic Modules Installati...

Страница 2: ...RE SAFETY 4 3 PRODUCT IDENTIFICATION 4 4 MECHANICAL INSTALLATION 5 4 1 SELECTING THE LOCATION 5 4 2 TILT ANGLE SELECTION 5 4 3 CONVENTIONAL REQUIREMENTS 6 4 4 INSTALLATION METHODS 7 4 5 ATTACHMENT GUI...

Страница 3: ...30 applocation class A Modules rated for use in this applications class may be used in system operating at greater than 50V DC or 240W where general contact access is anticlpated Modules qualified for...

Страница 4: ...they are ready to be installed Store pallets in a ventilated rain proof and dry location until the Modules are ready to be unpacked During the transportation do not to apply direct pressure on the bac...

Страница 5: ...module unnecessarily during installation The glass surface and the frame may be hot there is a risk of burns and electric shock Do not work in the rain snow or in windy conditions Avoid exposing cabl...

Страница 6: ...heet and the mounting surface Roof construction and installation may affect the fire safety of the building Improper installation may create hazards in the event of a fire Use appropriate components s...

Страница 7: ...he coastline Confirm with DMEGC install after obtaining approval Modules must be installed or operated in areas where salt hail snow sand dust air pollution chemically active acid rain soot etc are ex...

Страница 8: ...is 2900 PSI 20 Mpa in order to avoid potential damages to module frames Follow the instruction of the clamping system supplier Provide adequate ventilation under the modules in conformity to your loc...

Страница 9: ...e suggest stainless steel M8 bolts should be around 15 20 N m the mounting details are shown in the following figures 4 4 2 Mounting with Clamps When choosing this type of clamp mounting method use at...

Страница 10: ...eet a maximum positive pressure of 1600Pa and negative pressure of 1600 Pa this design load was then tested with a safety factor of 1 5 times The high loading capacity applies to severe environment li...

Страница 11: ...DMEGC Photovoltaic Modules Installation Manual 9 4 5 1Framed module bolt and clamp installation...

Страница 12: ...DMEGC Photovoltaic Modules Installation Manual 10 4 5 2 Frameless clamp installation...

Страница 13: ...mum number of series connected modules depends on system design the type of inverter used and environmental conditions Based on the maximum series fuse rating of module and local electrical installati...

Страница 14: ...l utility are generally required Especially for larger installations DMEGC recommends lightning protection following the local requirements and regulations 6 Grounding For grounding and bonding requir...

Страница 15: ...381 are used with metal framed photovoltaic solar panels and related products that require grounding for safety reasons 3 Addition Third party Grounding Devices DMEGC PV Modules can be grounded using...

Страница 16: ...ater and a soft sponge or cloth for cleaning A mild nonabrasive cleaning agent can be used to remove stubborn dirt In order to reduce the potential for electrical and thermal shock DMEGC recommends cl...

Страница 17: ...out of or in any way connected with such installation operation use or maintenance No responsibility is assumed by DMEGC for any infringement of patents or other rights of third parties which may res...

Страница 18: ...xxxB6 60NT DMGxxxB6 60NT DMxxxM2 B60NT DMxxxM2 B60NT Group 5 72 156 75 cells modules with aluminium frame xxx 355 370 in increment of 5 DMGxxxM6 72BT DMGxxxM6 72BW DMGxxxM6 72ST DMGxxxM6 72SW DMGxxxM6...

Страница 19: ...DMxxxM2 B72HBT DMxxxM2 B72HSW DMxxxM2 B72HBW Group 11 120 166 cells modules with aluminium frame xxx 355 375 in increment of 5 DMxxxM6 G60HST DMGxxxM6 G60HBT DMxxxM6 G60HSW DMxxxM6 G60HBW Group 12 120...

Отзывы: