XS-110
Signal Adder Converter
Page 12 of 24 XS-110 User Manual MAN-EN-DE-XS110-01.02_13
All rights reserved to DLG Automacao Industrial
Default triggering
Default triggering turns the analog output a function of only the last sensor triggered. For
instance, for a XS-110 configured for 10 inputs, the current output will be 20 mA only when the
10
th
input is triggered, regardless of the state of the other 9 inputs.
Sequential triggering
The XS-110 works sequentially (in pairs), i.e., if only one input is triggered (except the first
input), the output will not change. That means that the equipment will consider only the last two
consecutive triggered inputs. As an example, for a XS-110 configured with 10 inputs, the output
will be set to 20 mA only if the 10th AND 9th inputs are triggered. Taking the same case as
another example, if all except the 9
th
inputs are triggered, the output will be 16.8 mA (or 8 V),
because the last two consecutive triggered inputs are the 7
th
and the 8
th
.