Diagnostics
The LMP-100 provides diagnostic information, describing in detail its operation status. The
diagnostic information is encoded in 42 bytes, as shown below.
byte 0
bytes 1 and 2
byte 3
byte 4
...
byte 41
Diagnostic byte count
Reserved
Operation
diagnostics
Rule R01 diagnostics
...
Rule R38 diagnostics
Diagnostic is comprised of several conditions mapped into bits, where bits with value 1
indicate an alarmed condition.
Byte 0 indicates the number of available diagnostic bytes. The LMP-100 provides 42
diagnostic bytes.
Bytes 1 and 2 are reserved.
Byte 3 contains the Modbus rules overall diagnostics, encoded as shown in table 5.
Byte Bit
Condition
Description
Comments
3
0
Reserved
1
Reserved
2
Reserved
3
Reserved
4
Reserved
5
Exception in Modbus
response
While processing the
Modbus rules, at least one
slave returned a response
with an exception.
The LMP-100 remains
in operation. It is
possible to check
which slaves produced
the exception by
checking the rule
specific diagnostics.
6
Timeout in Modbus
response
While processing the
Modbus rules, at least one
slave did not return a
response within the time
period specified by the
“Modbus response timeout”
parameter.
The LMP-100 remains
in operation. It is
possible to check
which slaves produced
the exception by
checking the rule
specific diagnostics.
7
Error in Modbus response
While processing the
Modbus rules, at least one
slave returned a response
The LMP-100 remains
in operation. It is
possible to check