IM
–111
MODBUS UNIVERSAL INDICATOR
Page 24 of 44
IM
–111 User manual
MAN-EN-DE-IM111-01.00_16
All rights reserved to DLG Automação Industrial © 2011
– 2016
9 - MODBUS TABLE
Ad
d
res
s
O
ff
se
t
Mnemonic
Description
Def
ault
Up
p
er
limit
L
o
w
er
limit
Read/Write
Retentive/
Non-
retentive
40001
0
EAI1
Indicated variable (display)
R
40002
1
MSA1
Alarm 1 and 2 status
R
40003
2
SR01
Relay 1 and 2 status
R
40004
3
STDIV
General status
R
40005
4
TAMB
Ambient temperature (TC cold junction
compensation)
120.0
-40.0
R
40006
5
R101
Analog output value
0
100.0
0
R
40007
6
LDREL
Turn on/off relay 1 and 2
0
12
0
R/W
Modbus communications settings
40008
7
ID
Slave address
1
255
0
R/W R
40009
8
BR0
Baud rate
1
4
0
R/W R
40010
9
PAR0
Parity
2
2
0
R/W R
40011
10
DR0
Response delay
10
100
0
R/W R
Input settings
40012
11
TYPIN
Input type
13
16
0
R/W R
40013
12
UNTMP
Temperature unit
0
1
0
R/W R
40014
13
FMNIN
Minimum input frequency
0
30000
0
R/W R
40015
14
FMXIN
Maximum input frequency
30000
30000
0
R/W R
40016
15
ENGLO
Minimum engineering unit
0
30000
–9999
R/W R
40017
16
ENGHI
Maximum engineering unit
30000
30000
–9999
R/W R
40018
17
ENGDP
Decimal point
0
3
0
R/W R
40019
18
OFSIN
Input offset
0
30000
-9999
R/W R
40020
19
FLTIN
Input filter
1
100
0
R/W R
40021
20
LINON
Enable linearization
1
1
0
R/W R
40022
21
BRSEL
Burn-out selection
1
3
0
R/W R
40023
22
BRUNDER
Lower burn-out value
1
30000
–9999
R/W R
40024
23
BRUPPER
Upper burn-out value
1
30000
–9999
R/W R
Alarm 1 configuration
40025
24
SPAL1
Alarm 1 set point
0
30000
–9999
R/W R
40026
25
TPAL1
Alarm 1 type
0
3
0
R/W R
40027
26
HTAL1
Alarm 1 hysteresis
15
30000
-9999
R/W R
40028
27
T1AL1
Alarm 1 T1
0
100
0
R/W R
40029
28
T2AL1
Alarm 1 T2
0
100
0
R/W R
Alarm 2 configuration
40030
29
SPAL2
Alarm 2 set point
0
30000
-9999
R/W R
40031
30
TPAL2
Alarm 2 type
0
3
0
R/W R
40032
31
HTAL2
Alarm 2 hysteresis
0
30000
-9999
R/W R
40033
32
T1AL2
Alarm 2 T1
0
100
0
R/W R
40034
33
T2AL2
Alarm 2 T2
0
100
0
R/W R
Input linearization
40035
34
LIN_IN_01
Input linearization
– point 1
0
30000
-9999
R/W R
40036
35
LIN_IN_02
Input linearization
– point 2
0
30000
-9999
R/W R
40037
36
LIN_IN_03
Input linearization
– point 3
0
30000
-9999
R/W R
Содержание IM-111
Страница 1: ...User manual Modbus Universal Indicator MAN EN DE IM111 01 00_16 MODBUS UNIVERSAL INDICATOR IM 111 ...
Страница 2: ......
Страница 41: ...Notes ...
Страница 42: ......
Страница 43: ......