DLG E-BOX-48100R LFP Battery User Manual
8
followed and the LFP battery has no charge remaining when it is checked,
consider it to be damaged. Do not attempt to recharge or use it. Replace
it with a new LFP battery.
See previous storage temperature conditions.
The self-discharge of the LFP battery is 1-2% per month. Keep the
battery SOC to 40%-60% during storage.
1.
Disconnect the LFP battery from all loads and, if present, the
charging device.
2. Store the battery in a cool and dry place without direct sunshine.
3. Keep the battery away from corrosive substances, inflammable and
explosive material as well as hazardous gases.
4. For long-term storage (
>
6months), charge the LFP battery to more
than 80% of its rated capacity before storage. The battery needs to be
recharged every 6months to more than 80%of the rated capacity.
6 Installation and configuration
6.1 Installation preparation
6.1.1 Safety Requirements
Only those who have been trained in the power system and have a
good knowledge of the power system are allowed to install the device.