REFRIGERATION TROUBLESHOOTING
Page 81 of 23
PRODUCT TOO COLD OR FROZEN
Possible Cause:
Compressor runs too long or continuously
WHAT TO CHECK
SOLUTION
1. Is the temperature control the correct one for the equipment being used?
YES
2. Is the temperature control set properly?
YES
3. Is the temperature control bulb located properly?
YES
4. Is the temperature control operational?
YES
5. Does the evaporator frost over completely while the system is running?
YES
6. Consult the Dixie -Narco Factory Service at 1-800-688-9090 or your
Dixie-Narco Representative.
NOTE: Have the vender Model & Serial number available.
1.
NO
, install correct control
2. NO,
adjust to desired setting.
3. NO,
correct its position.
4. NO,
check.
5. NO,
check for leaks or low
charge.
NOISY REFRIGERATION UNIT
POSSIBLE CAUSES
SOLUTION
1. Are refrigerant lines free of contact with surfaces?
YES
2. Is the condenser fan blade obstructed or damaged?
NO
3. Is the evaporator fan blade obstructed or damaged?
NO
4. Is compressor noisy?
NO
5. Consult the Dixie -Narco Factory Service at 1-800-688-9090 or your
Dixie-Narco Representative.
NOTE: Have the vender Model & Serial number available.
1. NO,
reposition tubing.
2. YES,
free any obstructions or
check the blade if needed.
3. YES,
free any obstructions or
check the blade if needed.
4. YES,
check.
Содержание Pre SRS 90 SP
Страница 9: ...SERIES 90 SINGLE PRICE TROUBLESHOOTING Page 34 of 23...
Страница 14: ...SERIES 90 SINGLE PRICE TROUBLESHOOTING Page 39 of 23...
Страница 15: ...SERIES 90 SINGLE PRICE TROUBLESHOOTING Page 40 of 23...
Страница 16: ...SERIES 90 SINGLE PRICE TROUBLESHOOTING Page 41 of 23...
Страница 20: ...REFRIGERATION TROUBLESHOOTING Page 80 of 23 NOTE Have vender Model Serial number available...