1592020110 XR01-02CX GB r1.2 24.07.2015 

                           XR01-02CX 

2/3 

 

7. 

PARAMETERS 

REGULATION 

 

Hy  Differential: 

(0,1°C 

 25°C / 1°F ÷ 45°F) Intervention differential for set point. Compressor Cut 

IN is SET POINT + differential (Hy). Compressor Cut OUT is when the temperature reaches the 

set point. 

LS  Minimum SET POINT:

 (-55°C÷SET/-67°F÷SET): Sets the minimum value for the set point.. 

US  Maximum SET POINT:

 (SET÷99°C/ SET÷99°F). Set the maximum value for set point. 

ot  First  probe  calibration: 

(-9.9÷9.9°C  /-17÷17°F)  allows  to  adjust  possible  offset  of  the  first 

probe. 

od  Outputs activation delay at start up:

 (0÷99min) This function is enabled at the initial start up of 

the instrument and inhibits any output activation for the period of time set in the parameter.  

AC   Anti-short  cycle  delay

:  (0÷50  min)  minimum  interval  between  the  compressor  stop  and  the 

following restart. 

Cy  Compressor ON time with faulty probe: 

(0÷99 min) time during which the compressor is active 

in case of faulty thermostat probe. With Cy=0 compressor is always OFF. 

Cn  Compressor OFF time with faulty probe: 

(0÷99 min) time during which the compressor is OFF 

in case of faulty thermostat probe. With Cn=0 compressor is always active. 

CH  Kind of Action:

 

cL

= cooling action; 

Ht

 = heating action. 

 

DISPLAY 

 

CF  Measurement unit: 

(°C÷°F) 

°C

 =Celsius; 

°F

 =Fahrenheit. 

WARNING

: When the measurement 

unit is changed the SET point and the values  of the parameters  Hy, LS, US, oE, o1, AU, AL 

have to be checked and modified if necessary). 

rE  Resolution (only for °C):

(dE ÷ in) 

dE

= decimal between -9.9 and 9.9°C; 

in

= integer 

dy  Display delay: 

(0

15 min.) when the temperature increases, the display is updated of 1 °C/1°F 

after this time. 

 

DEFROST (Only XR02CX) 

 

id  Interval  between  defrost  cycles: 

(0÷99  ore)  Determines  the  time  interval  between  the 

beginning of two defrost cycles.  

Md  Maximum length for defrost: 

(0÷99 min. with 0 no defrost) when 

P2=n

, (not evaporator probe: 

timed defrost) it sets the defrost duration, when 

P2 = y

 (defrost end based on temperature) it sets 

the maximum length for defrost. 

dF  Display during defrost: 

(rt / it / SP / dF) 

rt=

 real temperature; 

it=

 start defrost temperature; 

St=

 

SET-POINT; 

dF=

 label 

dF. 

 

ALARMS

 

 

AU  Maximum temperature alarm: 

(AL÷99°C/99°F) when this temperature is reached  the alarm is 

enabled, after the “

Ad

” delay time. 

AL  Minimum temperature alarm: 

(-55÷AU°C /-67÷AU°F) when this temperature is reached  the 

alarm is enabled, after the “

Ad

” delay time. 

Ad  Temperature alarm delay:

 (0÷99 min) time interval between the detection of an alarm condition 

and alarm signalling. 

dA  Exclusion of temperature alarm at startup: 

(0÷99 min) time interval between the detection of 

the temperature alarm condition after instrument power on and alarm signalling. 

DIGITAL INPUT 

 

iP   Digital input polarity:

 (oP ÷ cL) 

oP

= activated by closing the contact; 

cL

= activated by opening 

the contact; 

iF  Digital  input  configuration: 

(EA/bA/do/dF/Au/Hc)

  EA= 

external  alarm:  “EA”  message  is 

displayed; 

bA

= serious alarm “CA” message is displayed; 

do

= door switch function; 

dF

= defrost 

activation; 

Au 

=not used; 

Hc=

 inversion of the kind of action; 

di  Digital input delay:

 (0÷99 min) with 

iF=EA

 or 

bA

 delay between the detection of the external 

alarm condition and its signalling. . With 

iF=do

 it represents the delay to activate the door open 

alarm. 

dC  Compressor and fan status when open door

: (no/Fn/cP/Fc): 

no

= normal; 

Fn

 = Fans OFF; 

cP

 

=Compressor OFF; 

Fc

 = Compressor and fans OFF; 

rd

 

Regulation with door open

: (n÷y) 

n

 = no regulation if door is opened; 

Y

= when di is elapsed 

regulation restarts even if door open alarm is present; 

OTHER 

 

Pt   Parameter code table 

rL   Software release 

8. 

DIGITAL INPUTS 

The free voltage digital input is programmable in different configurations by the “

iF

” parameter. 

 

DOOR SWITCH (iF=do) 

 

It signals the door status and the corresponding relay output status through the “

dC

” parameter: 

no

 = 

normal (any change); 

Fn

 = Fan OFF; 

CP

 = Compressor OFF; 

FC

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “

di

”, the door alarm is enabled, 

the display shows the message “

dA

” and 

the regulation restarts if rd = y.

 The alarm stops as soon 

as the external digital input is disabled again. With the door open, the high and low temperature alarms 

are disabled. 

 

EXTERNAL ALARM (iF=EA) 

 

As soon as the digital input is activated the unit will wait for “

di

” time delay before signalling the “

EA

” 

alarm message.  The outputs status don’t change.  The alarm stops just after the digital input  is de-

activated. 

 

SERIOUS ALARM (iF=bA) 

When  the  digital  input  is  activated,  the  unit  will  wait  for  “

di

”  delay  before  signalling  the  “

CA

”  alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-

activated. 

 

START DEFROST (iF=dF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 

restart only if the digital input is disabled otherwise the instrument will wait until the “

dd

” safety time is 

expired. 

INVERSION OF THE KIND OF ACTION: HEATING - COOLING  (iF=Hc) 

 

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

9. 

INSTALLATION AND MOUNTING 

 

The  instruments  shall  be  mounted  on  vertical  panel,  in  a  29x71 

mm hole, and fixed using the special bracket supplied. 
The temperature range allowed for correct operation is 0

60 °C. 

Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 

excessive dirt or humidity. The same recommendations apply to 

probes. Let air circulate by the cooling holes. 
 

 

10.  ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 

mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 

requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the 

power connections. Do not  exceed the maximum current  allowed on  each relay, in case of  heavier 
loads use a suitable external relay. 

10.1

 

PROBES 

 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 

infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 

measure the average room temperature. Place the defrost termination probe among the evaporator 

fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 

defrost, to prevent premature defrost termination. 

11.  HOW TO USE THE HOT KEY 

11.1

 

HOW TO PROGRAM THE HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “Hot key” and push 

 key; the  "

uP

" message appears 

followed a by flashing “

En

” 

3.

 

Push “

SET

” key and the “

En

” will stop flashing. 

4.

 

Turn OFF the instrument remove the “Hot Key”, then turn it ON again. 

 

NOTE

: the “

Er

” message is displayed for failed programming. In this case push again o key if you want 

to restart the upload again or remove the “Hot key” to abort the operation. 

11.2

 

HOW TO PROGRAM AN INSTRUMENT USING HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle

 and then turn the Controller ON. 

3.

 

Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the 

do

” message is blinking followed a by flashing “

En

”. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “Hot Key”.. 

 

NOTE

: the “

Er

” message is displayed for failed programming. In this case push again o key if you want 

to restart the upload again or remove the “Hot key” to abort the operation. 

12.  ALARM SIGNALLING 

Mess.  Cause 

Outputs 

"P1"  

Room probe failure 

Compressor output according to “Cy” e “Cn”  

"P2"  

Evaporator probe failure 

Defrost end is timed 

"HA" 

Maximum temperature alarm 

Outputs unchanged 

"LA" 

Minimum temperature alarm 

Outputs unchanged 

“EA” 

External alarm 

Outputs unchanged 

“CA” 

Serious external alarm 

All outputs OFF. 

“dA” 

Door Open 

Compressor and fans restarts  

12.1

 

ALARM RECOVERY 

Probe alarms 

P1

” and “

P2”

 start some seconds after the fault in the related probe; they automatically 

stop some seconds after the probe restarts normal operation. Check connections before replacing the 

probe. Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the temperature returns to 

normal values. 

Alarms 

“EA”

 and 

“CA” 

(with iF=bL)

 

recover as soon as the digital input is disabled. 

13.  TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: 

frontal 32x74 mm; depth 50mm; 

Mounting: 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20; 

Frontal protection: 

IP65 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power supply: 

according to the model: 110Vac 

10%, 50/60Hz --- 230Vac 

10%, 50/60Hz

 

Power absorption: 

3.5 VA max

 

Display

: 2 digits, red LED, 14,2 mm high; 

Inputs

: 1 NTC.

 

Digital input: 

free voltage contact 

Relay outputs: compressor 

SPST 20(8)A 250Vac or 8(3) A 250Vac; 

 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

2; 

Software class: 

A.;  

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II 

 

Operating temperature: 

0÷60 °C; 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range: NTC 

-40÷110°C; 

 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable); 

Accuracy (ambient temp. 25°C)

:  ±0,1 °C ±1 digit 

 

 

 

 

 

 

 

 

 

 