background image

 

 

1592010320 XJ200 GB r1 3 24 10 2014-FCC 

XJ200

 

2 / 3 

 

4.2.2  FIXING WITH THE USE OF A BRACKET  

A suitable fastening bracket is included in every package to be used to: 

a.

 

shelves mount fitting; 

b.

 

pipemount fitting with appropriate retaining clamps (not supplied) 

c.

 

wall mount fittin 

as shown in the following pictures: 

 

!!!!!ATTENTION!!!!! 

Set the XJ200 in the desired place in a 

VERTICAL POSITION

 

Avoid

 horizontal or slanting positions.  

 

RIGHT FIXING MODE 

RIGHT FIXING MODE 

 

 

 
 

Parts required for assembly (not supplied) 

 

 

 

1.

 

Fix the XJ200 to the fixing bracket using the 2 screws in the package 

2.

 

The 2 screws are to be entered in holes “A” as shown in Fig. 1. 

3.

 

The  bracket  can  be  bent  and  fixed  so  that  the  XJ200  is  installed  in  a  vertical 
position. 

 

4.3

 

RECOMMENDATIONS FOR PROPER INSTALLATION 

 

If  possible,  place  the  module  high  up  in  order  to  guarantee  enhanced  data 

transmission/reception.  

 

If  possible,  avoid  intermediate  obstacles  such  as  barriers,  walls,  floors  and 

counters between the modules.  

 

If necessary, pass through the obstacle using the cable and install the module on 

the  opposite  side  in  order  to  have  it  in  direct  view  with  the  master  module 

connected to the X-WEB. 

 

The maximum distance possible between the XJ200 modules in an open space 

(with no obstacles) is 200 metres.  

 

If the installation spans over a number of floors, try to position all the modules on 

the  same  floor  and  connect  the  devices  via  cable  in  order  to  prevent 
communication problems due to obstacles caused by the floor/ceiling. 

 

The allowed temperature range for correct functioning is between 0 and 60 °C. 

Avoid  places  subject  to  heavy  vibrations,  corrosive  gas,  excessive  filth  or 
humidity. 

 

5.

 

CONNECTIONS 

 

Each module is supplied complete with 

a 1.5-metre cable to connect the serial 
communication line and the power line.  

The XJ200 is powered by the PW-200J 
power  supplier  and  therefore,  it  is 

connected to the RS485 serial line. The 
following  types  of  connection  are 

possible. 

 

6.

 

X-WEB - XJ200 MASTER CONNECTION 

6.1

 

TRANSFORM THE XJ200 TO MASTER 

The XJ200 connected to the X-WEB must be configured as Master. 
To do so: 

a.

 

Remove the cover of the XJ200. 

b.

 

Close the jumper found inside the XJ200 by inserting the micro switch as 

shown in the picture below. 

 

 

 

c.

 

Close the cover of the XJ200 once again. 

d.

 

Connect the XJ200, PW200J and the X-WEB as shown in the connection 

diagram below. 

 

6.2

 

XJ200 –X-WEB CONNECTION 

XJ200 and PW-200J connection 

a.

 

Disconnect the power supply from the PW200J 

b.

 

Connect the GREEN wire to the RS485 “+” terminal of the PW-200J 

c.

 

Connect the PINK wire to the RS485 “-” terminal of the PW-200J 

d.

 

Connect the white connector to the "+5V supply" connector of the PW-200J 

 

 

 

 
 

XJ200 and X-WEB connection 

Use  the disconnecting  terminal  supplied  with  the  PW-200J as  a bridge  of  the RS485 

line. 
The connection between the XJ200 and X-WEB is then implemented as follows: 

Connect the GREEN wire of the XJ200 to the RS485 “+” terminal of the X-WEB 
Connect the PINK wire of the XJ200 to the RS485 “-” terminal of the X-WEB 

 
Power the X-WEB and the PW200J once again. 

7.

 

XJ200 CONNECTION AND DEVICES EQUIPPED WITH A SERIAL 

OUTPUT 

7.1

 

DEVICE EQUIPPED WITH AN RS485 SERIAL OUTPUT 

7.1.1  Device  with  an  RS485  output  but  not  able  to  power  the 
XJ200. 

E.G.

 Ranges: XR100C; XR500C; XR75CX and XR77CX. 

XJ200 and PW-200J connection 

Отзывы: