dixell XH460L Скачать руководство пользователя страница 4

Dixell

 

Operating instructions 

1592002910

 

 

1592002910 XH460L GB R1.0 18.05.04 

 

XH460L 

4/5 

9.4

 

PRESSURE SWITCH (I2F = PAL) 

If  during  the  interval  time  set  by  “

did

”  parameter,  the  pressure  switch  has  reached  the  number  of 

activation of  the “

nPS

” parameter, the “

PAL

” pressure alarm message will be displayed. The compressor 

and the regulation are stopped. When the digital input is ON the compressor is always OFF. 

If the nPS activation in the did time is reached, switch off and on the instrument to restart normal 
regulation. 

9.5

 

HEATING RELAY SAFETY (i1F=Ht) 

With 

i1F=Ht 

as soon as the digital input is activated for “

did

”  time heating relay is disabled. 

The alarm will stop as soon as the digital input is de-activated. 

9.6

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameters. 

 

CL

 : the digital input is activated by closing the contact.

 

 

OP

 : the digital input is activated by opening the contact 

10.

 

INSTALLATION AND MOUNTING 

Instruments 

XW240L 

shall  be  mounted  on  vertical  panel,  in  a  150x31  mm  hole,  and  fixed  using  two 

screws   3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L).  
The  temperature  range  allowed  for  correct  operation  is  0  -  60  °C.  Avoid  places  subject  to  strong 
vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let 
the air circulate by the cooling holes. 

 

 

10.1

 

XH460L: CUT OUT 

 

165

150

31

+0.5

-0

+0

.5

-0

+1

-1

Ø3 x2

 

11.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 
mm

for the digital and analogue inputs. Relays and power supply have a Faston connection (6,3mm). 

Heat-resistant cables have to be used. Before connecting cables make sure the power supply complies 
with the instrument’s requirements. Separate the probe cables from the power supply cables, from the 
outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case 
of heavier loads use a suitable external relay. 

N.B.

 Maximum current allowed for all the loads is 20A. 

11.1

 

PROBE CONNECTIONS 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It 
is recommended to place the thermostat probe away from air streams to correctly measure the average 
room temperature. 

12.

 

HOW TO USE THE HOT KEY  

12.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message appears 

followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

 key if you want 

to restart the upload again or remove the “

Hot key

” to abort the operation. 

12.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn the Controller ON. 

3.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Controller memory, the 

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then on if 

you want to restart the download again or remove the “

Hot key

” to abort the operation. 

13.

 

ALARM SIGNALLING 

Message  Cause 

Outputs 

“P1”  

Thermostat probe failure 

Compressor and heating outputs off 

“P2”  

Evaporator probe failure 

Defrost and by time 

“P3” 

Humidity  probe failure 

Humidity regulation off 

“HA” 

High temperature alarm 

Outputs unchanged 

“LA” 

Low temperature alarm 

Outputs unchanged 

“HHA”  High humidity alarm 

Outputs unchanged 

“HLA”  Low humidity alarm 

Outputs unchanged 

“dA” 

Door switch alarm 

Outputs depending on the odC parameter 

“EAL”  External alarm 

Other outputs unchanged 

“BAL”  Serious external alarm 

Outputs OFF 

“PAL”  Pressure switch alarm 

Outputs OFF

 

 
The alarm message is displayed until the alarm condition recoveries. 

All the alarm messages are showed alternating with the room temperature except for the “

P1

” which is 

flashing. To reset the “EE” alarm and restart the normal functioning press any key, the “

rSt

” message is 

displayed for about 3s. 

13.1

 

SILENCING BUZZER 

Once the alarm signal is detected the buzzer, if present, can be silenced by pressing any key.  

13.2

 

ALARM RECOVERY 

Probe  alarms

  :  “

P1

”  (probe1  faulty),  “

P2

”,  “

P3

”;  they  automatically  stop  10s  after  the  probe  restarts 

normal operation. Check connections before replacing the probe. 

Temperature alarms

 “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature returns to 

normal values or when the defrost starts. 

Humidity alarms

 “

HHA

” and “

LHA

” automatically stop as soon as the humidity returns to normal values. 

Door switch alarm

 “

dA

”  stop as soon as the door is closed. 

External alarms

 “

EAL

”, “

BAL

”  stop as soon as the external digital input is disabled  

Pressure switch alarm 

PAL” alarm is recovered by switching OFF the instrument

14.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: XH460L: 

facia 38x185 mm; depth 76mm;  

Mounting:  XH460L:

  panel  mounting  in  a  150x31  mm  panel  cut-out  with  two  screws.    3  x  2mm. 

Distance between the holes 165mm 

Protection: 

IP20.

 

Frontal protection:

 IP65 with optional frontal gasket mod. RG-L (XH460L);  

Connections: 

Screw terminal block   2,5 mm

2

 heat-resistant wiring and 6,3mm Faston 

Power supply: 

230Vac or 110Vac   10%; 

Power absorption: 

7VA max.

 

Display

: double d icons.  

Inputs

: 1 NTC probe +  4÷20mA probe 

Digital input

: 1 free voltage 

Relay outputs: compressor:

  relay SPST 20(8) A, 250Vac;  

heather: 

relay SPST 8(3) A, 250Vac;  

defrost: 

relay SPST 8(3) A, 250Vac  

fans:

 relay SPST 8(3) A, 250Vac; 

humidifier:

 relay SPST 8(3) A, 250Vac  

de-humidifier:

 relay SPST 8(3) A, 250Vac  

Other output :

 alarm buzzer  (optional) 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B.; 

Pollution grade: 

normal; 

Software class: 

A.

 

Operating temperature: 

0÷60 °C.; 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20 85% (no condensing) 

Measuring and regulation range:  

NTC probe: 

-40÷110°C (-58÷230°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

15.

 

WIRING CONNECTIONS 

15.1

 

XH460L 

R

oo

m

11

9 10

12 13

17

16

18 19

21 22 23

14 15

L

N

Comp

20(8)A

250V

~

6

2

7

3

8

4

5

1

Fan

8(3)A

250V

~

8(3)A

250V

~

8(3)A

250V

~

8(3)A

250V

~

D

ef

20

Heater

Hum

8(3)A

250V

~

Def

NC

 

Supply 115Vac

: 14-15 terminals 

16.

 

DEFAULT SETTING VALUES  

 

 

Set temperature 

Set humidity 

Duration 

Freezing Phase 

5.0 °C 

50.0 RH% 

5.00 h 

Proving Phase 

5.0 °C 

50.0 RH% 

5.00 h 

 
 

Label  Value  Menu 

Description 

Range 

dbt 

2.0 

Pr1 

Half dead band width for temperature 

0.1°C o 1°F ÷ 25°C o 77°F 

dbH 

5.0 

Pr1 

Half dead band width for humidity 

0.5 ÷ 50 

LS 

-40.0 

Pr2 

Minimum temperature set point limit 

-50.0°C o –58°F ÷ Set T  

uS 

110 

Pr2 

Maximum temperature set point limit 

Set T ÷  110°C o 230°F  

odS 

Pr2 

Outputs activation delay at start up 

0 ÷ 250 min 

Ac 

Pr1 

Anti-short cycle delay 

0 ÷ 30 min 

tHu 

c-H 

Pr2 

Humidity regulation 

db 

= dehumidifier relay.; 

cHu

 

= dehum+ compr.; 

c-H= 

without dehum. relay 

LSH 

0.0 

Pr2 

Minimum humidity set point limit 

Lci ÷ Set H  

uSH 

100 

Pr2 

Maximum humidity set point limit 

Set H ÷ uci 

cF 

°C 

Pr2 

Measurement unit 

°C ÷°F 

rES 

dE 

Pr2 

Resolution (for °C): 

in = integer / dE = decimal 

rEH 

Hd 

Pr2 

Resolution for RH%: 

in = integer / Hd = half digit 

trC 

co 

Pr2 

Instrument behaviour at the end of the cycle 

co

=start hoolding, 

in

=stop 

regulation, 

cL

=restart the first 

phase+End message; 

cLE

 = 

restart the first phase 

tdf 

rE 

Pr2 

Defrost type 

rE,  rT,  in  

EdF 

in 

Pr2 

Defrost mode 

In, Sd 

SdF 

0.0 

Pr2 

Set point for SMART DEFROST 

-30 ÷ +30°C / -22÷+86°F 

dtE 

8.0 

Pr2 

Defrost termination temperature  

-50,0÷110°C/ -58÷230°F 

idF 

Pr1 

Interval between defrosts 

1 ÷ 120 h 

MdF 

20 

Pr1 

Duration of defrost 

0 ÷ 250 min 

dFd 

it 

Pr2 

Display during defrost 

rt / it / SEt / dEF / dEG 

dAd 

30 

Pr2 

Defrost display time out 

0 ÷ 250 min 

Содержание XH460L

Страница 1: ...ng temp SET_T dbt and dehumidifying RH SET_RH dbH the cooling action has the priority over the dehumidifying action only the compressor relay is energised till the SET_T is reached at this point also the heating relay is enabled 2 If is simultaneously present a request of heating temp SET_T dbt and dehumidifying RH SET_RH dbH the dehumidifying action has the priority over the heating action both t...

Страница 2: ... The defrost is enabled LED 3 FLASHING Drip time in progress LED 2 FLASHING Programming Phase flashing with LED3 ON Heating enabled temp FLASHING Temperature Set programming phase ON ALARM signal ON Fan is running ON RH ON Dehumidifying enabled ON Humidifying enabled umid FLASHING Humidity Set programming phase ON Freezing phase is in progress FLASHING Proving phase is in progress FLASHING Setting...

Страница 3: ...etection of an alarm condition and the corresponding alarm signalling dAO Delay of temperature alarm at start up 0min 23h 50min time interval between the detection of the temperature alarm condition after the instrument power on and the alarm signalling EdA Alarm delay at the end of defrost 0 255 min Time interval between the detection of the temperature alarm condition at the end of defrost and t...

Страница 4: ...Outputs unchanged dA Door switch alarm Outputs depending on the odC parameter EAL External alarm Other outputs unchanged BAL Serious external alarm Outputs OFF PAL Pressure switch alarm Outputs OFF The alarm message is displayed until the alarm condition recoveries All the alarm messages are showed alternating with the room temperature except for the P1 which is flashing To reset the EE alarm and ...

Страница 5: ...arm delay 0 250 min dHo 1 3 Pr2 Delay of humidity alarm at start up 0 0 23 5 h doH 20 Pr2 Alarm delay at the end of defrost 0 250 min doA 20 Pr2 Open door alarm delay 0 250 min 250 nu tbA oFF Pr2 Relay status after pushing a key on oFF nPS 15 Pr2 Pressure switch number 0 15 ot 0 0 Pr1 Thermostat probe calibration 12 0 12 0 oE 0 0 Pr2 Evaporator probe calibration 12 0 12 0 o3 0 0 Pr1 Humidity probe...

Отзывы: