dixell XH460L Скачать руководство пользователя страница 2

Dixell

 

Operating instructions 

1592002910

 

 

1592002910 XH460L GB R1.0 18.05.04 

 

XH460L 

2/5 

6.3

 

HOW TO SET THE TARGET TEMPERATURE OF THE FREEZING AND PROVING CYCLE 

1.

 

Push the 

SET_T

 key, the display shows on the upper display the “St1” message, while the “set ” 

icon starts flashing. 

2.

 

Push again the 

SET_T

 the temperature set point of the freezing phase is shown. Set it using the 

UP 

 

and 

DOWN

 keys.  

3.

 

Push again the 

SET_T

 to confirm the value and pass to the setting of the proving phase: the “St2” 

message is displayed. 

4.

 

Push the 

SET_T

 key to see its value and use the 

UP

 and 

DOWN

 keys to set it. 

6.4

 

HOW TO START THE CYCLE 

Push and release 

START

 

 key: the led 

 will be turned ON. 

The 

 led flashes during the proving phase 

 

6.5

 

END OF THE CYCLE   

When  the  timer  has  expired,  the  buzzer  starts  sounding  and  the  bottom  display  shows  the  “

End

” 

message. 
To mute the buzzer push a key: The display come back to show the humidity and the LED of the START 
key is turned off. 
 

6.6

 

HOW TO MODIFY THE SETTING OF THE RUNNING CYCLE. 

To modify the setting of the running cycle temperature (SET_T), humidity (SET_RH) or remaining time 
(CLOCK): 
1.

 

Push twice the corespondent key: the setting value of the current phase (freezing or proving) will be 
displayed.  

2.

 

Modify it using the 

UP 

and 

DOWN 

keys  

3.

 

Confirm  the  value  using  the  corespondent  key:  temperature  (SET_T),  humidity  (SET_RH)  or 
remaining time (CLOCK).  

 

7.

 

THE DISPLAY 

 
 

 

To display and modify target temperature set point. (

SET_T

) for the freezing (St1)and the 

proving (St2) phase. 

 

To  display  and  modify  target  humidity  set  point  (

SET_RH

)  or  the  freezing  (SH1)and  the 

proving (SH2) phase; in programming mode it selects a parameter or confirm an operation. 

 

In programming mode it browses the parameter codes or increases the displayed value. 

 

To start a manual defrost: hold it pressed for at least 3s. 
In programming mode it browses the parameter codes or decreases the displayed value. 

 

Switch ON and OFF the light, if present (oA1=lig) 

 

Start

: to start the cycle 

 

Clock

: to set the duration of the freezing (tM1) and proving (tM2) phase 

 

Switch ON and OFF the instrument. 

 

KEY COMBINATIONS 

 

 

+

 

 

To lock and unlock the keyboard

 

 

+

 

To enter the programming mode.

 

 

+

 

 

To exit the programming mode.

 

7.1

 

ICONS AND SYMBOLS 

Each LED function is described in the following table. 
 

LED2

LED3

LED4

Temperature Display 

Humidity Display 

 

 

LED 

MODE 

FUNCTION 

LED 

MODE 

FUNCTION 

Led 4

 

ON

 

- Instrument in stand by.  
- In “Pr2” indicates that the parameter is also present in “Pr1”. 

 

ON 

°C 

°F

 

ON 

°C 

 

ON 

The compressor is running 

 

FLASHING 

- Anti-short cycle delay enabled 

 

LED 3 

ON 

The defrost is enabled 

 

LED 3

 

FLASHING 

Drip time in progress 

LED 2

 

FLASHING 

Programming Phase (flashing with LED3) 

 

ON 

Heating enabled 

 (temp) 

FLASHING 

Temperature Set programming phase 

 

ON 

- ALARM signal 

 

ON 

Fan is running 

 

ON 

RH% 

 

ON 

Dehumidifying enabled 

 

ON 

Humidifying enabled 

 (umid) 

FLASHING 

Humidity Set programming phase 

 

ON 

Freezing phase is in progress 

 

FLASHING 

Proving phase is in progress 

 

FLASHING 

Setting of the duration of the cycle 

7.2

 

HOW TO SEE AND MODIFY THE SET POINT (TEMPERATURE AND  HUMIDITY) 

 

1.

 

Push  and  immediately  release  the 

SET 

key:  the  display  will  show  the  Set  point 

valueand the correspondant set icon starts flashing; 

2.

 

To change the Set value push the 

or 

n

 arrows within 10s. 

3.

 

To memorise the new set point value push the 

SET

 key again or wait 10s. 

7.3

 

TO START A MANUAL DEFROST 

 

 
1.  Push the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

7.4

 

TO ENTER IN PARAMETERS LIST “PR1” 

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 
 

 

+

 

 
1.

 

Enter  the  Programming  mode  by  pressing  the

  SET_RH

for  few 

seconds. (LED2&3 start flashing) 

2.

 

The instrument will show the first parameter present in “Pr1” 

 
 
 
 

7.5

 

TO ENTER IN PARAMETERS LIST “PR2” 

To access parameters in “

Pr2

”: 

1.

 

Enter the “Pr1” level. 

2.

 

Select “Pr2” parameter and press the “

 SET_RH

 ” key.  

3.

 

The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero. 

4.

 

Use 

o

  or 

n

  to  input  the  security  code  in  the  flashing  digit;  confirm  the  figure  by  pressing  “

 

SET_RH

 ”.  

The security code is “321“. 

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing “

 SET_RH

 ” on the last 

digit. 

 

Another possibility

 is the following: after switching ON the instrument the user can push 

SET_RH

 + 

n

 

keys within 30 seconds. 
 

NOTE

: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing 

SET_RH

 + 

n

When a parameter is present in “Pr1” LED 4 is on. 

7.6

 

TO CHANGE PARAMETER VALUES 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

o

 or 

n

3.

 

Press the “

 SET_RH

 ” key to display its value (LED2&3 start blinking). 

4.

 

Use 

o

 or 

n

 to change its value. 

5.

 

Press “

 SET_RH

 ” to store the new value and move to the following parameter. 

To exit

: Press 

SET_RH

 

+ UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

7.7

 

HOW TO LOCK THE KEYBOARD 

 
 

 

1.  

Keep the 

o

 and 

n

 keys pressed together for more than 3 s the 

o

 and 

n

 keys. 

2.  

The “

POF

” message will be displayed and the keyboard is locked. At this point it is 

only possible the viewing of the set point or the MAX o Min temperature stored and 
to switch ON and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

Keep the 

o

 and 

n

 keys pressed together for more than 3s. 

 

Содержание XH460L

Страница 1: ...ng temp SET_T dbt and dehumidifying RH SET_RH dbH the cooling action has the priority over the dehumidifying action only the compressor relay is energised till the SET_T is reached at this point also the heating relay is enabled 2 If is simultaneously present a request of heating temp SET_T dbt and dehumidifying RH SET_RH dbH the dehumidifying action has the priority over the heating action both t...

Страница 2: ... The defrost is enabled LED 3 FLASHING Drip time in progress LED 2 FLASHING Programming Phase flashing with LED3 ON Heating enabled temp FLASHING Temperature Set programming phase ON ALARM signal ON Fan is running ON RH ON Dehumidifying enabled ON Humidifying enabled umid FLASHING Humidity Set programming phase ON Freezing phase is in progress FLASHING Proving phase is in progress FLASHING Setting...

Страница 3: ...etection of an alarm condition and the corresponding alarm signalling dAO Delay of temperature alarm at start up 0min 23h 50min time interval between the detection of the temperature alarm condition after the instrument power on and the alarm signalling EdA Alarm delay at the end of defrost 0 255 min Time interval between the detection of the temperature alarm condition at the end of defrost and t...

Страница 4: ...Outputs unchanged dA Door switch alarm Outputs depending on the odC parameter EAL External alarm Other outputs unchanged BAL Serious external alarm Outputs OFF PAL Pressure switch alarm Outputs OFF The alarm message is displayed until the alarm condition recoveries All the alarm messages are showed alternating with the room temperature except for the P1 which is flashing To reset the EE alarm and ...

Страница 5: ...arm delay 0 250 min dHo 1 3 Pr2 Delay of humidity alarm at start up 0 0 23 5 h doH 20 Pr2 Alarm delay at the end of defrost 0 250 min doA 20 Pr2 Open door alarm delay 0 250 min 250 nu tbA oFF Pr2 Relay status after pushing a key on oFF nPS 15 Pr2 Pressure switch number 0 15 ot 0 0 Pr1 Thermostat probe calibration 12 0 12 0 oE 0 0 Pr2 Evaporator probe calibration 12 0 12 0 o3 0 0 Pr1 Humidity probe...