1592009241 XW40L-V GB r1.0 04.05.2011 

                           XW40L – XW40V 

1/4 

W

ING

 

XW40L – XW40V 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot 
be used as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the  operating  limits  avoiding 
sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of 
condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel 
with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model  XW40L,  38x185  mm  format,  and  model  XW40V,  100x64  format,    are  microprocessor  based 
controllers suitable for applications on medium or low temperature refrigerating units. They are provided 
with 3 relay outputs to control compressor, defrost - which can be either electrical or hot gas  - and the 
lights.  They  are  also  provided  with  2  NTC  or  PTC  probe  inputs,  one  for  temperature  control,  one  to 
control  the  defrost  end  temperature  of  the  evaporator.  There  are  1  digital  inputs  (free  contact) 
configurable by parameter. 
An  output allows the user to programme the parameter list with the “Hot Key”. 

3.

 

CONTROLLING LOADS 

3.1

 

THE COMPRESSOR 

The  regulation  is  performed  according  to  the  temperature  measured  by  the  thermostat  probe  with  a 
positive differential from the set point: if the temperature increases and reaches set point plus differential 
the compressor is started and then turned off when the temperature reaches the set point value again. 
In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters “COn” and “COF”. 

3.2

 

FAST FREEZING 

When defrost is not in progress, it can be activated the keypad by holding the 

o

 key pressed for about 

3 seconds. The compressor operates in continuous mode for the time set through the “CCt” parameter. 
The cycle can be terminated before the end of the set time using the same activation key, 

o

 for about 

3 seconds. 

3.3

 

DEFROST 

Two defrost modes are available through the “tdF” parameter: defrost with electrical heater or hot gas. 
The  defrost  interval  is  control by means of parameter “EdF”: (EdF=in) the defrost is made every “IdF” 
time,  (EdF=Sd)  the  interval  “IdF”  is  calculate  through  Smart  Defrost  algorithm  (only  when  the 
compressor is ON and the evaporator temperature is bigger than “SdF” parameter). 
At the end of defrost the drip time is controlled through the “Fdt” parameter. 
 

4.

 

KEYBOARD 

 

 

 

 

 

To  display  and  modify  target  set  point;  in  programming  mode  it  selects  a  parameter  or 
confirm an operation.  
By holding it pressed for 3s when max or min temperature is displayed it will be erased. 
 

 

To  see  the  max.  stored  temperature;  in  programming  mode  it  browses  the  parameter 
codes or increases the displayed value. By holding it pressed for 3s the fast freezing  cycle 
is started. 

 

To see the min stored temperature; in programming mode it browses the parameter codes 
or decreases the displayed value. 
 

 

 
By holding it pressed for 3s the defrost is started. 
 

 

 
Switch ON and OFF the light of the cold-room 

 

 
Switch ON and OFF the instrument. 

 
KEY COMBINATIONS 

 

 

 

 
To lock and unlock the keyboard. 

 

 

 
To enter the programming mode. 
 

 

 

 
To exit the programming mode. 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

 

ON 

The compressor is running 

 

FLASHING 

- Programming Phase (flashing with LED 

- Anti-short cycle delay enabled 

 

FLASHING 

Programming Phase (flashing with LED 

 

ON 

The defrost is enabled 

 

FLASHING 

Drip time in progress 

 

ON 

The Fast Freezing cycle is enabled 

  

ON 

- ALARM signal 
- In “Pr2” indicates that the parameter is also present in “Pr1” 

 

ON 

The light is on 

 

4.2

 

HOW TO SEE THE MIN TEMPERATURE 

 

1.  

Press and release the 

n

 key. 

2.  

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

By pressing the 

n

 key or waiting for 5s the normal display will be restored. 

4.3

 

HOW TO SEE THE MAX TEMPERATURE 

 

1.  

Press and release the 

o

 key. 

2.  

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

By pressing the 

o

 key or waiting for 5s the normal display will be restored. 

4.4

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

To reset the stored temperature, when max or min temperature is displayed : 
1.

 

Press SET key until “rST” label starts blinking. 

 
N.B. After the installation RESET the temperature stored . 

4.5

 

HOW TO SEE AND MODIFY THE SET POINT 

 

 

1. 

Push and immediately release the SET key: the display will show the Set point value; 

2. 

The SET LED start blinking; 

3. 

To change the Set value push the 

or 

n

 arrows within 10s. 

4. 

To memorise the new set point value push the SET key again or wait 10s. 

4.6

 

TO START A MANUAL DEFROST  

 

 
1. 

Push the DEF key for more than 2 seconds and a manual defrost will start. 

4.7

 

TO ENTER IN PARAMETERS LIST “PR1”  

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 

 

1.  Enter the Programming mode by pressing the Set and DOWN key for few 

seconds (

 and 

 start blinking). 

2. 

The instrument will show the first parameter present in “Pr1” 

 