XW260
5/5
ALARMS
ALC Temperature alarms configuration
rE÷Ab
rE
Pr2
ALU MAXIMUM temperature alarm
-50,0÷110°C / -58÷230°F
10/20
Pr1
ALL minimum temperature alarm
-50,0÷110°C / -58÷230°F
10/20
Pr1
AFH Temperature alarm and fan
differential
0,1÷25,5 °C / 1÷45°F
2/4
Pr2
ALd Temperature alarm delay
0÷255 min.
15
Pr2
dAO Delay of temperature alarm at start
up
0 ÷ 23h 50 min.
1,3
Pr2
EdA Alarm delay at the end of defrost
0÷255 min.
30
Pr2
dot Delay of temperature alarm after
closing the door
0÷255 min.
15
Pr2
dOA Open door alarm delay
0÷255 min.
15
Pr2
nPS Pressure switch activation number
0÷15
0
Pr2
ANALOGUE
INPUTS
Ot
Thermostat probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr1
OE
Evaporator probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr2
O3
Auxiliary probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr2
P2P Evaporator probe presence
n ÷ y
y
Pr2
P3P Auxiliary probe presence
n ÷ y
n
Pr2
HES Temperature increase during the
Energy Saving cycle
-30÷30°C / -22÷86°F
0
Pr2
DIGITAL INPUTS
Odc Open door control
No, Fan, CPr, F_C
Fan
Pr2
I1P Door
switch
polarity
CL÷OP
CL
Pr2
I2P
Configurable digital input polarity
CL÷OP
CL
Pr2
i2F
Digital input configuration
EAL, bAL, PAL, dFr, AUS,
ES, OnF
EAL Pr2
dId
Digital input alarm delay
0÷255 min.
5
Pr2
OTHER
Adr Serial
address
0÷247
1
Pr1
rEL
Software release
- - -
- - -
Pr2
Ptb
Map code
- - -
- - -
Pr2
Prd
Probes display
Pb1÷Pb3
- - -
Pr2
Pr2
Access parameter list
- - -
- - -
Pr1