IC100C Series
PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 2 di 38
INDEX
1. General
Advices__________________________ 2
2. User
Interface ____________________________ 3
3. Key
Function ____________________________ 3
4. Keyboard
Leds___________________________ 4
5.
Remote Keyboard VI610 ___________________ 4
6. Normal
Condition
read-out _________________ 4
7.
Silencing the Buzzer ______________________ 5
8. First
Installing ___________________________ 5
9.
How to Set the Clock RTC__________________ 5
10. “ Hot Key” Programming __________________ 5
11. Keyboard
Programming ___________________ 5
12. Change the Password _____________________ 6
13. Value of Display Read–Out Par. CF36 ________ 6
14. Start / Stop Chiller or Heat Pump ____________ 7
15. Stand- By Function _______________________ 7
16. “M key” the Function Menu_________________ 7
17. Keyboard
Functions ______________________ 8
18. How to Turn a Compressr in Off-Line ________ 8
19. Dynamic Set Point ________________________ 8
20. Energy
Saving ___________________________ 9
21. Compressor
Functioning __________________ 9
22. Condenser Fan Regulation ________________ 10
23. Hot Start Function _______________________ 11
24. Automatic Change - Over _________________ 11
25. Defrost
Function ________________________ 11
26. Relay
Configuration______________________ 12
27. Data
Logger ____________________________ 12
28. Boiler
Function__________________________ 12
29. Maintenance
Function ____________________ 12
30. Black
Out ______________________________ 12
31. Installing and Mounting___________________ 12
32. Electrical
Wiring_________________________ 13
33. Alarm Code and Events___________________ 14
34. Output Lock for Alarm Event Table _________ 17
35. Connecting
Diagram _____________________ 18
36. Parameter
description ____________________ 19
37. Parameter
Table _________________________ 27
38. Technical
Data __________________________ 38
1.
G
ENERAL
A
DVICES
•
Please read before using this manual
•
This manual is part of the product and should be kept near the
instrument for easy and quick reference.
•
The instrument shall not be used for purposes different from
those described hereunder. It cannot be used as a safety
device.
•
Check the application limits before proceeding.
1.1
Safety Precaution
•
Check the supply voltage is correct before connecting the
instrument.
•
Do not expose to water or moisture: use the controller only
within the operating limits avoiding sudden temperature
changes with high atmospheric humidity to prevent
formation of condensation
•
Warning: disconnect all electrical connections before any
kind of maintenance.
•
Fit the probe where it is not accessible by the End User. The
instrument must not be opened.
•
In case of failure or faulty operation send the instrument
back to the distributor or to “Dixell s.r.l.” (see address) with a
detailed description of the fault.
•
Consider the maximum current which can be applied to each
relay (see Technical Data).
•
Ensure that the wires for probes, loads and the power supply
are separated and far enough from each other, without
crossing or intertwining.
•
In case of applications in industrial environments, the use of
mains filters (our mod. FT1) in parallel with inductive loads
could be useful.