1592022010 Quick reference guide iCHILL 100CX EVO rel. 1.0
32/40
17.8
PROPORTIONAL OUTPUT
0..10
V TO CONTROL DUMPER MOTORS
OUT1…OUT4
= signals for the modulation of the dumper motor
GND
= ground
If the dumper motor has a common
line between a pole of the power supply and the “–“ pole of the 0..10V
signal, it is necessary to use two transformers for the power supply of the controller Ichill and the power supply
of the dumper motor.