1592022760 Quick reference guide iCHILL 200CX EVO rel. 1.0
20/40
14
TABLE OF THE OUTPUT STATUS IN ALARM CONDITION
14.1
ALARM:
“A”
TYPE
AND
STATUS
OF
THE
LOADS
IN
CASE
OF
ALARM
Alarm
Code
Alarm
description
Compressor
Anti
freeze
heaters
Boiler
Support
heaters
Evap.
Pump.
Supply
fan
Condenser
Pump
Cond.
Fan
Cir1
Cir2
Auxili
ary
relay
ACF1
..
ACF12
Configuration
alarm
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ACFL
Condenser
flow alarm
OFF
OFF
(3)
OFF
AEE
Eeprom
alarm
OFF
OFF
OFF
OFF
OFF
AEFL
Evaporator
flow alarm
OFF
OFF
(boiler)
OFF
(3)
OFF
AEht
High
water
temperature
inlat
evaporator
OFF
AELt
Low
temperature
of the
evaporator
inlet in Heat
Pump mode
OFF
AHFL
Sanitary
water pump
flow alarm
OFF
(6)
/
/
/
/
/
/
ALc1
Generic
alarm n°1
OFF
OFF
OFF
OFF
OFF