1592022760 Quick reference guide iCHILL 200CX EVO rel. 1.0
15/40
• press the UP or DOWN button to select the submenu;
• press the SET to enter the submenu.
Exit menu functions:
• Press the menu button or wait the time-out.
Entering the menu, it is possbile to:
1. Read and reset the alarms (
ALrM)
2. Read and reset the alarm log (
ALOG)
3. Upload the parameter into the Hot Key (
UPL)
4. Enable
– disable a gas circuit (
CrEn)
5. Enable
– disable a compressors (
COEn)
6. Read and reset the number of compressor running hour (
Hour)
7. Read and reset the number of compressor starts-up (
COSn)
8. Read dynamic set point probe value
(
PbdS
)
9. Read compressor discharge temperature (
COdt)
10. Read condensing fan speed percentage of the proportional output (
Cond)
11. Read the percentage of the proportional output 0 ÷ 10 Vdc
Pout
12. Enable
– disable one of the pumps
POEn
13. Read the delay time between two defrost cycles (
dF)
14.
Read auxiliary output probe value (
uS)
15.
Read the temperature measured by internal sensor of the remote keyboards
(
trEM)
16.
Read the temperature, the set point and the output status of the
Free cooling
(FC)
17.
Read the temperature, the set point and the output status of the Solar panel
(SoL)
18.
Read temperature, pressure and status of the electronic expansion valve 1
(Et1)
19.
Read temperature, pressure and status of the electronic expansion valve 2
(Et2)
11.1
ALARM
LIST:
READ
AND
RESET
ALrM FUNCTION
1.
Push MENU key
2.
The display shows AlrM label
3.
Push
SET
key (Nothing happens if there are not alarms)
4.
The bottom display shows the alarm code and the top display shows the label
rSt,
if it is possible
to reset the alarm, or
NO
if it is not possible to reset the alarm
5.
Push
UP
or
DOWN
to scroll the alarm list (if more than one alarm is active)
6.
Repeat the reset procedure for each alarm
7.
To exit the ALrM reset, push MENU or wait the timeout.
11.2
ALARM
LOG
LIST
ALOG FUNCTION
1.
Push MENU key
2.
Push
UP
or
DOWN
to select ALOG
3.
Push SET key
4.
The bottom display shows the alarm label, the top display shows a number in the range 00 to 99.
5.
Use the UP or DOWN keys to scroll the list.
6.
To exit the ALOG function push MENU or wait the timeout.
Содержание IC200CX Series
Страница 1: ...QUICK REFERENCE GUIDE IC200CX v 1 0 ...
Страница 2: ......
Страница 27: ...1592022760 Quick reference guide iCHILL 200CX EVO rel 1 0 27 40 ...
Страница 35: ...1592022760 Quick reference guide iCHILL 200CX EVO rel 1 0 35 40 ...
Страница 40: ...1592022760 Quick reference guide iCHILL 200CX EVO rel 1 0 40 40 ...