1592022010 Quick reference guide iCHILL 100CX EVO rel. 1.0
10/40
6
OTHER DISPLAY INFORMATION
6.1
READ
THE
SET
POINT
VALUE
Press and release the SET key:
If the unit is on standby:
•
lower display shows SEtC (set chiller);
•
press SET key again, lower display shows SEtH (set heat pump, if it is enabled);
•
press SET key again, lower display shows SEtr (set real of operation, in the case where the Energy
Saving and / or function dynamic set point are active);
•
press SET key again, lower display shows SEtS (set sanitary circuit, in case it is enabled)
If the instrument is in chiller operation:
•
lower display shows SEtC (set chiller);
•
press SET key again, lower display shows SEtr (set real of operation, in the case where the Energy
Saving and / or function dynamic set point are active);
•
press SET key again, lower display shows SEtS (set sanitary circuit, in case it is enabled)
If the instrument is in chiller operation:
•
lower display shows SetH (set heat pump);
•
press SET key again, lower display shows SEtr (set real of operation, in the case where the Energy
Saving and / or function dynamic set point are active);
•
press SET key again, lower display shows SEtS (set sanitary circuit, in case it is enabled)
6.2
MODIFY
THE
SET
POINT
•
push
SET
key for at least
3
seconds
•
use the
UP
or
DOWN
key to modify the setpoint. In chiller mode it is possible to modify the chiller
set point, in heat pump it is possible to modify the heat pump set point, in std-by it is possible to
modify both the set point.
•
push
SET
to confirm or wait the timeout (15seconds).
7
KEY FUNCTION
KEY
ACTION
FUNCTION
Push and release
Show chiller set point
SetC,
heat pump set point
SetH,
sanitay water set point
SetS
Push once again
In chiller or heat pump if the Energy saving or the
Dynamic setpoint are enabled it shows the real
setpoint
Setr.
Push for 3 seconds
Allows to modify the set point